38
GAS CONTROL LED STATUS CODES
LED Flash Sequence
Control Status
Short
fl
ash
once every four
seconds
IDLE (no call for heat,
no fault conditions)
“Heartbeat”,
alternates bright/dim
Call For Heat
(no fault conditions)
One Flash,
three second pause
Low Flame Signal
(control continues to operate)
Two Flash,
three second pause
Pressure Switch Failed
Closed
Three Flash,
three second pause
Pressure Switch Failed Open
Four Flash,
three second pause
TCO Limit Lockout
Five Flash,
three second pause
Flame Out Of Sequence
Six-One Flash,
three second pause
Soft Lockout
– Retry Limit
- Failed TFI
Six-Two Flash,
three second pause
Soft Lockout
- Recycle Limit
- PS/Limit opened
Six-Three Flash,
three second pause
Soft Lockout
- Recycle Limit
- Flame Lost
Six-Four Flash, three
second pause
Soft Lockout
- Flame out of Sequence
Sensed
Seven Flash,
three second pause
Flammable Vapor Sensor
Lockout
Eight-One Flash,
three second pause
FVS Fault Detected
Eight-Two Flash,
three second pause
Temperature Sensor Fault
Detected
Eight-Three Flash,
three second pause
Electronics Fault Detected
Eight-Four Flash,
three second pause
Valve Fault Detected
IGNITION STATE AND TIMING
IGNITION STATE
TIMING
Pre-purge
5 seconds (NG models)
15 seconds (LP models)
HSI Warmup
10 seconds
Ignition Activation
Period (IAP)
3.5 seconds maximum
Flame Recognition
Period (FRP)
0.5 second
Trial For Ignition
IAP + FRP
Flame Stabilization
Period
Not Applicable
Inter-purge
30 seconds
Flame Failure
Response Time
2 seconds max
(@ 1uA
fl
ame current)
Post-purge
30 seconds
PS Prove Period
2 minutes
PS Fault Delay
(failed open/closed)
2 minutes
Soft Lockout
20 minutes
TCO Limit Lockout
Inde
fi
nite (follow de
fi
ned
procedure to restart)
Flammable Vapor
Sensor Lockout
Inde
fi
nite (follow de
fi
ned
procedure to restart)
Hardware Fault
Lockout
Inde
fi
nite (clear fault to restart
in 15 seconds or less)