78-8127-8864-0-C 5
2.7 Slide integrated splice body onto clean cable jacket, loose core end first
(Figure 5).
If the splice body contains
a long built-in ground strap for external grounding, ensure that the long ground strap is on the side of the splice
where the external grounding will be located
.
Loose core end
Integrated splice body
Cleaned cable jacket
Figure 5
3.0 Install Connector
Note: If using a crimp-type connector, go to step (3.3).
3.1 If using a 3M
™
Shearbolt Connector QCI 350 - 750,
refer to the instructions included with the connector for
insulation cut-back dimension. Insulation removal length shall not exceed 3 1/2" (89 mm) from conductor end
(Figure 6).
Refer to connector instructions for dimensions
Figure 6
3.2 Install 3M Shearbolt Connector QCI 350 - 750 according to the instructions included with the connector
(Figure 7).
Connector
Shearbolt
Figure 7
Go to section 4.0 “Install Splice.”