NOTICE TO INSTALLER: Instructions must remain with installation.

FM2834

0220

Supersedes

1116

© Copyright 2020 Zoeller

®

 Co. All rights reserved.

DATE INSTALLED:

MODEL NUMBER:

PREASSEMBLED SUMP PUMP SYSTEM WITH BATTERY BACKUP

MODEL 508 - 12 V DC BATTERY BACKUP SYSTEM

WITH 115 V AC POWERED SUMP PUMP

MODEL M53 OR M98

INSTALLATION INSTRUCTIONS

SEE BELOW FOR

LIST OF WARNINGS

  1.  Make certain that the receptacle is within reach of the pump’s power supply 

cord.  Do not use primary pump circuit.  DO NOT USE AN EXTENSION CORD.  

Extension cords that are too long or too light do not deliver sufficient voltage 

to the pump motor, and they could present a safety hazard if the insulation 

were to become damaged or the connection end were to fall into a wet or 

damp area.

  2.  Make sure the pump electrical supply circuit is equipped with fuses or circuit 

breakers of proper capacity.  A separate branch circuit is recommended, 

sized according to the National Electrical Code for the current shown on the 

pump nameplate.

  3.  Testing for ground: as a safety measure, each electrical outlet should be 

checked for ground using an Underwriters Laboratory Listed circuit analyzer 

which will indicate if the power, neutral and ground wires are correctly 

connected to your outlet.  If they are not, call a qualified, licensed electrician.

  4.  For Added Safety: pumping and other equipment with a 3-prong grounded plug 

must be connected to a 3-prong grounded receptacle. For added safety the 

receptacle may be protected with a ground-fault circuit interrupter.  When 

a pump needs to be connected in a watertight junction box, the plug can be 

removed and spliced to the supply cable with proper grounding.  For added 

safety this circuit may be protected by a ground-fault circuit interrupter.  The 

complete installation must comply with the National Electrical Code and all 

applicable local codes and ordinances.

  5.  FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS POWER 

SOURCE BEFORE HANDLING.  Single phase pumps are supplied with a 3-prong 

grounded plug to help protect you against the possibility of electrical shock.  

DO NOT, UNDER ANY CIRCUMSTANCES, REMOVE THE GROUND PIN.  The 

3-prong plug must be inserted into a mating 3-prong grounded receptacle.  

If the installation does not have such a receptacle, it must be changed to the 

proper type, wired and grounded in accordance with the National Electrical 

Code and all applicable local codes and ordinances.

  6.  The tank is to be vented in accordance with local plumbing code.  Pumps 

must be installed in accordance with the National Electrical Code and all 

applicable local codes and ordinances.  Pumps are not to be 

installed in locations classified as hazardous in accordance with 

National Electrical Code, ANSI/NFPA 70.

  7.  Risk of electrical shock. Do not remove power supply cord and strain relief 

or connect conduit directly to the pump.

 8.  Installation and servicing of electrical circuits and hardware should be 

performed by a qualified, licensed electrician.

  9.  Pump installation and servicing  should be performed by a qualified person.

 10.  Risk of electrical shock. These pumps have not been investigated for use in 

swimming pools and marine areas.

 11.  Prop65 Warning for California residents: Cancer and Reproductive Harm- 

www.P65Warnings.ca.gov.

 12.  It is the owner’s responsibility to check the battery and battery connection at 

least once a month. Batteries contain acid and caution must be taken when 

handling.

  1.  Check to be sure your power source is capable of handling the voltage 

requirements of the motor, as indicated on the pump name plate.

  2.  Vent hole. It is necessary that all submersible sump, effluent, and sewage 

pumps capable of handling various sizes of solid waste be of the bottom 

intake design to reduce clogging and seal failures.  Vent holes should 

be checked periodically for clogging.  The 50 Series pumps have a vent 

located in the pump housing opposite the float, adjacent to a housing lug. 

Water stream will be visible from this hole during pump run periods.

