Page 16
OWNER'S MANUAL
About Advanced Features & Operation
CYCLES PER HOUR - The Cycles Per Hour setting
(
page 16)
monitors the number of times per hour
your HVAC unit may energize. For example, at a
setting of 6 cycles per hour the HVAC unit will only
be allowed to energize once every 10 minutes. The
Cycles Per Hour limit may be temporarily overridden
by pressing the WARMER or COOLER button.
TWO STAGE OPERATION - The 2nd stage of heat
(auxiliary heat) is turned on when the room temp-
erature is equal to or less than:
the setpoint minus
the 1st stage deadband (one degree, adjustable),
minus the 2nd stage deadband (two degrees, non-
adjustable).
Heat or Cool
Setpoint
Deadband
Deadband
db 1
db 2
(adj. 1-6 )
1st Stage
turn on
2nd Stage
turn on
Heating
(non-adj. 2 )
Deadband
db 1
(adj. 1-6 )
1st Stage
turn on
Cooling
Press NEXT
to advance
Press NEXT
to advance
Press the PROGRAM button to exit Advanced Setup.
Indicates that the ther-
mostat jumper is set for
an
O
reversing valve
(energize in cooling) or
a
b
reversing valve
(energize in heating).
ON
indicates that the
thermostat jumper is
set for Electric Heat
operation, or
OFF
for
Gas/Electric or Heat
Pump operation.
0
NEXT
NEXT
S1-THEU21P7S