Performing maintenance
90
Instruction manual BFC
15
s
15.4.3
Clean heat exchanger
1. Detach the burner.
2. Clean the combustion chamber of the heat exchanger using a vacuum
cleaner and a soft brush.
3. Detach the chimney flue.
4. Clean the end of the heat exchanger using tap water.
5. Fit the burner.
6. Fit the chimney flue.
Note
Check the pressure differential again after cleaning. If the pressure
differential is too low following cleaning, please contact the supplier of the water
heater.
15.5 Finalizing
maintenance
See Eratta.
1. Fill the water heater (5 "Filling").
2. Start the water heater (9 "Starting the water heater")
3. Check the CO
2
value (3.11.3 "CO
2
adjustment").
4. Check the switching pressure of the pressure switch. (3.11.4 "Switching
pressure measurement")
5. Erase the message
SERVICE REQUIRED
. Do this by pressing once on
then once on
.
Содержание 120 through 250 Series
Страница 4: ...E2 ...
Страница 6: ...4 Instruction manual BFC gis ...
Страница 10: ...Contents 8 Instruction manual BFC ...
Страница 31: ...Instruction manual BFC 29 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33 ...
Страница 48: ...Conversion to a different gas category 46 Instruction manual BFC 4 is ...
Страница 58: ...Status of the water heater 56 Instruction manual BFC 8 gis ...
Страница 62: ...Shutting down 60 Instruction manual BFC 10 gis ...
Страница 74: ...Service program 72 Instruction manual BFC 12 is ...
Страница 88: ...Service interval 86 Instruction manual BFC 14 is ...
Страница 97: ...Instruction manual BFC 95 is ...
Страница 100: ...Appendices 98 Instruction manual BFC 17 is 17 4 Declaration of conformity Declaration of conformity ...
Страница 102: ...Instruction manual BFC 100 ...