background image

 

8 78-8127-8864-0-C

4.3  Clean cables using standard practice:

 

a. Do not allow solvent or abrasive to contact the cable semi-conductive insulation shield.

 

b. Do not reduce cable insulation diameter below 1.04" (26,4 mm) specified for the splice.

 

c.  The insulation surface must be round, smooth and free of cuts/voids. Sanding may be necessary, finish 

sanding should be done with a 120 grit or higher electrical grade abrasive.

 

d.  Make certain that the cable insulation is smooth, clean and dry before continuing.

4.4  Apply 3M

 Red Compound P55/R on cable insulations, making certain to fill in edge of cable semi-con. 

Do 

not use silicone grease

 

(Figure 14).

Fill semi-con step

Fill semi-con step

Apply 3M™ Red

Compound P55/R

Apply 3M™ Red

Compound P55/R

Figure 14

Note:  This core installs differently than other cold shrink products.

4.5  Position the splice body over connector area, aligning end of the splice body (not the core) at the center 

of the tape marker. 

Slowly

 start to remove the splice core by pulling and unwinding the loose core end 

counterclockwise, allowing only ¼" (6 mm) of the splice to shrink onto the tape marker. Carefully slide the 

splice body off the tape marker by pulling and twisting until the entire tape marker is exposed. Continue 

removing the core to complete the splice body installation 

(Figure 15).

Note:  The splice body ends must overlap onto the semi-con of each cable by at least 1/2" (13 mm).
Note:   Do not push the splice body toward the tape marker as this may cause the end to roll under. If the end 

does roll under, DO NOT use sharp-edged tools to pull it out as this could cut and damage the splice.

Unwind Counter-clockwise

Align splice body with tape marker

Figure 15

Содержание QS4-15JCN-350-750

Страница 1: ...e Kit Number Cable Insulation O D Range Conductor Size Range QS4 15JCN 350 750 1 04 1 70 26 4 43 2 mm 350 750 kcmil 185 325 mm2 Splices including size transitions can be made to smaller or larger conductors but larger conductors may require special neutral handling provided both cables are within the Insulation O D Range and the connector meets the dimensional requirements shown below Connector Di...

Страница 2: ...ubber Mastic Tape 2228 Rolls 2 x 36 2 ea e Scotch Mastic Strips 2230 6 length 9 ea f Cold Shrink Adapter Tube 1 ea g 3M Cable Cleaning Pads CC 3 1 ea h Cut back Template 1 ea i Wire Brush 1 ea j Instruction Booklet 1 ea Cold shrink adapter tube may not be included in all kits Note Do not use knives to open plastic bags Note Connector not shown but if included it is indicated on the packaging label...

Страница 3: ...24 mm Cable Jacket Neutral Wires Insulation Semi con 4 102 mm 8 1 4 210 mm Figure 1 2 3 Clean or cover cable jacket 30 760 mm from jacket edge on side where splice body will be parked 2 4 Select a Scotch Mastic Strip 2230 from the kit and remove white release liners Using light tension apply a single wrap of mastic at the edge of the cable jacket and partially over the neutral wires Figure 2 Cable...

Страница 4: ...e jacket edge under the neutral wires Figure 3 Knead mastic around neutral wires Insulation Semi Con Neutral Wires Scotch Mastic Strip 2230 Scotch Mastic Strip 2230 Fold mastic strip in half lengthwise Bend neutral wires over cable jacket Figure 3 2 6 Apply an additional single wrap of Scotch Mastic Strip 2230 at the edge of the cable jacket and partially over the neutral wires Overwrap mastic wit...

Страница 5: ...le jacket Figure 5 3 0 Install Connector Note If using a crimp type connector go to step 3 3 3 1 If using a 3M Shearbolt Connector QCI 350 750 refer to the instructions included with the connector for insulation cut back dimension Insulation removal length shall not exceed 3 1 2 89 mm from conductor end Figure 6 Refer to connector instructions for dimensions Figure 6 3 2 Install 3M Shearbolt Conne...

Страница 6: ...uminum connector crimped with a specific tool and die Aluminum Al Cu Crimp Connector Growth Chart Conductor Size Typical growth allowance per end 350 500 kcmil 1 4 6 mm 750 kcmil 3 8 10 mm Note 1 Copper connectors do not require a length change allowance 2 Maximum aluminum connector crimped length allowed is 7 50 191 mm One half connector length growth allowance Figure 8 3 4 For 350 and 500 kcmil ...

Страница 7: ...inhibitor from connector ends Figures 10 and 11 File sharp connector flashing if necessary taking care to remove all metal filings from splice area Antioxidant Compound Figure 10 Connector Figure 11 4 0 Install Splice 4 1 Apply a tape marker to semi con insulation shield on cable which does not contain splice Measure 10 254 mm from center of connector Figure 12 Tape Marker Semi con 10 254 mm Figur...

Страница 8: ...igure 14 Note This core installs differently than other cold shrink products 4 5 Position the splice body over connector area aligning end of the splice body not the core at the center of the tape marker Slowly start to remove the splice core by pulling and unwinding the loose core end counterclockwise allowing only 6 mm of the splice to shrink onto the tape marker Carefully slide the splice body ...

Страница 9: ...and tighten the shield sleeve outward and secure it along with the ground braid if not grounding externally to the neutral wires on either side of the splice using two constant force springs on each end between the vinyl tape at the jacket edge and the vinyl tape as shown Figure 16 5 3 If shield sleeve extends beyond neutral wires it may be interwoven with the constant force springs Trim excess gr...

Страница 10: ...If shield sleeve extends beyond neutral wires it may be interwoven with the constant force springs Trim excess ground braid if needed Cinch tighten the spring after wrapping the final winding Figure 18 Ground Braid Constant Force Springs Cable Jacket Rejacketing Tube Vinyl Tape Figure 18 5 8 Place one mastic sealing strip on the cable jacket under the solder block of the ground strap no farther th...

Страница 11: ...ile as low as possible For C tap or H tap connectors position flat against the cable Crimp connector following the connector manufacturer s recommendations Figure 22 Ground Wire Connector Ground Braid Figure 22 6 2 Cut one mastic sealing strip into two equal pieces Place one piece on the cable jacket centered under the ground wire near the jacket end Roll two mastic strips into small rolls Place o...

Страница 12: ... mastic and ground wire Press the mastic around the ground wire and to the cable jacket Figure 24 Second Half Mastic Strip Ground Wire Figure 24 6 4 Wrap two half lapped layers of vinyl tape over the ground connector Figure 25 Vinyl Tape Ground Wire Mastic Seal for Ground Wire Figure 25 ...

Страница 13: ...ure 27 If grounding was applied apply tape over mastic strips 2 rubber mastic 2 rubber mastic Figure 26 Stretch and tear off last 1 2 25 50 mm of rubber mastic Figure 27 7 2 Remove the clear plastic wrap Install the rejacketing tube by twisting the tube not the yellow liner from side to side to start the movement Then slide and unroll the tube over the constant force springs and rubber mastic Figu...

Страница 14: ...ct optional grounding Note In applications where the splice is regularly exposed to high levels of ultra violet radiation i e direct sunlight wrap two half lapped layers of Scotch Super 33 Vinyl Electrical Tape or Scotch Vinyl Electrical Tape Super 88 over the re jacketing tube ...

Страница 15: ... 1 3 U 2 H 7 8 2 H 7 8 3 u C l A 2 1 0 0 2 0 0 4 4 T R A 2 3 U 1 4 H 4 9 4 H 4 9 2 2 u C 4 1 0 0 1 0 0 5 2 R 4 3 A 2 T R 4 3 U 3 n w o r B 3 H 7 8 2 u C l A 4 1 0 0 2 0 0 5 4 T R A 4 3 U 1 3 H 6 0 1 4 H 6 0 1 2 2 u C 4 1 0 1 1 0 0 5 4 R 4 3 A 3 T R 4 3 U 4 n w o r B 4 H 7 8 3 u C l A 0 0 5 I C 0 0 5 3 T R A 4 3 U 3 H 6 0 1 3 u C l A 6 1 0 0 2 0 0 6 4 T R A 6 3 U 1 3 H 5 1 1 3 3 u C 9 1 0 0 1 0 5 7...

Страница 16: ... writing by an authorized officer of 3M Warranty Limited Remedy Limited Liability This product will be free from defects in material and manufacture at the time of purchase 3M MAKES NO OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE If this product is defective within the warranty period stated above your exclusive remedy sh...

Отзывы: