DIMENSIONS AND CAPACITIES DATA

Table 1. Tank Capacities and Dimensions

Model Number

Tank Capacity in Gallons (Liters)

A - Inches (mm)

B - Inches (mm)

C - Inches (mm)

Inlet/Outlet

52

50 (189.3)

55 3/4 (1416)

21 3/4 (552)

27 (685)

1 1/4

80

80 (302.8)

60 1/4 (1350)

25 1/2 (648)

31 (787)

1 1/4

120

119 (450.5)

62 1/4 (1581)

29 1/2 (749)

35 (889)

1 1/4

 

Table 2. 

Recovery Rate in Gallons Per Hour Temperature Rise °F

Standard

KW Input

BTU/

Hour

30°

40°

50°

60°

70°

80°

90°

100°

110°

120°

130°

140°

6

20,478

82

62

49

41

35

31

27

25

22

21

19

18

9

30,717

123

92

74

62

53

46

41

37

34

31

28

26

12

40,956

164

123

98

82

70

61

55

49

45

41

38

35

13.5

46,075

184

138

111

92

79

69

62

55

50

46

43

40

15

51,195

205

154

123

102

88

77

68

61

56

51

47

44

18

61,434

246

184

148

123

105

92

82

74

67

61

57

53

24

81,912

328

246

197

164

140

123

109

98

89

82

76

70

27

92,151

369

276

221

184

158

138

123

111

101

92

85

79

30

102,390

410

307

246

205

176

154

137

123

112

102

95

88

36

122,868

492

369

295

246

211

184

164

148

134

123

113

105

40.5

138,226

554

418

3332

277

237

208

1185

166

151

138

128

119

45

153,585

615

461

369

307

263

230

205

184

168

154

142

132

54

184,302

738

553

443

369

316

277

246

221

201

184

170

158

*Figured at 1 KW (3413 Btu) = 4.1 gallons at 100°F temperature rise.

To determine recovery rate per minute, divide recovery rate per hour by 60.

This Instruction Manual covers two models of commercial 

electric water heaters:

These two models are equipped from the factory with different 

controls.
In this Instruction Manual, one model is factory equipped with 

a surface mounted thermostat/ECO combination control and is 

referred to as a 

surface-mount control

 model.

The other model is equipped with an electronic control system 

and is referred to as an 

electronic control model

.

Figure 1.  Dimensions and Components

3/4” NPT

OPENING

DISPLAY FOR

ELECTRONIC

CONTROL

MODELS ONLY

WATER

OUTLET

CONDUIT

OPENING

INLET

OPENING

DRAIN

VALVE

A

C

B

5.25

Printed on 2/8/2018 9:05 AM CT

Содержание 52

Страница 1: ...D NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE COMMERCIAL ELECTRIC WATER HEATERS OPTIONAL Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS 52 8...

Страница 2: ...death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoided could result in...

Страница 3: ...pe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN Water temperature over 125 F 52 C can cause severe burns instantly resulting in severe in...

Страница 4: ...ONVERSION TO SINGLE PHASE 20 CONVERSION TO THREE PHASE 20 OPERATION 21 GENERAL 21 FILLING THE WATER HEATER 21 INITIAL START UP 21 Draining the Water Heater 21 TEMPERATURE REGULATION 22 High Temperatur...

Страница 5: ...he electrical system of the heater Never touch electrical components with wet hands or when standing in water When replacing fuses always use the correct size for the circuit see page 13 The principal...

Страница 6: ...390 410 307 246 205 176 154 137 123 112 102 95 88 36 122 868 492 369 295 246 211 184 164 148 134 123 113 105 40 5 138 226 554 418 3332 277 237 208 1185 166 151 138 128 119 45 153 585 615 461 369 307 2...

Страница 7: ...E VOLTS AC ELEMENTS EACH RATED MEASURED WATTS COMMERCIAL STORAGE TANK WATER HEATER MODEL NUMBER SERIAL NUMBER ITEM ID PART NUMBER WATTS TOTAL CAPACITY US GAL STANDBY LOSS MAX WORKING PRESSURE Low Lead...

Страница 8: ...8 FEATURES AND COMPONENTS Figure 2 Electronic Control Modules Printed on 2 8 2018 9 05 AM CT...

Страница 9: ...9 FEATURES AND COMPONENTS Figure 3 Surface Mount Control Models Printed on 2 8 2018 9 05 AM CT...

Страница 10: ...ions will not result in damage to the area adjacent to the heater or to lower floors of the structure Close to the point of major hot water usage and the power supply Hot water piping and branch circu...

Страница 11: ...ature are available Consult a qualified installer or service agency Follow all manufacturer s Instructions for installation of these valves Before changing the factory setting on the thermostat read t...

Страница 12: ...ature pressure relief valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating th...

Страница 13: ...shall not exceed 15 amperes for 14 AWG 20 amperes for 12 AWG and 30 amperes for 10 AWG copper or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper clad aluminum For dry locations onl...

Страница 14: ...es control circuit fusing using two 3 amp class G fuses with 600 volt rating Do not substitute fuses of a different rating SEQUENCE OF OPERATION 1 When the control is powered the UIM should display mo...

Страница 15: ...his table is to be used for 8 tap and 5 tap transformers Figure 4 Secondary Transformer Coil Table 5 Secondary Transformer Coil Configuration Volts Line On Load On 208 COMMON 208 SECONDARY 120V 240 CO...

Страница 16: ...16 Figure 5 CCB Control Circuit Diagram Electronic Control Models WIRING DIAGRAMS Printed on 2 8 2018 9 05 AM CT...

Страница 17: ...ing diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C Fusing consists of three 30 amp fuses...

Страница 18: ...llow wires to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service it may be...

Страница 19: ...ring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C Fusing consists of two 30 amp fuses f...

Страница 20: ...res to terminal L2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service it may be conn...

Страница 21: ...urn on the electrical disconnect switch 5 Observe the operation of the electrical components during the first heating cycle Use care as the electrical circuits are energized 6 Close the front panel Te...

Страница 22: ...ECO activate the water temperature must drop below 140 F 60 C before the control system can be reset Once the water temperature has cooled below this point the power supply to the water heater must be...

Страница 23: ...nt is adjusted to control water temperature This is an adjustable user setting in the control system s Temperatures Menu This and all control system menus are accessed through the UIM User Interface M...

Страница 24: ...rmation Screen below shows the control system Desktop Screen This is the default screen If there are no active Fault or Alert conditions and no user input for approximately 10 minutes the control syst...

Страница 25: ...sent heating elements the control system has not energized and is not sensing electrical current from Heating elements icon for a water heater equipped with 3 Banks of heating elements Each circle rep...

Страница 26: ...rmit tent operational problems or when the customer has reset the control system prior to a service agent s arrival Fault Occurrence Running total of all Fault and Alert Conditions that have occurred...

Страница 27: ...additional Bank of 3 heating elements OPERATING SEQUENCE With an Operating Set Point of 120 F and all Differential settings at 2 F the On Off sequencing of heating element Banks would be as follows B...

Страница 28: ...current state of the ECO high temperature limit switch contacts The ECO switch is located inside the immersion Temperature Probe two red wires Enable Disable 1 2 Displays the current state open or clo...

Страница 29: ...er In Economy Mode Displays whether the control system is currently operating in Economy Mode or not Daily Operating Mode Sun Mon Tue Wed Thu Fri Sat Seven daily sub menus are listed at the bottom of...

Страница 30: ...nal Button underneath CHANGE to activate the adjustment mode for the Setpoint Adjustment value Use the Up Down buttons to change the Setpoint Adjustment to the desired value The SetpointAdjustment val...

Страница 31: ...ANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm the new setting...

Страница 32: ...NGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to change the operating m...

Страница 33: ...current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault cond...

Страница 34: ...story Menu This menu displays non adjustable operational information The control system records and stores the last 9 Fault and Alert messages in chronological order in this menu The most recent will...

Страница 35: ...ment The heater tank is equipped with an anode rod to aid in corrosion control and should be inspected periodically see Anode Rod Inspection ANODE ROD INSPECTION Each water heater contains at least on...

Страница 36: ...in operation Allow the water heater to complete several heating cycles to ensure it is operating properly SEDIMENT REMOVAL Water borne impurities consist of fine particles of soil and sand which settl...

Страница 37: ...en the time required to heat water to the desired temperature 6 Look for hot water leakage 7 Sediment or pipe scale may be affecting water heater operation ABNORMAL SOUNDS 1 Sediment or lime scale acc...

Страница 38: ...ening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Water on the side of the tank may be condensation due to the panel or insulation not being in pl...

Страница 39: ...n the system 3 Service valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCUL...

Страница 40: ...be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCI...

Страница 41: ...ld be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMME...

Страница 42: ...rvice valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK...

Страница 43: ...the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS WITH...

Страница 44: ...ol the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS W...

Страница 45: ...for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 3 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRA...

Страница 46: ...ter heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH VERTICAL STORAGE TANK...

Страница 47: ...water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH HORIZONTAL STORAGE T...

Страница 48: ...er local codes shall govern their usage COMMERCIAL ELECTRIC 4 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE...

Страница 49: ...rage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESS...

Страница 50: ...storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE...

Страница 51: ...fold Kits with Three Heaters Tank Capacity Gallons Part Number H W D A 52 100109232 66 1 4 91 3 4 27 1 4 13 1 4 80 100109232 70 1 2 95 1 4 31 1 4 9 3 4 120 100109232 73 1 4 99 1 2 35 3 4 5 1 2 Inlet a...

Страница 52: ...52 Copyright 2017 All rights reserved www hotwater com Printed on 2 8 2018 9 05 AM CT...

Отзывы: