background image

6

Units, which are to be installed on combustible flooring, must
be supported by a full layer of hollow concrete blocks, from
8” (203.2 mm) to 12” (304.8 mm) thick and extending
12”  (304.8 mm) minimum beyond the heater in all directions.
The concrete blocks must provide an unbroken concrete surface
under the heater with the hollows running continuously and
horizontally.  A 3/16-inch steel plate must cover the concrete
blocks, see Figure 2.

NOTE:  If electrical conduits run under the floor of the proposed
heater location, insulate the floor as recommended above.

For appliances installation locations with elevations above 2000
feet (609.6 m), refer to HIGH ALTITUDE INSTALLATIONS section.

    

PROPER INSTALLATION ON COMBUSTIBLE FLOORING

FIGURE 2.

HARD WATER

Where hard water conditions exist, water softening or the
threshold type of water treatment is recommended.  This will
protect the dishwasher, Coffee urns, water heaters, water piping
and other equipment.

See MAINTENANCE section for details of tank cleanout
procedure.

CLEARANCES

These heaters are designed for installation on non-combustible
flooring in an alcove with clearances to combustible construction
of 6” (152.4 mm) from the sides and rear, 24” (610 mm) from the
top with a 6” (152.4 mm) minimum between vent pipe and ceiling.
Minimum clearance from flue pipe to combustible material is 6”
(152.4 mm), see Figure 3.

                         

PROPER INSTALLATION CLEARANCES

FIGURE 3.

A clearance of 30” (762 mm) shall be maintained from
serviceable parts, such as power burners, relief valves flue
baffles, thermostats or drain valves.

AIR REQUIREMENTS

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE
MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND
LIQUIDS.

DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR
VENTILATING AIR.

 

 

WARNING

FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR
COMBUSTION AND VENTILATION.  AN INSUFFICIENT SUPPLY
OF AIR WILL CAUSE RECIRCULATION OF COMBUSTION
PRODUCTS RESULTING IN AIR CONTAMINATION THAT MAY BE
HAZARDOUS TO LIFE.  SUCH A CONDITION OFTEN WILL RESULT
IN A YELLOW, LUMINOUS BURNER FLAME, CAUSING
CARBONING OR SOOTING OF THE COMBUSTION CHAMBER,
BURNERS AND FLUE TUBES AND CREATES A RISK OF
ASPHYXIATION.

Where an exhaust fan is installed in the same room with a heater,
sufficient openings for air must be provided in the walls.

UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO
THE ROOM THROUGH THE CHIMNEY, CAUSING POOR
COMBUSTION.  SOOTING MAY RESULT IN SERIOUS DAMAGE
TO THE HEATER AND RISK OF FIRE OR EXPLOSION.

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction,
unconfined spaces may provide adequate air for combustion
and ventilation.

If the unconfined space is within a building of tight construction,
(building using the following construction: weather stripping,
heavy insulation, caulking, vapor barrier, etc.), air for combustion
and ventilation must be obtained from outdoors or spaces freely
communicating with the outdoors.  The installation instructions
for confined spaces in tightly constructed buildings must be
followed to ensure adequate air supply.

CONFINED SPACE

When drawing combustion and dilution air from inside a
conventionally constructed building to a confined space, such a
space shall be provided with two permanent openings, ONE IN
OR WITHIN 12 INCHES (304.8 mm) OF THE ENCLOSURE TOP
AND ONE IN OR WITHIN 12 INCHES (304.8 mm) OF THE
ENCLOSURE BOTTOM.  Each opening shall have a free area of
at least one square inch per 1000 Btuh of the total input of all
appliances in the enclosure, but not less than 100 square inches.

If the confined space is within a building of tight construction, air
for combustion and ventilation must be obtained from outdoors.
When directly communication with the outdoors through vertical
ducts, two permanent openings, located in the above manner,
shall be provided.  Each opening shall have a free area of not
less than one square inch per 4000 Btuh of the total input of all
appliances in the enclosure.

VENTING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE
FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES.  SUCH CONDITIONS CAUSE
SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Содержание Conservationist BTPV 650A

Страница 1: ...000 CAUTION TEXT PRINTED OR OUTLINED IN RED CONTAINS IN FORMATION RELATIVE TO YOUR SAFETY PLEASE READTHOROUGHLYBEFOREINSTALLINGANDUSING THISAPPLIANCE A DIVISION OF A O SMITH CORPORATION MCBEE SOUTHCA...

Страница 2: ...MODELS HORIZONTAL DIRECTVENTING BTPV MODELS ALLDIMENSIONSININCHES MILLIMETERS Gas Approx Models A B C D E F G H I Conn Ship Wt 80 3 4 73 32 1 4 9 6 26 1 2 93 29 1 2 48 1 2 1 950 2 051 1 854 819 229 1...

Страница 3: ...uired Ability 5 Uncrating 5 Locating the Heater 5 6 Hard Water 6 Clearances 6 Air Requirements 6 Venting 6 7 Vertical Venting For BTP Models 7 Horizontal Side wall Venting For BTPV Models 7 8 Direct V...

Страница 4: ...ANKWATERHEATER YOURA O SMITHWATERHEATERMEETS OR EXCEEDS THE ASHRAE IES 90 1B 2001 STANDARDS WITH RESPECT TO INSULATION AND STANDBY LOSS REQUIREMENTS MAKING AN INSULATION BLANKET UNNECESSARY THE USE OF...

Страница 5: ...1 flue reducer The intake vent hood carton contains one 1 intake vent hood and one 1 inlet adapter All parts should be installed as received without alteration LOCATING THE HEATER When installing the...

Страница 6: ...E SUCHACONDITIONOFTENWILLRESULT IN A YELLOW LUMINOUS BURNER FLAME CAUSING CARBONING OR SOOTING OF THE COMBUSTION CHAMBER BURNERS AND FLUE TUBES AND CREATES A RISK OF ASPHYXIATION Where an exhaust fan...

Страница 7: ...system Refer to Table 1 for the vent pipe size required for installation to the barometric draft control assembly outlet TABLE1 Model Flue Outlet BTP 540A 9 228 6 mm BTP 650A 9 228 6 mm BTP 740A 9 22...

Страница 8: ...portions of the vent system must be installed with a minimum upward slope of 1 4 per foot of length All joints and seams in the venting system must be sealed gas tight If a silicone sealer is used it...

Страница 9: ...g must be adequately supported to avoid unnecessary stress on vent hood venting or burner See Table 5 limitations on venting system design for direct vent installations TABLE5 Dimension in BTPV Inches...

Страница 10: ...3 feet 9144 m vertically from gas line meter or other gas supply entering a structure see Figure 6 FIGURE 7 DIRECTVENTSYSTEMINSTALLATION Plan the vent system backwards from the vent hood to the heate...

Страница 11: ...Prime and cement each joint to assure gas tight construction 16 Seal all joints at the vent hoods with silicone sealant Also seal the joints at the flue collar and air inlet adapter Joint on the exhau...

Страница 12: ...10 THE DIRT LEG MUST BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE To prevent da...

Страница 13: ...rs should be obtained and field installed as shown in the installation diagrams Thermometers are installed in the system as a means of detecting the temperature of the outlet water supply RELIEF VALVE...

Страница 14: ...TO COLD WATER INLET LINE ONE TEMPERATURE ONE HEATER HORIZONTAL STORAGE TANK FORCED CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT...

Страница 15: ...UTION IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW PREVENTER CHECK VALVE OR WATER METER WITH CHECK VALVE PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED WIRING DIAGR...

Страница 16: ...E RELIEF VALVE TO OPEN DRAIN 140 F TO 150 F SHOULD BE MAXIMUM WATERTEMPERATUREMAINTAINEDINTHE PRE HEATERS 120 F SHOULD BE THE MINIMUM TEMPERATURE OF WATER IN THE PRE HEATERS CONNECT CIRCULATING LINE F...

Страница 17: ...R OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES NOTE 1 TOGGLE SWITCH CONTROLS 180 WATER CIRCULATION INSTALL ON OR CLOSE TO...

Страница 18: ...pied by the water heaters assemblies Space for the barometric draft control assemblies combustion clearances and servicing must be added WARNING FAILURE TO PROPERLY MANIFOLD MULTIPLE WATER HEATERS AND...

Страница 19: ...HEATERANDPIPING NEVER OPERATE THE HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF VALVE OPENING OF THE HEATER FILLING...

Страница 20: ...20 FIGURE 11...

Страница 21: ...21 FIGURE 12...

Страница 22: ...to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped an ignition device which automatically lights the burner Do NOT try to light the burner by hand 5 Refer t...

Страница 23: ...R TEMPERATURES REQUIRED FOR AUTOMATIC DISHWASHERANDLAUNDRYUSECANCAUSESCALDBURNS RESULTING IN SERIOUS PERSONAL INJURY AND OR DEATH THETEMPERATUREATWHICHINJURYOCCURSVARIESWITH THE PERSON S AGE AND TIME...

Страница 24: ...2 reading Increase air damper setting will decrease fire rate and decrease flue gas CO2 reading Adjustable air damper is preset for the rated fire rate prior to delivery should not be re adjusted unle...

Страница 25: ...25 PREMIX LOW NOx BURNER EXPLODED VIEW FOR BTP MODELS FIGURE 13...

Страница 26: ...26 PREMIX LOW NOx BURNER EXPLODED VIEW FOR BTPV MODELS FIGURE 14...

Страница 27: ...LINEANDOTHERFLAMMABLEVAPORSAND LIQUIDS SEE WARNING PAGE 6 Water heater maintenance includes periodic tank flushing and cleaning and removal of lime scale The power burner should be inspected and adjus...

Страница 28: ...orn mineral deposits A O Smith UN LIME Professional delimer should be used A O Smith UN LIME Delimer is an easy to handle patented food grade acid formulated specifically for lime scale removal from a...

Страница 29: ...which are an integral part of the combustion chamber as damage could occur The flue passages are 48 1 2 1 232 mm long x 3 76 2 mm diameter 8 Upon completion of cleaning return heater to operation by f...

Страница 30: ...flow preventer or pressure reducing valve is in the inlet system it will not permit the expanded hot water volume to equalize pressure with the main The relief valve must release this water or the wa...

Страница 31: ...witch by ohm meter while pilot gas pressure is 7 w c 1 7 kPa or higher Check for the continuity between the flame rod and sensor connection at Honeywell flame control module by the ohm meter Check for...

Страница 32: ...iled procedure of replacing flame rod MOTORRUNSCONTINUOUSLY BURNERLIGHTSON MOMENTARILYTHENLOCKSOUTOREXCESSIVE ON OFFCYCLE Under this condition the burner will start the purge cycle again then pilot ig...

Страница 33: ...less an effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE...

Страница 34: ...34 NOTES...

Страница 35: ...35 NOTES...

Страница 36: ...36 REPLACEMENT PARTS 5621 W 115TH STREET ALSIP IL 60803 Phone 800 433 2545 Fax 800 433 2515 www aosmithwaterheaters com E Mail parts hotwater com...

Отзывы: