background image

11

5.

Attach a properly sized length of Selkirk Metalbestos model
PS or model G venting to the exhaust vent adapter using the
inner vee bands, see Figures 7 and 7B on page 10.

6.

Fill the grooves in both inner vee bands with high-temp
silicone sealant, Dow Corning 736 or equivalent.

7.

Position the inner vee bands around the inner pipe flanges
and tighten the screws securing the bands.

8.

Align the outer channel band with the outer pipe grooves
and tighten the screws securing the bands.

9.

Repeat steps 6-8 for each successive pipe length until the
venting reaches the heater.

10. Follow the manufacturer’s instructions for proper support

and guide spacing for horizontal runs of pipe, see Table 6.

TABLE 6.

Vent Diameter

S

F

8” - BTPV -540A, 650A & 740A

15’  3”

7’  6”

S = Maximum spacing between two guides or a support

and a guide in either a vertical or horizontal direction.

F = Maximum height above a guide or support for free

standing system above a roof or parapet wall.

11. Use an expansion joint between any two fixed points in the

exhaust venting system wherever the expansion may exceed
1/4”.  Selkirk Metalbestos model PS and model G venting
will expand by one inch per 100°F in gas temperature per
100 feet of vent length.  The expansion can be calculated by
the following formula:

Expansion,

Vent length between

  5  

Inches

two fixed points, feet           100

If the expansion calculated is greater than 1/4”, an expansion
joint must be used between the two fixed points.

12. Attach the flue reducer included in the exhaust vent hood

package to the flue collar on the heater.

13. Attach the flue reducer to the vent system using a seal ring.

Attach this ring to the venting using the inner vee bands as
outlined in Steps 5-7.

14. Attach 8” air-intake connector to intake vent hood collar.  It

may be necessary to use a slip-slip coupling to fit the pipe
to the intake vent hood.

15. Attach 8” air-intake connector back to the 6” burner air inlet

with 8” x 6” reducer.  Prime and cement each joint to assure
gas-tight construction.

16. Seal all joints at the vent hoods with silicone sealant.  Also

seal the joints at the flue collar and air inlet adapter.  Joint on
the exhaust side must be sealed with high-temp silicone
sealant, Dow Corning 736 or equivalent.

  WARNING

PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE, AND
MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME.
ALLOW ADEQUATE CURING TIME BEFORE OPERATING HEATER.

DRAIN VALVE AND ACCESS PANELS

The heaters are equipped with a 3/4” NPT drain valves mounted
above and to the left of the burner.

An access panel is located above and to the right of the burner,
see Figure 8.  This panel covers the cleanout opening in the tank
which is sealed by a gasket and cover.  Another cleanout access
panel is located towards the back of the heater.

             

FIGURE 8.

GAS PIPING

Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation
codes for your area.

Size the main gas line in accordance with Table 9 and 9A.
Minimum required gas supply pipe size is 1 1/4”. The figures
shown are for straight lengths of pipe at 0.5 in. w.c. pressure
drop, which is considered normal for low pressure systems.
Note that fittings such as elbows and tees will add to the pipe
pressure drop.

TABLE 9

MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR

(Based upon a Pressure Drop of 0.5 inch Water Column

and 0.5 Specific Gravity Gas and max. gas press. of .5 psig)

LENGTH

IN

Nominal Iron Pipe Sizes, Inches

FEET

1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

10

175

360

680

1400

2100

3960

6300

11000

23000

20

120

250

485

950

1460

2750

4360

7700

15800

30

97

200

375

770

1180

2200

3520

6250

12800

40

82

170

320

660

990

1900

3000

5300

10900

50

73

151

285

580

900

1680

2650

4750

9700

60

66

138

260

530

810

1520

2400

4300

8800

70

61

125

240

490

750

1400

2250

3900

8100

80

57

118

220

460

690

1300

2050

3700

7500

90

53

110

205

430

650

1220

1950

3450

7200

100

50

103

195

400

620

1150

1850

3250

6700

125

44

93

175

360

550

1020

1650

2950

6000

150

40

84

160

325

500

950

1500

2650

5500

175

37

77

145

300

460

850

1370

2450

5000

200

35

72

135

280

430

800

1280

2280

4600

         =

               x

Содержание Conservationist BTPV 650A

Страница 1: ...000 CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS IN FORMATION RELATIVE TO YOUR SAFETY PLEASE READTHOROUGHLYBEFOREINSTALLINGANDUSING THISAPPLIANCE A DIVISION OF A O SMITH CORPORATION MCBEE SOUTHCA...

Страница 2: ...MODELS HORIZONTAL DIRECTVENTING BTPV MODELS ALLDIMENSIONSININCHES MILLIMETERS Gas Approx Models A B C D E F G H I Conn Ship Wt 80 3 4 73 32 1 4 9 6 26 1 2 93 29 1 2 48 1 2 1 950 2 051 1 854 819 229 1...

Страница 3: ...uired Ability 5 Uncrating 5 Locating the Heater 5 6 Hard Water 6 Clearances 6 Air Requirements 6 Venting 6 7 Vertical Venting For BTP Models 7 Horizontal Side wall Venting For BTPV Models 7 8 Direct V...

Страница 4: ...ANKWATERHEATER YOURA O SMITHWATERHEATERMEETS OR EXCEEDS THE ASHRAE IES 90 1B 2001 STANDARDS WITH RESPECT TO INSULATION AND STANDBY LOSS REQUIREMENTS MAKING AN INSULATION BLANKET UNNECESSARY THE USE OF...

