HEATER STATUS MENU

This menu displays non adjustable operational information. 

This menu contains more information that can be displayed on 

one screen of the LCD display. Use the Up & Down Buttons to 

navigate to the bottom of this menu.

Figure 16. Top of Menu

Figure 17. Bottom of Menu

Status 

Displays the current Operating State of the control system. IE: 

Heating, Standby, Fault see 

Table 9.

Element Banks On

Displays  the  current  number  of  heating  element  Banks  the 

control system has energized. Each Bank of elements contains 

3 heating elements.

Figure 18. Economy Mode Setup Menu

Setpoint Adjustment

Adjustable user setting (2°F to 50°F - factory default is 20°F) 

the control system uses to calculate the “Economy Set Point.” 

The Economy Set Point = normal Operating Set Point minus 

the programmed Setpoint Adjustment value. The Economy Set 

Point is the water temperature the control system maintains 

during programmed Economy Mode time periods. “Economy 

Set Point” is displayed instead of “Operating Set Point” and 

“Economy Mode” appears beneath the current time on the 

Desktop Screen during Economy Mode time periods.

Current Time

Seven Day 24 hr clock. Use this menu item to set the current 

time and day of the week. Current day and time are not set from 

the factory. “Clock Not Set” will be displayed on the Desktop 

until the time/day has been initially set.

Heater In Economy Mode

Displays whether the control system is currently operating in 

Economy Mode or not.

Daily Operating Mode (Sun - Mon - Tue - Wed - Thu - Fri - 

Sat)

Seven daily sub menus are listed at the bottom of the Economy 

Mode Setup menu. There are 3 Operating Modes in each sub 

menu; 

ECO Contact

Displays the current state of the ECO high temperature 

limit switch contacts. The ECO switch is located inside the 

immersion Temperature Probe (two red wires).

Enable / Disable 1 & 2

Displays the current state, open or closed, of the two Enable/

Disable  circuits  (J7  socket  on  the    CCB  (Central  Control 

Board)  - see wiring diagrams) provided for external supervisory 

controls such as building EMS (Energy Management System). 

Both  of  these  Enable/Disable  circuits  must  be  closed  to 

“enable” heating operation. If either Enable/Disable circuit is 

open for any reason heating operation will be “disabled.” There 

is a plug with two jumper wires installed from the factory in 

the CCB J7 socket to enable heating operation when external 

controls are not in use.

Service  Note:  If  a  supervisory  control(s)  is  used  to  enable/

disable heating operation, install field wiring between the J7 

socket on the CCB and a set of “dry contacts” on the external 

control per all applicable building codes. This is a switching 

circuit only: DO NOT apply any external voltage or connect 

any load (IE: relay coil) to either circuit. 

Element Bank On

Displays the on/off status of each Bank of heating elements. 

Yes = On, No = Off.

Alarm Condition

Displays the status of the user definable Alarm Output function 

- see Alarm Output Setup Menu. Yes = alarm condition has 

been met, No = alarm condition has not been met. 

Alarm Relay Output

Displays the state of the normally open contacts of the Alarm 

Output relay. This relay (J3 contacts on the CCB) is used for 

building  EMS  (Energy  Management  System)  notification  of 

operational conditions such as Fault conditions.

ECONOMY MODE SETUP MENU

This menu contains settings used to establish an “Economy 

Set  Point”  and  “Economy  Mode”  operating  periods.  This 

control system feature can help reduce operating costs during 

unoccupied, low load, or peak demand periods.

Printed on 2/8/2018 9:05 AM CT

Содержание 52

Страница 1: ...D NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE COMMERCIAL ELECTRIC WATER HEATERS OPTIONAL Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS 52 8...

Страница 2: ...death WARNING indicates a potentially hazardous situation which if not avoided could result in injury or death CAUTION indicates a potentially hazardous situation which if not avoided could result in...

Страница 3: ...pe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN Water temperature over 125 F 52 C can cause severe burns instantly resulting in severe in...

Страница 4: ...ONVERSION TO SINGLE PHASE 20 CONVERSION TO THREE PHASE 20 OPERATION 21 GENERAL 21 FILLING THE WATER HEATER 21 INITIAL START UP 21 Draining the Water Heater 21 TEMPERATURE REGULATION 22 High Temperatur...

Страница 5: ...he electrical system of the heater Never touch electrical components with wet hands or when standing in water When replacing fuses always use the correct size for the circuit see page 13 The principal...

Страница 6: ...390 410 307 246 205 176 154 137 123 112 102 95 88 36 122 868 492 369 295 246 211 184 164 148 134 123 113 105 40 5 138 226 554 418 3332 277 237 208 1185 166 151 138 128 119 45 153 585 615 461 369 307 2...

Страница 7: ...E VOLTS AC ELEMENTS EACH RATED MEASURED WATTS COMMERCIAL STORAGE TANK WATER HEATER MODEL NUMBER SERIAL NUMBER ITEM ID PART NUMBER WATTS TOTAL CAPACITY US GAL STANDBY LOSS MAX WORKING PRESSURE Low Lead...

Страница 8: ...8 FEATURES AND COMPONENTS Figure 2 Electronic Control Modules Printed on 2 8 2018 9 05 AM CT...

Страница 9: ...9 FEATURES AND COMPONENTS Figure 3 Surface Mount Control Models Printed on 2 8 2018 9 05 AM CT...

Страница 10: ...ions will not result in damage to the area adjacent to the heater or to lower floors of the structure Close to the point of major hot water usage and the power supply Hot water piping and branch circu...

Страница 11: ...ature are available Consult a qualified installer or service agency Follow all manufacturer s Instructions for installation of these valves Before changing the factory setting on the thermostat read t...

Страница 12: ...ature pressure relief valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating th...

Страница 13: ...shall not exceed 15 amperes for 14 AWG 20 amperes for 12 AWG and 30 amperes for 10 AWG copper or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper clad aluminum For dry locations onl...

Страница 14: ...es control circuit fusing using two 3 amp class G fuses with 600 volt rating Do not substitute fuses of a different rating SEQUENCE OF OPERATION 1 When the control is powered the UIM should display mo...

Страница 15: ...his table is to be used for 8 tap and 5 tap transformers Figure 4 Secondary Transformer Coil Table 5 Secondary Transformer Coil Configuration Volts Line On Load On 208 COMMON 208 SECONDARY 120V 240 CO...

Страница 16: ...16 Figure 5 CCB Control Circuit Diagram Electronic Control Models WIRING DIAGRAMS Printed on 2 8 2018 9 05 AM CT...

Страница 17: ...ing diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C Fusing consists of three 30 amp fuses...

Страница 18: ...llow wires to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service it may be...

Страница 19: ...ring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C Fusing consists of two 30 amp fuses f...

Страница 20: ...res to terminal L2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service it may be conn...

Страница 21: ...urn on the electrical disconnect switch 5 Observe the operation of the electrical components during the first heating cycle Use care as the electrical circuits are energized 6 Close the front panel Te...

Страница 22: ...ECO activate the water temperature must drop below 140 F 60 C before the control system can be reset Once the water temperature has cooled below this point the power supply to the water heater must be...

Страница 23: ...nt is adjusted to control water temperature This is an adjustable user setting in the control system s Temperatures Menu This and all control system menus are accessed through the UIM User Interface M...

Страница 24: ...rmation Screen below shows the control system Desktop Screen This is the default screen If there are no active Fault or Alert conditions and no user input for approximately 10 minutes the control syst...

Страница 25: ...sent heating elements the control system has not energized and is not sensing electrical current from Heating elements icon for a water heater equipped with 3 Banks of heating elements Each circle rep...

Страница 26: ...rmit tent operational problems or when the customer has reset the control system prior to a service agent s arrival Fault Occurrence Running total of all Fault and Alert Conditions that have occurred...

Страница 27: ...additional Bank of 3 heating elements OPERATING SEQUENCE With an Operating Set Point of 120 F and all Differential settings at 2 F the On Off sequencing of heating element Banks would be as follows B...

Страница 28: ...current state of the ECO high temperature limit switch contacts The ECO switch is located inside the immersion Temperature Probe two red wires Enable Disable 1 2 Displays the current state open or clo...

Страница 29: ...er In Economy Mode Displays whether the control system is currently operating in Economy Mode or not Daily Operating Mode Sun Mon Tue Wed Thu Fri Sat Seven daily sub menus are listed at the bottom of...

Страница 30: ...nal Button underneath CHANGE to activate the adjustment mode for the Setpoint Adjustment value Use the Up Down buttons to change the Setpoint Adjustment to the desired value The SetpointAdjustment val...

Страница 31: ...ANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm the new setting...

Страница 32: ...NGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to change the operating m...

Страница 33: ...current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault cond...

Страница 34: ...story Menu This menu displays non adjustable operational information The control system records and stores the last 9 Fault and Alert messages in chronological order in this menu The most recent will...

Страница 35: ...ment The heater tank is equipped with an anode rod to aid in corrosion control and should be inspected periodically see Anode Rod Inspection ANODE ROD INSPECTION Each water heater contains at least on...

Страница 36: ...in operation Allow the water heater to complete several heating cycles to ensure it is operating properly SEDIMENT REMOVAL Water borne impurities consist of fine particles of soil and sand which settl...

Страница 37: ...en the time required to heat water to the desired temperature 6 Look for hot water leakage 7 Sediment or pipe scale may be affecting water heater operation ABNORMAL SOUNDS 1 Sediment or lime scale acc...

Страница 38: ...ening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Water on the side of the tank may be condensation due to the panel or insulation not being in pl...

Страница 39: ...n the system 3 Service valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCUL...

Страница 40: ...be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCI...

Страница 41: ...ld be wired to and control the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMME...

Страница 42: ...rvice valves are shown for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK...

Страница 43: ...the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS WITH...

Страница 44: ...ol the pump between the water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 2 UNITS W...

Страница 45: ...for servicing unit However local codes shall govern their usage COMMERCIAL ELECTRIC 3 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRA...

Страница 46: ...ter heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH VERTICAL STORAGE TANK...

Страница 47: ...water heater s and the storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 3 UNITS WITH HORIZONTAL STORAGE T...

Страница 48: ...er local codes shall govern their usage COMMERCIAL ELECTRIC 4 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE...

Страница 49: ...rage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESS...

Страница 50: ...storage tank s 5 The water heater s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control COMMERCIAL ELECTRIC 4 UNITS WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE...

Страница 51: ...fold Kits with Three Heaters Tank Capacity Gallons Part Number H W D A 52 100109232 66 1 4 91 3 4 27 1 4 13 1 4 80 100109232 70 1 2 95 1 4 31 1 4 9 3 4 120 100109232 73 1 4 99 1 2 35 3 4 5 1 2 Inlet a...

Страница 52: ...52 Copyright 2017 All rights reserved www hotwater com Printed on 2 8 2018 9 05 AM CT...

Отзывы: