13.4 Warnings on the display
Warnings on the display
Indication
Cause
Measure
Remark
Maximum burning
hours: Service
required.
The actual burning
hours have exceeded
the preset burning
hours.
Water heater runs, but displays a warning
For maintenance to your water heater, please contact your
installation engineer.
Anode protection not
working.
•
The cables
between the
potentiostat and
anodes are loose or
have been
connected
incorrectly.
•
The earth
connection of the
anodes is loose.
•
The water heater is
not filled with water.
Water heater runs, but displays a warning.
Note
The water heater is functioning, but there is no anode protection
for the tank.
1. Connect the wiring correctly and the warning will disappear.
2. If the wiring is correct but the warning remains, check that the
earth connection is good and whether the tank is filled with
water.
Содержание 120 through 250 Series
Страница 4: ...E2 ...
Страница 6: ...4 Instruction manual BFC gis ...
Страница 10: ...Contents 8 Instruction manual BFC ...
Страница 31: ...Instruction manual BFC 29 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33 ...
Страница 48: ...Conversion to a different gas category 46 Instruction manual BFC 4 is ...
Страница 58: ...Status of the water heater 56 Instruction manual BFC 8 gis ...
Страница 62: ...Shutting down 60 Instruction manual BFC 10 gis ...
Страница 74: ...Service program 72 Instruction manual BFC 12 is ...
Страница 88: ...Service interval 86 Instruction manual BFC 14 is ...
Страница 97: ...Instruction manual BFC 95 is ...
Страница 100: ...Appendices 98 Instruction manual BFC 17 is 17 4 Declaration of conformity Declaration of conformity ...
Страница 102: ...Instruction manual BFC 100 ...