Страница 5: ...1 flue reducer The intake vent hood carton contains one 1 intake vent hood and one 1 inlet adapter All parts should be installed as received without alteration LOCATING THE HEATER When installing the...

Страница 6: ...E SUCHACONDITIONOFTENWILLRESULT IN A YELLOW LUMINOUS BURNER FLAME CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER BURNERS AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION Where an exhaust fan...

Страница 7: ...system Refer to Table 1 for the vent pipe size required for installation to the barometric draft control assembly outlet TABLE1 Model Flue Outlet BTP 540A 9 228 6 mm BTP 650A 9 228 6 mm BTP 740A 9 22...

Страница 8: ...portions of the vent system must be installed with a minimum upward slope of 1 4 per foot of length All joints and seams in the venting system must be sealed gas tight If a silicone sealer is used it...

Страница 9: ...g must be adequately supported to avoid unnecessary stress on vent hood venting or burner See Table 5 limitations on venting system design for direct vent installations TABLE5 Dimension in BTPV Inches...

Страница 10: ...3 feet 9144 m vertically from gas line meter or other gas supply entering a structure see Figure 6 FIGURE 7 DIRECTVENTSYSTEMINSTALLATION Plan the vent system backwards from the vent hood to the heate...

Страница 11: ...Prime and cement each joint to assure gas tight construction 16 Seal all joints at the vent hoods with silicone sealant Also seal the joints at the flue collar and air inlet adapter Joint on the exhau...

Страница 12: ...10 THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE To prevent da...

Страница 13: ...rs should be obtained and field installed as shown in the installation diagrams Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply RELIEF VALVE...

Страница 14: ...TO COLD WATER INLET LINE ONE TEMPERATURE ONE HEATER HORIZONTAL STORAGE TANK FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT...

Страница 15: ...UTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED WIRING DIAGR...

Страница 16: ...E RELIEF VALVE TO OPEN DRAIN 140 F TO 150 F SHOULD BE MAXIMUM WATERTEMPERATUREMAINTAINEDINTHE PRE HEATERS 120 F SHOULD BE THE MINIMUM TEMPERATURE OF WATER IN THE PRE HEATERS CONNECT CIRCULATING LINE F...

Страница 17: ...R OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES NOTE 1 TOGGLE SWITCH CONTROLS 180 WATER CIRCULATION INSTALL ON OR CLOSE TO...

Страница 18: ...pied by the water heaters assemblies Space for the barometric draft control assemblies combustion clearances and servicing must be added WARNING FAILURE TO PROPERLY MANIFOLD MULTIPLE WATER HEATERS AND...

Страница 19: ...HEATERANDPIPING NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER FILLING...

Страница 20: ...20 FIGURE 11...

Страница 21: ...21 FIGURE 12...

Страница 22: ...to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped an ignition device which automatically lights the burner Do NOT try to light the burner by hand 5 Refer t...

Страница 23: ...R TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHERANDLAUNDRYUSECANCAUSESCALDBURNS RESULTING IN SERIOUS PERSONAL INJURY AND OR DEATH THETEMPERATUREATWHICHINJURYOCCURSVARIESWITH THE PERSON S AGE AND TIME...

Страница 24: ...2 reading Increase air damper setting will decrease fire rate and decrease flue gas CO2 reading Adjustable air damper is preset for the rated fire rate prior to delivery should not be re adjusted unle...

Страница 25: ...25 PREMIX LOW NOx BURNER EXPLODED VIEW FOR BTP MODELS FIGURE 13...

Страница 26: ...26 PREMIX LOW NOx BURNER EXPLODED VIEW FOR BTPV MODELS FIGURE 14...

Страница 27: ...LINEANDOTHERFLAMMABLEVAPORSAND LIQUIDS SEE WARNING PAGE 6 Water heater maintenance includes periodic tank flushing and cleaning and removal of lime scale The power burner should be inspected and adjus...

Страница 28: ...orn mineral deposits A O Smith UN LIME Professional delimer should be used A O Smith UN LIME Delimer is an easy to handle patented food grade acid formulated specifically for lime scale removal from a...

Страница 29: ...which are an integral part of the combustion chamber as damage could occur The flue passages are 48 1 2 1 232 mm long x 3 76 2 mm diameter 8 Upon completion of cleaning return heater to operation by f...

Страница 30: ...flow preventer or pressure reducing valve is in the inlet system it will not permit the expanded hot water volume to equalize pressure with the main The relief valve must release this water or the wa...

Страница 31: ...witch by ohm meter while pilot gas pressure is 7 w c 1 7 kPa or higher Check for the continuity between the flame rod and sensor connection at Honeywell flame control module by the ohm meter Check for...

Страница 32: ...iled procedure of replacing flame rod MOTORRUNSCONTINUOUSLY BURNERLIGHTSON MOMENTARILYTHENLOCKSOUTOREXCESSIVE ON OFFCYCLE Under this condition the burner will start the purge cycle again then pilot ig...

Страница 33: ...less an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE...

Страница 34: ...34 NOTES...

Страница 35: ...35 NOTES...

Страница 36: ...36 REPLACEMENT PARTS 5621 W 115TH STREET ALSIP IL 60803 Phone 800 433 2545 Fax 800 433 2515 www aosmithwaterheaters com E Mail parts hotwater com...

Отзывы: