background image

9

protected from harmful climate impacts. If stored for a period longer than 1 year we recommend the oil charge to be 
replaced prior to commissioning. Any manipulation with the actuators at temperatures lower than -25 °C is forbidden.  
It  is  impermissible  to  store  actuators  outdoor  or  in  areas  unprotected  from  rainfall,  snowfall  and/or  ice.  Surplus 
preservative grease must be only removed before commissioning the actuator. When storing unpacked actuators for  
a period exceeding 3 months, we recommend you to insert a small bag with silica gel or another suitable desiccant 
material into the terminal box.

7.  CHECKING OF THE INSTRUMENT FUNCTION AND ITS LOCATION

Before starting to install the device, again check actuator for any damage suffered in the course of storage.
The function of electric motor can be verified by connecting it to power supply through a switch and by powering it up 

shortly. It is sufficient to observe if the electric motor starts up and if the output shaft starts rotating. Rotary actuators can 
operate in any position when the electric motor axis is not more than 15 degrees below the horizontal level. Actuators must 
be located in an area providing easy access to manual control wheel, terminal box and control box. Also, i t must be verified 
again if the location meets the provisions of section

 “Operating Conditions”.

 If local conditions require another method of 

installation, manufacturer’s approval must be obtained.

8.  ATTACHMENT

Set actuator onto the valve so that its output shaft reliably fits into the valve coupling. Use four

 (eight) 

screws to connect 

actuator with valve. Turn hand wheel to check correct connection between actuator and valve. Remove cover of terminal box 
and carry out electrical connection of actuator according to internal connection diagram.

9.  ADJUSTMENT OF THE ACTUATOR

Having fitted the actuator onto the valve and checked for correct mechanical connection proceed with the actual set-up 

and adjustment.

1.  Shift the actuator manually to an intermediate position.
2.   Connect the actuator to power supply line, and shortly switch to verify correct rotation direction of the output shaft. 

When  looking  inside  the  control  box,  the  drive  wheel  of  the  positioning  units  will  rotate  clockwise,  while  moving  in 

“closing“

 direction.

3.   Electrically set actuator close to

 “closed”

 position, use hand wheel to arrive precisely at the 

“closed”

 position. In this 

“closed”

 position set the positioning unit 

(micro switch SQT1 (PZ) according to point 5c).

4.   Set output shaft to a position, where the signalling switch SQT2 

(SZ)

 is supposed to change over. Adjust SQT2 

(SZ) 

switch according to instructions specified under point 5b).

5.   Turn the actuator output shaft by the required number of revolutions 

(working stroke)

 and set the switch to SQC1 

(PO)

 

“open” 

position as described under point 5c).

6.   Set output shaft of the actuator to the position, where the signalling switch SQC2

 (SO)

 is supposed to change over. Adjust 

the SQC2 

(SO)

 switch according to instructions specified under point 5b). Setting of positioning and signalling switches 

must be checked repeatedly.

Important notices

a)   After  mounting  the  valve  with  the  actuator  on  the  pipeline  use  hand  wheel  of  the  actuator  to  set  the  valve  

into its central position. Short-term running of the electric motor must be used to detect whether the actuator 
output  shaft  rotates  in  the  correct  direction,  i.e.,  whether  it  responds  correctly  to  the  shutdown  using  the  
appropriate torque or positioning switches. Verification can be performed by pressing the handle of the respective 
switch with a suitable tool preferably made of insulating material or at least with a handle made of insulating 
material.

 

      If the actuator does not rotate in the right direction, switch the two phase conductors at the terminal board of 
the actuator 

(terminals 1, 2, 3).

b)   After mounting the valve with the actuator on the pipeline it is necessary to mount a pressure relief valve to the 

power cabinet of the actuator. For this purpose there is a power cabinet of the actuator provided with holes with 
plug bolts. A pressure relief valve is mounted into the uppermost hole instead of the plug bolt, whereby it must 
be ensured that the pressure relief valve axis is vertical.

Summary of Contents for MODACT MOA OC

Page 1: ...Type numbers 52070 3xxx 52074 3xxx Electric multi turn rotary actuators for nuclear power stations inside active zones 10 19 INSTRUCTION FOR ASSEMBLY AND OPERATION...

Page 2: ...ZPA Pe ky a s is certified company in accordance with ISO 9001 as amended...

Page 3: ...re 85 to 103 2 kPa relative humidity up to 95 3 radiation level up to 1 Gy hr Working mode of a small scale accident VVER reactors RBMK reactors temperature up to 90 C up to 105 C pressure up to 170 k...

Page 4: ...motor the control lever and thus the clutch automatically return to the motor control position To allow tripping of the electric motor upon reaching the desired torque on the output shaft the worm is...

Page 5: ...ping switches SQFC1 MO 21 Adjuster 22 Torque control shaft 23 Top closing segment 24 Bottom opening segment 25 Locking closing screw 26 Locking opening screw 27 Bottom closing indicator 28 Bottom open...

Page 6: ...ment lies outside the area between the two coloured lines on the scale Once the tripping torque has been set up tighten locking screw 25 or 26 and locking nut 44 Tripping torque must be set at a highe...

Page 7: ...there is a pinion 49 which is connected to the shaft 48 via and adjustable friction clutch Notice After each handling with locking screws in the control part of the actuator these screws must be secu...

Page 8: ...switch button is pressed Now the micro switch has been adjusted Then slide tripping rod 58 out as described above 6 PACKING AND STORING The actuators are packaged together with the valve on which the...

Page 9: ...diate position 2 Connect the actuator to power supply line and shortly switch to verify correct rotation direction of the output shaft When looking inside the control box the drive wheel of the positi...

Page 10: ...in the control cabinet with CIATIM 221 grease To increase the corrosion resistance also grease springs in the control cabinet Grease must not be applied on the sliing seats in the torque unit In all...

Page 11: ...s in adjustment and in function or determine the procedure for its remove 2 Small repairs in case of loss of functionality or damage at the actuator operator is possible to do small repairs as for exa...

Page 12: ...0 40 63 1 22 6 1 1 67 63 MOA OC 40 100 5 2 0 7 0 3 x 3 0 100 1 14 4 55 63 MOA OC 50 25 5 2 0 7 0 3 x 5 0 25 50 25 1 57 3 106 53 MOA OC 63 12 5 2 0 7 0 3 x 9 0 12 5 1 57 3 250 130 63 MOA OC 63 25 5 2 0...

Page 13: ...Z 0 55 1403 66 0 43 6 2 4 5 3 0 21 16 AJSI 145B 4Z 1 2 1425 76 3 0 51 6 7 6 2 4 5 40 32 AJSI 145B 4Z 1 2 1425 76 3 0 51 6 7 6 2 4 5 40 32 AJSI 145B 4Z 1 2 1425 76 3 0 51 6 7 6 2 4 5 40 32 AJSI 145B 8Z...

Page 14: ...0 130 d3 102 140 165 d4 M 10 M 16 M 20 number of threaded 4 4 4 holes h1 min 12 5 20 25 1 25 d4 h max 3 4 5 d7 42 60 80 h2 10 12 15 b2 H11 14 20 24 d6 30 41 5 52 d9 H8 20 30 40 16 min 55 76 97 t3 22 8...

Page 15: ...300 720 A Dimensional drawing of MODACT MOA OC electric actuators t no 52 070 52 071 52 072 Dimension mm Type number 52 070 52 071 52 072 A B C D E F G H J K L N O P 365 185 290 250 100 283 240 150 25...

Page 16: ...ripping torque Operating diagram of microswitches Valve open Valve close Terminal number to terminal board Valve open Valve close Terminal number to terminal board Full stroke Contact open Contact clo...

Page 17: ...aft sealing 42x55x8 in the actuator centering ring GUFERO Sealing ring SN 029401 0 40 90 2 Output shaft sealing 40x62x7 in the hand wheel GUFERO Sealing ring SN 029401 0 40 90 1 Drive shaft sealing 12...

Page 18: ...ng device cover sealing Sealing ring 45x2 SN 029281 9 8918 1 Torque tripping shaft flange sealing Sealing ring 40x2 SN 029281 9 8918 2 Seal pipes for wires between the electric motor and the terminal...

Page 19: ...turn actuators MODACT MO EEx MOED EEx Explosion proof electric multi turn actuators MODACT MOA Electric multi turn actuators for nuclear power stations application outside containment MODACT MOA OC E...

Page 20: ...9 fax 420 321 785 165 420 321 785 167 e mail zpa zpa pecky cz ZPA Pe ky a s t 5 kv tna 166 289 11 PE KY Czech Republic www zpa pecky cz tel 420 321 785 141 9 fax 420 321 785 165 420 321 785 167 e mai...

Reviews: