4. CONTROL

Service menu

MENU - MODE

MENU - HW SETTING

Enter code 1616 to access the service menu

1616

Choose this 

menu after 

centring the 

screen and 

tapping on enter

Access menu

Access selected 

menu

Delete/return

MANUAL control

Ad 1)

Ad 2)

Ad 3)

Door contact (NO/NC)

External control contact 

(NO/NC)

Error contact (NO/NC)

Ad 1)

 – External temperature sensor activation/settings 

 

None - 

Can not be changed with the COMFORT regulator

 

Ad 2)

 - Sets the external contact input behaviour. Options:

 

None

 – inactive

 

External control

 – External switching of device

 

Ad 3)

 - Thermostat (NO/NC)

Use this menu to set the detailed behaviour of the inputs and 

outputs of the regulators

MENU - MODBUS RTU

Address 

1~247

Parity 

None

Odd

Even

Communication speed: 

        4800 Bd

        9600 Bd

        14400 Bd

        19200 Bd

        38400 Bd

Use this menu to set the Modbus RTU communication 

parameters

An incorrect setting may prevent communication with the 

regulator

MENU - FILTER TIMER

MENU - TEMPERATURE SENSOR

Current timer 

status

Set the time after which 

a notice will appear in 

the main screen.

1000h ~ 5000h

Shows the status of the

clogged filter in the main screen

RESET button 

(use after replacing 

filters)

Use this menu to set the period (in motor hours) after which 

you will be reminded to replace the filters or reset to timer.

Available only in automatic mode 

Use this menu to select the sensor to be used for primary 

temperature control

Options:

 

None

 

Thermostat

 – Room thermostat (ON/OFF)

 

N

oNe

Содержание ESSENSSE NEO COMFORT

Страница 1: ...ESSENSSE NEO COMFORT EN Installation and operation instructions ...

Страница 2: ...ed Check that it corresponds to the type of product ordered In case of discrepancy do not unpack the product and con tact the vendor After unpacking check that the product and all the other components are in good order In case of doubt contact the vendor Do not install a damaged unit If you will not unpack the product immediately after delive ry store it indoors in a dry place with ambient tempera...

Страница 3: ... CONTACT EXTERNE ON OFF 53 54 51 52 CONTACT INCENDIE CMSI 62 61 BOOST BOOST 57 58 boitier de commande J1 J2 GND GND 15 13 14 9 8 7 10 5 4 3 2 1 6 12 11 16 17 18 19 20 21 22 23 24 82 83 81 80 79 78 77 76 75 74 73 25 26 27 28 29 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 31 33 35 36 37 38 39 40 41 42 43 9 44 45 46 47 48 49 50 30 32 34 72 71 70 69 GND N L LO L LO L LO N GND GND 0 10V SSR S...

Страница 4: ... 77 76 75 74 73 25 26 27 28 29 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 31 33 35 36 37 38 39 40 41 42 43 9 44 45 46 47 48 49 50 30 32 34 72 71 70 69 LO L LO N GND GND 0 10V SSR SSR GND 0 10V 230VAC FLAP EXT 230VAC W PUMP ALARM HEATER RUN OUTPUT COOL HEAT HEAT PUMP HEAT PUMP ERROR DEFROST EXTERNAL ON OFF FIRE BOOST PRESENCE SENSOR PIR REC ERR VENT EXT HEATER COOL PUMP PREHEATER 0 10V G...

Страница 5: ...1 2 DK 1 DK B3 door contact TECHNICAL INFORMATION Isolated switching contact with maximum voltage 12V Cable Two core cable with a cross section of 0 5 mm2 Maximum length 50 m ATTENTION Not included with the product 2 1 3 Thermostatic valve TV1 1 TECHNICAL INFORMATION Thermostatic valve to regulate the water exchanger Suitable for all types of curtain with water exchanger Works independent to the e...

Страница 6: ...TION Not included with the product 3 COMMISSIONING PLEASE NOTE Before starting up the unit check the following Did you leave inside tools or objects that could damage the unit Is the supply of energy and heating water if applicable adequate Is the unit well closed Is the control module properly connected Does the unit have adequate protection according to the applicable standards ...

Страница 7: ...ly the display lights up and the data is loaded The device is ready to be activated once the service data has fully loaded The remote control has a touch screen The device is controlled tapping the symbols on the screen They only inform about status not errors They inform about errors Clicking on them opens a screen with the error report The menus are described below page 13 page 14 page 17 Turn t...

Страница 8: ...d temperature settings with closed doors Air flow settings with closed doors Language Display backlight Parameters Date and time NFC Timer Back to previous screen Confirm return Confirm return Display required air flow three speeds Reduce or increase opening s air flow with closed doors Display the current air flow status Current date and time Reduce or increase required tempe rature Required temp...

Страница 9: ...e set the unit goes on stand by mode after the timer expires There are 5 languages available Confirm return Display backlight when on Lightning level on stand by Back to main screen The NFC menu allows devices compatible with Near Field Communication NFC to transmit relevant information Mobile telephones and tables are usually fitted with this chip Check whether your device has this feature before...

Страница 10: ...e inputs and outputs of the regulators MENU MODBUS RTU Address 1 247 Parity None Odd Even Communication speed 4800 Bd 9600 Bd 14400 Bd 19200 Bd 38400 Bd Use this menu to set the Modbus RTU communication parameters An incorrect setting may prevent communication with the regulator MENU FILTER TIMER MENU TEMPERATURE SENSOR Current timer status Set the time after which a notice will appear in the main...

Страница 11: ...gs can be accessed without password Full Only the information menu can be accessed without password User mode Special user mode see image below End of winter period month number Mode Fixed Start of winter period month number Enable disable function Enable disable function Fixed mode settings Ventilation rate with open doors 33 100 Heating settings with open doors Manual 0 50 100 Timed rundown at m...

Страница 12: ...controller connection Option 1 ON ON CP 1 CP 2 ON ON ON ON OFF OFF Electric connection Option 2 CP 1 CP 2 CP 1 CP 2 CANH CANL GND 12V ON ON ON ON Electric connection Option 2 OFF OFF Ad 1 Use one door contact as main Its status will be sent to the SLAVE regulators and it will no longer be necessary to connect it to each regulator if required Not allowed the door contact will not transmit to the SL...

Страница 13: ...reset the MENU 1616 FILTER TIMER 46 Heater malfunction Unit out of order Heater malfunction Check the heater and the condition of the safety thermostat Does the heater have proper cooling Check engine running 65 Communication error Unit out of order Communication error Check the communication cable for damages and if it is properly connected Observe the wiring diagram to prevent occurrences that m...

Страница 14: ...ier s Give the following information to the supplier or service type designation of the air curtain accessories in use place of installation serial number conditions of the installation incl electrical period of operation detailed description of the malfunction 7 2 DECOMMISSIONING THE PRODUCT LIQUIDATOIN Before scrapping the product make it unusable Old products still have raw materials that can b...

Страница 15: ...15 8 WIRING DIAGRAM RGJ VCES2 CO S MA ...

Страница 16: ...16 RGJ VCES2 CO E MA 8 WIRING DIAGRAM ...

Страница 17: ...17 RGJ VCES2 CO V MA 8 WIRING DIAGRAM ...

Страница 18: ...18 RGJ VCES2 CO S SL 8 WIRING DIAGRAM ...

Страница 19: ...19 RGJ VCES2 CO E SL 8 WIRING DIAGRAM ...

Страница 20: ...20 RGJ VCES2 CO V SL 8 WIRING DIAGRAM ...

Страница 21: ...N In case of any doubt or query do not hesitate to contact our sales or technical support departments CONTACT Address 2VV s r o Poděbradská 289 530 09 Pardubice Czech Republic Internet http www 2vv cz contact distribution php ...

Отзывы: