10

The boiler should be located in an area that is inaccessible to 

the general public.

TABLE 1.  Risk of Scalds.

Water Temperature

Time to Produce 2nd & 3rd Degree 

Burns on Adult Skin

over 170°F (77°C)

Nearly instantaneous

160°F (71°C)

About 1/2 second

150°F (66°C) 

About 1-1/2 seconds

140°F (60°C)

less than 5 seconds

130°F (54°C)

About 30 seconds

 120°F (49°C) or less

More than 5 minutes

SHoUlD ovERHEATING oCCUR oR THE GAS SUPPlY FAIl 

To SHUT oFF, TURN oFF THE MAIN MANUAl GAS SHUToFF 

vAlvE To THE APPlIANCE.
The operating temperature of the boiler must be maintained 

as follows:

• 

120°F (49°C) or higher inlet water temperature to the boiler.

• 

20°F (11°C) differential between the boiler’s inlet and 

outlet (e.g. 120°F [49°C] inlet, 140°F [60°C] outlet 

minimum design temperatures).

If the inlet water temperature into the boiler is less than 

120°F (49°C), adjustments on the water bypass are needed. 

Please contact your A.o. Smith qualified service agent.

CONTROL SYSTEM

The EMC modulation control system is a fully integrated, state 

of the art electronic control system. It consists of sensors, output 

devices, a power switch, a 24vAC transformer, wiring, and the 

following printed circuit boards:

•  Modulation Control Board (MCB)
•  Power Distribution Board (PDB)
•  User Interface Module (UIM)
The  MCB  contains  circuitry  for  both  master  control  and  flame 

control. Dip switches on the MCB are used to configure the 

system. The User Interface Module (UIM) communicates with the 

user through a set of touch pads and a 4-line, 20-character lCD 

display. The PDB provides connection points for input power, the 

water pump, and the transformer. It also distributes power to the 

system and contains the system fuses.
The MCB also contains an external communications system to allow 

for connection to a PC, a modem, an EMS system, or something 

similar. Through this connection, multiple boilers can also be 

linked together. 

CAUTION: The internal communications cables 

should never be connected to the external communications 

connectors, and vice-versa.

There are several microcontrollers used on the boards. These 

control the temperature and ignition control functions for 

the boiler. Inherent in the design are the normal operating 

WATER TEMPERATURE REGULATION

HoT WATER CAN SCAlD: Boilers are intended to produce hot 

water. Water heated to a temperature which will satisfy space 

heating, clothes washing, dish washing and other sanitizing needs 

can scald and permanently injure you upon contact. Some people 

are more likely to be permanently injured by hot water than others. 

These include the elderly, children, the infirm or physically/mentally 

disabled. If anyone using hot water in your home fits into one of theses 

groups or if there is a local code or state law requiring a specific 

temperature water at the hot water tap, then you must take special 

precautions. In addition to using the lowest possible temperature 

setting that satisfies your hot water needs, a means such as a mixing 

valve should be used at the hot water taps used by these people or 

at the hot water supply tank. Mixing valves are available at plumbing 

supply or hardware stores. Follow the manufacturer’s instructions 

for installation of the valves. Before changing the thermostat setting 

on the hot water system controller, see Table 1.

Hot  water  temperatures  required  for  automatic  dishwasher 

and laundry use can cause scald burns resulting in serious 

personal injury and/or death. The temperature at which injury 

occurs varies with the person’s age and time of exposure. The 

slower response time of children, aged or disabled persons 

increases the hazards to them. Never allow small children to 

use a hot water tap, or to draw their own bath water. Never leave 

a child or disabled person unattended in a bathtub or shower.

Содержание VF VB 500

Страница 1: ...e any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installati...

Страница 2: ...nces known to the State of California to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical...

Страница 3: ...3 GENERAL SAFETY...

Страница 4: ...trol assembly pro vided on the boiler met safe lighting and other performance criteria Detailed installation diagrams are found in this manual These diagrams will serve to provide the installer a refe...

Страница 5: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Страница 6: ...6 CONNECTION DIAGRAM...

Страница 7: ...7...

Страница 8: ...8 Figure 1 SCHEMATIC DIAGRAM VB VW 500 750 1000 SCHEMATIC DIAGRAM...

Страница 9: ...9 LIGHTING OPERATION INSTRUCTIONS FOR MODELS VB VW 500 750 AND 1000...

Страница 10: ...stem or something similar Through this connection multiple boilers can also be linked together CAUTION The internal communications cables should never be connected to the external communications conne...

Страница 11: ...me rod is missing or shorted the flame will not be detected OUTPUTS FROM MCB Relay Contact Output Alarm MCB 24VAC optional Provides electrical power to operate an external alarm This can be an audio d...

Страница 12: ...u activated screens Within each of the screens helpful information can be displayed by pressing the Help button The LED s visually inform the user about the mode the system is in The touch switches al...

Страница 13: ...jump to the error state Description of FCB control states Idle State When any error is declared during idle state The system will remain in this state until the MCB request a heating cycle or a cold...

Страница 14: ...to change the automatically resettable High Limit Setpoint 1 Press the MENU key 2 Scrollthe withtheDOWNkeynexttoUSERSETTINGSCREEN 3 Press the SELECT key 4 Scroll the with the DOWN key until it is poin...

Страница 15: ...rds in screens to reach a desired item and to change setpoints and user settings They have an auto increment decrement feature for some of the configurations and values When you first press one of the...

Страница 16: ...ected wiring Note The MRHL can be checked by disconnecting the outlet probe from the MCB and reading the resistance across the two active pins on the connectorattheendoftheprobecable Thevalueshouldbea...

Страница 17: ...Give reasonably quiet operation during initial ignition operation and extinction Cause no excessive lifting of flame from burner ports If the preceding burner characteristics are not evident check fo...

Страница 18: ...ible shortened service life BURNER MAINTENANCE Qualified servicers should follow this procedure when the boiler s burner needs cleaning 1 Turn off the electrical power to the boiler and close the main...

Страница 19: ...solidsexist Asthewaterisheated these tendtodropoutdepositingasscaleorlime Thisscalemustberemoved before the heat exchanger tubes become blocked DELIMING The amount of calcium carbonate lime released f...

Страница 20: ...20 notes...

Страница 21: ...21 notes...

Страница 22: ...22 notes...

Страница 23: ...ation for the boiler or any of its parts Some states and provinces do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you 5 CLAIM PROCEDURE Any cla...

Страница 24: ...24 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: