CONTROL SYSTEM FEATURES

Advanced Diagnostics: Plain English text and animated icons 

display detailed operational and diagnostic information. LCD 

screen on the front of the water heater displays the Sequence 

of Operation in real time. Fault or Alert messages are displayed 

when  operational  problems  occur. Advanced  Service  menu 

displays a list of possible causes for current Fault and Alert 

conditions to aid in servicing.
Economy Mode Operation: Control system automatically 

lowers the Operating Set Point by a programmed value during 

user defined time periods. Helps reduce operating costs during 

unoccupied or peak demand periods.

Linear Sequencing: Banks of heating elements (3 elements 

per  bank)  are  energized  according  to  adjustable  (1  to  20°) 

differential set points for each bank. First bank on is the last 

bank off. Helps reduce operating costs during low/moderate 

loads.

CONTROL SYSTEM NAVIGATION

The UIM (User Interface Module) is located on the front cabinet 

of the Electronic Control Model water heaters. All operational 

information and user settings are displayed and accessed 

using the UIM. The UIM includes five snap acting (momentary) 

user input buttons; an Up, Down and 3 Operational Buttons.

Figure 13.  User Interface Module (UIM)

UP & DOWN BUTTONS

Used to navigate (up and down) and to select (highlight) menu 

items. Also used to adjust or change (increase/decrease, on/

off, set time) various user settings.

OPERATIONAL BUTTONS

The 3 Operational Buttons are multifunctional. Their current 

function is defined by the text that appears above each button 

on the LCD screen. The function will change depending on what 

menu is currently displayed or what menu item is selected. 

When no text appears on the LCD screen above an Operational 

Button there is no function assigned.

THE DESKTOP SCREEN

Figure 14.  Model Information Screen

 below shows the control 

system “Desktop Screen.” This is the default screen. If there 

are no active Fault or Alert conditions and no user input for 

approximately 10 minutes the control system will return to this 

screen automatically.

MODEL INFORMATION

Model information and menu titles are shown in the black bar 

at the top of the Desktop Screen.

TANK TEMPERATURE

Current water temperature as sensed from the immersion 

Temperature Probe.

Operating Set Point:

 Temperature at which the control system 

will maintain tank (water) temperature in the Normal Mode. This 

line of text will read Economy Set Point whenever the control 

system is operating in the Economy Mode.

Status:

 The Operating State of the control system is displayed 

beneath the Operating Set Point.

Figure 14.  Model Information Screen

Menu: 

The left Operational Button is pressed to enter the Main 

Menu where all control system menus are accessed. See 

Table 

10 for a list of control system menus.

Help: 

The  right  Operational  Button  is  pressed  to  access 

instructions and explanations for user settings, Operating 

States, Status Icons, manufacturer’s web address, technical 

support phone number and service agent contact information.

Day/Time/Operating  Mode:

 The current time and day are 

also displayed on the Desktop Screen. “Clock Not Set” will be 

displayed until the time clock has been initially set. Day and 

Time are adjusted in the Economy Mode Setup menu. The 

current Operating Mode, either Normal Mode or Economy 

Mode, is displayed beneath the day and time.

Discreet  Menu  Contact  Information:

 From the Desktop 

Screen  press  and  hold  down  the  middle  (unmarked) 

Operational Button for 30 seconds and then release it. This will 

launch a discreet menu where personalized contact information 

can be entered. Installing contractors and/or service agents can 

enter their company name and telephone number. This contact 

information will be displayed with all Fault and Alert messages.

ELECTRONIC CONTROL MODELS OPERATION

Printed on 2/8/2018 9:05 AM CT

Содержание 52

Страница 1: ...D NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE COMMERCIAL ELECTRIC WATER HEATERS OPTIONAL Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS 52 8...

Страница 2: ...death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoided could result in...

Страница 3: ...pe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN Water temperature over 125 F 52 C can cause severe burns instantly resulting in severe in...

Страница 4: ...ONVERSION TO SINGLE PHASE 20 CONVERSION TO THREE PHASE 20 OPERATION 21 GENERAL 21 FILLING THE WATER HEATER 21 INITIAL START UP 21 Draining the Water Heater 21 TEMPERATURE REGULATION 22 High Temperatur...

Страница 5: ...he electrical system of the heater Never touch electrical components with wet hands or when standing in water When replacing fuses always use the correct size for the circuit see page 13 The principal...

Страница 6: ...390 410 307 246 205 176 154 137 123 112 102 95 88 36 122 868 492 369 295 246 211 184 164 148 134 123 113 105 40 5 138 226 554 418 3332 277 237 208 1185 166 151 138 128 119 45 153 585 615 461 369 307 2...

Страница 7: ...E VOLTS AC ELEMENTS EACH RATED MEASURED WATTS COMMERCIAL STORAGE TANK WATER HEATER MODEL NUMBER SERIAL NUMBER ITEM ID PART NUMBER WATTS TOTAL CAPACITY US GAL STANDBY LOSS MAX WORKING PRESSURE Low Lead...

Страница 8: ...8 FEATURES AND COMPONENTS Figure 2 Electronic Control Modules Printed on 2 8 2018 9 05 AM CT...

Страница 9: ...9 FEATURES AND COMPONENTS Figure 3 Surface Mount Control Models Printed on 2 8 2018 9 05 AM CT...

Страница 10: ...ions will not result in damage to the area adjacent to the heater or to lower floors of the structure Close to the point of major hot water usage and the power supply Hot water piping and branch circu...

Страница 11: ...ature are available Consult a qualified installer or service agency Follow all manufacturer s Instructions for installation of these valves Before changing the factory setting on the thermostat read t...

Страница 12: ...ature pressure relief valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating th...

Страница 13: ...shall not exceed 15 amperes for 14 AWG 20 amperes for 12 AWG and 30 amperes for 10 AWG copper or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper clad aluminum For dry locations onl...

Страница 14: ...es control circuit fusing using two 3 amp class G fuses with 600 volt rating Do not substitute fuses of a different rating SEQUENCE OF OPERATION 1 When the control is powered the UIM should display mo...

Страница 15: ...his table is to be used for 8 tap and 5 tap transformers Figure 4 Secondary Transformer Coil Table 5 Secondary Transformer Coil Configuration Volts Line On Load On 208 COMMON 208 SECONDARY 120V 240 CO...

Страница 16: ...16 Figure 5 CCB Control Circuit Diagram Electronic Control Models WIRING DIAGRAMS Printed on 2 8 2018 9 05 AM CT...

Страница 17: ...ing diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C Fusing consists of three 30 amp fuses...

Страница 18: ...llow wires to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service it may be...

Страница 19: ...ring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C Fusing consists of two 30 amp fuses f...

Страница 20: ...res to terminal L2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service it may be conn...

Страница 21: ...urn on the electrical disconnect switch 5 Observe the operation of the electrical components during the first heating cycle Use care as the electrical circuits are energized 6 Close the front panel Te...

Страница 22: ...ECO activate the water temperature must drop below 140 F 60 C before the control system can be reset Once the water temperature has cooled below this point the power supply to the water heater must be...

Страница 23: ...nt is adjusted to control water temperature This is an adjustable user setting in the control system s Temperatures Menu This and all control system menus are accessed through the UIM User Interface M...

Страница 24: ...rmation Screen below shows the control system Desktop Screen This is the default screen If there are no active Fault or Alert conditions and no user input for approximately 10 minutes the control syst...

Страница 25: ...sent heating elements the control system has not energized and is not sensing electrical current from Heating elements icon for a water heater equipped with 3 Banks of heating elements Each circle rep...

Страница 26: ...rmit tent operational problems or when the customer has reset the control system prior to a service agent s arrival Fault Occurrence Running total of all Fault and Alert Conditions that have occurred...

Страница 27: ...additional Bank of 3 heating elements OPERATING SEQUENCE With an Operating Set Point of 120 F and all Differential settings at 2 F the On Off sequencing of heating element Banks would be as follows B...

Страница 28: ...current state of the ECO high temperature limit switch contacts The ECO switch is located inside the immersion Temperature Probe two red wires Enable Disable 1 2 Displays the current state open or clo...

Страница 29: ...er In Economy Mode Displays whether the control system is currently operating in Economy Mode or not Daily Operating Mode Sun Mon Tue Wed Thu Fri Sat Seven daily sub menus are listed at the bottom of...

Страница 30: ...nal Button underneath CHANGE to activate the adjustment mode for the Setpoint Adjustment value Use the Up Down buttons to change the Setpoint Adjustment to the desired value The SetpointAdjustment val...

Страница 31: ...ANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm the new setting...

Страница 32: ...NGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to change the operating m...

Страница 33: ...current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault cond...

Страница 34: ...story Menu This menu displays non adjustable operational information The control system records and stores the last 9 Fault and Alert messages in chronological order in this menu The most recent will...

Страница 35: ...ment The heater tank is equipped with an anode rod to aid in corrosion control and should be inspected periodically see Anode Rod Inspection ANODE ROD INSPECTION Each water heater contains at least on...

Страница 36: ...in operation Allow the water heater to complete several heating cycles to ensure it is operating properly SEDIMENT REMOVAL Water borne impurities consist of fine particles of soil and sand which settl...

Страница 37: ...en the time required to heat water to the desired temperature 6 Look for hot water leakage 7 Sediment or pipe scale may be affecting water heater operation ABNORMAL SOUNDS 1 Sediment or lime scale acc...

Страница 38: ...ening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Water on the side of the tank may be condensation due to the panel or insulation not being in pl...

Страница 39: ...n the system 3 Service valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCUL...

Страница 40: ...be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCI...

Страница 41: ...ld be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMME...

Страница 42: ...rvice valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK...

Страница 43: ...the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS WITH...

Страница 44: ...ol the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS W...

Страница 45: ...for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 3 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRA...

Страница 46: ...ter heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH VERTICAL STORAGE TANK...

Страница 47: ...water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH HORIZONTAL STORAGE T...

Страница 48: ...er local codes shall govern their usage COMMERCIAL ELECTRIC 4 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE...

Страница 49: ...rage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESS...

Страница 50: ...storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE...

Страница 51: ...fold Kits with Three Heaters Tank Capacity Gallons Part Number H W D A 52 100109232 66 1 4 91 3 4 27 1 4 13 1 4 80 100109232 70 1 2 95 1 4 31 1 4 9 3 4 120 100109232 73 1 4 99 1 2 35 3 4 5 1 2 Inlet a...

Страница 52: ...52 Copyright 2017 All rights reserved www hotwater com Printed on 2 8 2018 9 05 AM CT...

Отзывы: