background image

Page 1 of 4

FINZ Mar 2007

A division of Terry Young Ltd.

INSTALLATION INSTRUCTIONS FOR

FINZ FREESTANDING WOODBURNER

March 2007

TESTED TO NZS 7421-1990

A.

 Yunca recommends that competent trades persons carry out all installations. (e.g. NZHHA

Registered Installer) to obtain maximum performance and safe, efficient heating.

B. 

A permit is required and we suggest you check with your local building inspectors as by-

laws can vary from area to area.

Also notify your Insurance Company that a space heater has been installed.

C. 

Floor Protector -

1. Must extend at least 300mm in front of closed door.

2. Must extend at least 100mm on each side of heater.

3. Spill  hearth  must  be  constructed  of  non-combustible  material,  with  a  minimum

thickness of 12mm.

D

 Seismic Restraint – Heater must be restrained from seismic movement as required by NZS

7421. 10mm Diameter bolting holes in the feet of the FINZ allow restraint.

F

 Manufacturers recommended minimum clearances from combustible walls:

APPLIED RESEARCH tested to NZS 7421-1990

Clearance

Rear Clearance (with YUNCA flue guard fitted)

70mm

Side Clearance (with YUNCA flue guard fitted)

160mm

Corner Clearance (with YUNCA flue guard fitted)

60mm

G. YUNCA Flue Kit

4.2 m x 150 mm stainless steel flue.

1 x weather cap & cowl

2.4m x 250mm galvanised liner

2 x spider brackets

1 x ceiling tile           1 x secondary shield

I. Accessory 1200 Flue Guard Kit

(Additional optional full length guard)

1 x 1200 length back guard.

1 x 1200 length perforated front guard.

1 x joining collar

H. YUNCA Flue Mounted Shield 

(Flue Guard)

1 x 1200mm length back guard plus an optional

900mm adjustable extension.

1 x 1200mm length perforated front guard 

1 x 1200mm length tertiary back guard with spacers.

1 x Top front deflector shield (half round shape,

angled when installed). (Optional)

J. Accessory 600 Flue Guard Kit

(Additional optional half length guard)

1 x 600 length back guard.

1 x 600 length perforated front guard.

1 x joining collar

Please Note: 

All joints must be sealed with flue sealing compound. Use stainless steel

screws or rivets to join the flue pipe (three equally spaced places at each joint). The first

length of flue pipe must be screwed to flue spigot. The required minimum flue

termination height is 4.6 m above the floor protector.

The minimum Flue Mounted Shield (Flue Guard) height Is 1200mm.

Summary of Contents for FINZ

Page 1: ...ue guard fitted 70mm Side Clearance with YUNCA flue guard fitted 160mm Corner Clearance with YUNCA flue guard fitted 60mm G YUNCA Flue Kit 4 2 m x 150 mm stainless steel flue 1 x weather cap cowl 2 4m x 250mm galvanised liner 2 x spider brackets 1 x ceiling tile 1 x secondary shield I Accessory 1200 Flue Guard Kit Additional optional full length guard 1 x 1200 length back guard 1 x 1200 length per...

Page 2: ...case the length of the flue shall not be less than 4 6m from the ash floor protector In some situations the Local Council may vary the above requirements 2 All parts of the chimney exposed to the outside air shall be suitably insulated in accordance with the manufacturers recommendations When loose fill insulation is used in the adjacent ceiling space maintain clearance between the secondary shiel...

Page 3: ...TED Measurements in millimetres A B E F G H 70 160 60 270 500 442 MINIMUM FLOOR PROTECTION MEASUREMENTS WITH YUNCA FLUE MOUNTED SHIELD FITTED Measurements in millimetres C D J K L M N O P 300 100 880 1007 1362 1203 737 680 707 Above Non combustible wall clearances Brick lining from floor to within 25mm of ceiling Leave air vents at the bottom to allow airflow in the cavity If Yunca flue mounted sh...

Page 4: ...ication of components may result in hazardous conditions Where such action is considered the manufacturer should be consulted in the first instance E Cracked and broken components e g glass panels or fire bricks may render the installation unsafe IF THE A WATERBOOSTER IS FITTED Note A water booster cannot be fitted in some Clean Air zones check local council regulations A Do not connect to an unve...