Page 11 of 24
P/N 595370-01 Rev B 07/19
Inspect and test the distress alarm along with the inspection and testing
of the SCBA before each use. Include the following inspection procedures
with the REGULAR OPERATIONAL INSPECTION procedures defined
in your SCBA instructions. If any malfunction of the SCBA or the distress
alarm is noted during the inspection, remove the SCBA from service and
tag it for repair by authorized personnel.
WARNING
FOLLOW REGULAR OPERATIONAL INSPECTION
PROCEDURE EXACTLY. IF THE DISTRESS
ALARM DOES NOT ACTUATE OR DOES NOT
OPERATE AS DESCRIBED, OR IF ANY OTHER
OPERATIONAL MALFUNCTION IS NOTED, DO
NOT USE THE SCBA.
WARNING
THE PROPER OPERATION OF THE LOCATOR
SYSTEM CANNOT BE CHECKED WITHOUT
CHECKING ALL COMPONENTS OF THE SYSTEM
TOGETHER. THE REGULAR OPERATIONAL
INSPECTION MUST INCLUDE THE
HHR
AND THE
TRANSMITTER WORKING WITH EACH OTHER
TO CONFIRM PROPER OPERATION. FAILURE TO
PROPERLY INSPECT THE COMPLETE SYSTEM
MAY RESULT IN FAILURE OF ONE COMPONENT,
WHICH COULD LEAD TO SERIOUS INJURY OR
DEATH.
CAUTION
THE PERFORMANCE PROPERTIES OF THE
DISTRESS ALARM CANNOT BE PROPERLY
TESTED IN THE FIELD.
WARNING
I N S E V E R A L O F T H E I N S P E C T I O N
PROCEDURES DESCRIBED, A FULL ALARM
WILL BE OBSERVED. THE FULL ALARM
CONDITION INCLUDES AN AUDIBLE TONE
THAT CAN EXCEED 95 DBA AT 3 METERS
(9.9 FT.). TO PREVENT POSSIBLE HEARING
DAMAGE DURING TEST, IMMEDIATELY RESET
THE ALARM ON VERIFICATION THAT IT IS
FUNCTIONING PROPERLY. WEAR HEARING
PROTECTION IF PROLONGED OR REPEATED
EXPOSURE TO A FULL ALARM CONDITION IS
ANTICIPATED.
REGULAR OPERATIONAL INSPECTION
INSPECTION OF THE DISTRESS ALARM
NOTE
IN SEVERAL OF THE INSPECTION PROCEDURES DESCRIBED, A
FULL ALARM WILL BE OBSERVED. THE FULL ALARM CONDITION
INCLUDES AN AUDIBLE TONE THAT CAN EXCEED 95 DBA AT 3
METERS (9.9 FT.). TO PREVENT POSSIBLE HEARING DAMAGE
DURING TEST, IMMEDIATELY RESET THE ALARM ON VERIFICATION
THAT IT IS FUNCTIONING PROPERLY. WEAR HEARING PROTECTION
IF PROLONGED OR REPEATED EXPOSURE TO A FULL ALARM
CONDITION IS ANTICIPATED.
NOTE
IF THIS INSPECTION IS DONE IN DIRECT SUNLIGHT IT MAY BE
HELPFUL TO SHADE THE LENS ON THE CONTROL CONSOLE
WITH YOUR HAND TO BE SURE THE LIGHTS ARE FLASHING AS
DESCRIBED.
1.
While performing the visual inspection of the SCBA, visually inspect
all distress alarm enclosures, lenses, and wire conduits for cracks,
wear or other damage. If any damage is found, remove the SCBA from
service and tag it for repair by qualified personnel.
2.
With the cylinder valve closed, press the manual alarm button, located
on the front of the distress alarm control console. The manual alarm
sounds a loud, almost continuous, 3-tone chirp accompanied by
flashing of the red signal light on the control console
3. Reset the manual alarm by pressing the reset button
twice
(fully
depress the reset button on the side of the control console, release,
and press again). The unit will sound three chirps and the green light
will flash.
4. Turn the distress alarm OFF by pressing the reset button
twice
again.
The unit will sound a two-tone chirp and the green light will go out.
5.
Open the cylinder valve to pressurize the SCBA system. The
distress alarm sounds 3 quick chirps and the light on the control
console flashes green about once per second. The 3 chirps sound at
approximately the same time the VIBRALERT in the mask-mounted
regulator actuates briefly. Make sure the air flow is stopped by pressing
the air saver/donning switch.
6. To check the pre-alarm, leave SCBA motionless for twenty (20)
seconds. The green flashing light is replaced by a red flashing light. An
ascending/descending tone sounds, increasing in volume. Leave the
SCBA motionless.
If your distress alarm is NOT equipped with the Locator System, perform
the REGULAR OPERATIONAL INSPECTION as defined on pages 11-12
of this instruction.
If your distress alarm IS equipped with the Locator System (as signified
by the two red labels on the Sensor Module), perform the REGULAR
OPERATIONAL INSPECTION as defined on pages 13-15 of this
instruction.
Содержание SCOTT PAK-ALERT
Страница 23: ...Page 23 of 24 P N 595370 01 Rev B 07 19 NOTES ...