29
Figure 19. Economy Mode Setup Menu
Figure 20.
Setpoint Adjustment
Adjustable user setting (2°F to 50°F - factory default is 20°F)
the control system uses to calculate the “Economy Set Point.”
The Economy Set Point = normal Operating Set Point minus
the programmed Setpoint Adjustment value. The Economy Set
Point is the water temperature the control system maintains
during programmed Economy Mode time periods. “Economy
Set Point” is displayed instead of “Operating Set Point” and
“Economy Mode” appears beneath the current time on the
Desktop Screen during Economy Mode time periods.
Current Time
Seven Day 24 hr clock. Use this menu item to set the current
time and day of the week. Current day and time are not set from
the factory. “Clock Not Set” will be displayed on the Desktop
until the time/day has been initially set.
Heater In Economy Mode
Displays whether the control system is currently operating in
Economy Mode or not.
Daily Operating Mode (Sun - Mon - Tue - Wed - Thu - Fri -
Sat)
Seven daily sub menus are listed at the bottom of the Economy
Mode Setup menu. There are 3 Operating Modes in each sub
menu;
“Normal Operation All Day” - “Economy Mode All Day” and
“Normal Operation Between.” Only one Operating Mode can
be active, the factory default is Normal Operation All Day.
Normal Operation All Day:
When this operating mode is
active the normal Operating Set Point is used for the entire day.
Economy Mode All Day:
When this operating mode is active
the Economy Set Point is used for the entire day.
Normal Operation Between:
When this operating mode is
active there will also be start and stop times to program. The
normal Operating Set Point is used between the programmed
start and stop times and the Economy Set Point will be in effect
during the rest of the day. There is one start time and one stop
time event per day.