710 / 710 ASME Service Manual
Ver. 1.00
64
CONFIDENTIAL
12-12. High-Altitude Region Support Functions (FM+ and INPUT-)
<
Using this function
>
The high-altitude region support functions have three operation levels,
with the appropriate level being set up by the installer until the abnormal
sound problem is solved. The desired level can be specified at the right
bank of dipswitches (No.2 and No.3) on the computer board.
If the abnormal sound problem persists even with a “Level 3” setting, please contact our
Technical Service Department. for advice. Note that there are many high risks associated with
manually changing the manifold pressures.
Level
Function
Setting Method
0
Standard setting
(Default)
Right bank of dipswitches No.2 OFF
No.3 OFF
1
the fan motor speed increased
by 7.5% (FM+ function)
Right bank of dipswitches No.2 ON
No.3 OFF
2
Reduction of the max gas input
by 10% (INPUT- function)
Right bank of dipswitches No.2 OFF
No.3 ON
3
the fan motor speed increased
by 7.5% (FM+ function)
&
Lowers the max. input by 10%
(
INPUT- function
)
Right bank of dipswitches No.2 ON
No.3 ON
Right bank of dipswitches
CAUTION