  3.  Pump should be checked frequently for debris and/or build up which may 

interfere with the float “on” or “off” position.  Repair and service should 

be performed by an Authorized Service and Warranty Center only.

  4.  Dewatering and effluent sump pumps are not designed for use in pits 

handling raw sewage.

  5.  Maximum operating temperature must not exceed 130 °F (54 °C).

  6.  Do not operate a pump in an application where the Total Dynamic Head is 

less than the minimum Total Dynamic Head listed on the Pump Performance 

Curves.

  7.  For indoor use only.

  8.  DC emergency pumps are designed for handling clear water.  Do not use 

in septic tanks to pump effluent or sewage pits to pump sewage.

  9.  Repair and service of your DC backup system should be performed by 

an Authorized Service and Warranty Center.

 10.  The installation of DC automatic backup pumps requires the use of a variable 

level float switch for operation.  It is the responsibility of the installing party, 

to ensure that the float switch will not hang up on the pump apparatus or 

pit peculiarities

 and is secured so the pump will turn “on” and “off”.  It is 

recommended that the pit be 18" (45.7 cm) in diameter or larger to accom-

modate both a primary and a DC backup pump.

NOTE:  Pumps with the “UL” mark and pumps with the “US” mark are tested to UL Standard 
UL778.  CSA Certified pumps are certified to CSA Standard C22.2 No. 108.

REFER TO WARRANTY ON PAGE 2.

CAUTION

SEE BELOW FOR

LIST OF CAUTIONS

Product information presented 

here reflects conditions at time 

of  publication. Consult factory 

regarding discrepancies or 

inconsistencies.

MAIL TO

:  P.O. BOX 16347 • Louisville, KY  40256-0347

SHIP TO

:  3649 Cane Run Road  • Louisville, KY  40211-1961

TEL

: (502) 778-2731 • 1 (800) 928-PUMP • 

FAX

: (502) 774-3624

Visit our website:

zoellerpumps.com

Patent No. D740329

508/53

508/98

NOTICE: VENT HOLE FOR 

CHECK VALVE SEE #2 IN 

CAUTION SECTION BELOW

Register your 

Zoeller Pump Company 

Product on our website:

http://reg.zoellerpumps.com/

Summary of Contents for ProPak 508/53

Page 1: ...lation and servicing of electrical circuits and hardware should be performed by a qualified licensed electrician 9 Pump installation and servicing should be performed by a qualified person 10 Risk of electrical shock These pumps have not been investigated for use in swimming pools and marine areas 11 Prop65 Warning for California residents Cancer and Reproductive Harm www P65Warnings ca gov 12 It ...

Page 2: ...haveother rights which vary from state to state In those instances where damages are incurred as a result of an alleged pump failure the homeowner must retain possession of the pump for investigation purposes The DC emergency pump is designed as a backup to your primary sump pump during unexpected power outages or primary pump failure The DC pump electronic controls and all the parts required for ...

Page 3: ...er clearance for the level control switch es to operate properly 5 DO Always disconnect pump from power source before handling DOalwaysconnecttoaseparatelyprotectedandproperlygrounded circuit DO NOT ever cut splice or damage power cord only splice in a watertight junction box DO NOT carry or lift pump by its power cord DO NOT use an extension cord with a sump pump 6 DO install a union in the disch...

Page 4: ...CHECK VALVE SCREWS INTO PRIMARY PUMP DISCHARGE HAND TIGHTEN ONLY WEEP HOLE MUST BE VISIBLE FLOAT SWITCH DC PUMP M53 OR M98 PRIMARY PUMP TYPICAL INSTALLATION EXPLODED VIEW OF PUMP SYSTEM OUTLET PUMP PRIMARY 1 25 mm MIN IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHER THAN DC BACKUP PUMP DC PUMP INSTALLED IN LINE WITH SUBMERSIBLE PUMP BATTERY BOX DC CHARGER OUTLET CHARGER R R FIGURE 1 FIGURE 2 C...

Page 5: ...control charger to the wall If more convenient the control charger may be set on a nearby shelf or ledge The control charger should be located 3 1 m or 4 1 2 m above the sump 6 Connect the green sensor wire to the sensor connector Figure 3 7 Connect the leads from the control charger to the battery terminals White pos lead to positive terminal and black neg lead to INITIAL START UP AND OPERATION 1...

Page 6: ...e 1 005645 153766 153766 9 1 1 2 X 2 1 8 long pipe 1 150197 N A N A 10 1 1 2 X 8 3 4 long pipe sch 40 1 010619 019509 019509 CHECKLIST EXPLODED VIEW DC PUMP All installations must comply with all applicable electrical and plumbing codes including but not limited to National Electrical Code local regional and or state plumbing codes etc Not intended for use in hazardous locations SK2961 BATTERY BOX...

Page 7: ...ting a turbulent condition a mixture of air and water may cause a complete or partial air lock and reduce or stop the flow of water in the discharge pipe b Baffle the incoming stream of water to reduce turbulence Diverting water stream against wall of basin usually corrects an air lock problem 7 Water level stays high DC Pump continues to run a Battery is low b If power has been restored and water...

Page 8: ...OW BATTERY ALARM OFF ALARM CONTACTS GREEN LEAD TO FLOAT SWITCH BLACK LEAD WHITE LEAD FIGURE 4 SK2503 FIGURE 5 SK2958 LCD DISPLAY AND KEYPAD FUNCTIONS There are two buttons on the front of the charger The scroll button is used to cycle through the information on the LCD screen The alarm reset button Can be pressed to clear alarm buzzer light and or display Can be held for longer than 3 seconds to s...

Page 9: ...a residentes de California sobre la Prop65 Cancer y daños reproductivos www P65Warnings ca gov 12 Es responsabilidad del propietario comprobar la batería y la conexión de la batería al menos una vez al mes Las baterías contienen ácido y hay que tener precaución al manipularlas 1 Compruebe que la fuente de alimentación sea capaz de resistir el voltaje que exige el motor que se indica en la placa de...

Page 10: ...nes de investigación La bomba de emergencia de CC está diseñada como respaldo a su bomba de sumidero principal durante cortes de energía inesperados o fal las de la bomba principal La bomba de CC los controles electrónicos y todos los elementos necesarios para la instalación vienen incluidos excepto la batería que es suministrada por el usuario El sistema está diseñado para su instalación en pozos...

Page 11: ...de que el sumidero es lo suficientemente grande como para permitir un espacio libre apropiado para que los interruptores de nivel funcionen correctamente 5 DESCONECTE siempre la bomba de su fuente de alimentación antes de manipularla SIEMPRE conéctela a un circuito protegido y conectado a tierra por separado NUNCA CORTE empalme o dañe el cable de alimentación solo empalme en una caja de conexión e...

Page 12: ... A LA DESCARGA DE LA BOMBA PRINCIPAL APRIETE A MANO SOLAMENTE EL ORIFICIO DE DRENAJE DEBE ESTAR VISIBLE INTERRUPTOR DE FLOTADOR BOMBA DE CC BOMBA PRINCIPAL M53 O M98 INSTALACIÓN TÍPICA VISTA EN DESPIECE DEL SISTEMA DE LA BOMBA SALIDA PARA BOMBA PRINCIPAL 25 mm 1 pulg MIN IMPORTANTE EL NIVEL DE APAGADO DE LOS COMPONENTES DEL FLOTADOR DEBE ESTAR POR ENCIMA DE LA BOMBA DE RESERVA DE CC FIG 1 BOMBA DE...

Page 13: ...uptor de reinicio de la alarma para silenciar Esto indica que la conexión del cargador a la batería se realizó correctamente PRECAUCIÓN La correcta conexión de la batería es esencial para el funcionamiento del sistema Utilice las tuercas suministradas con la batería y los conectores de ojete en los cables de la batería El terminal positivo es el perno grande de 1 0 cm 3 8 pulg de diámetro El perno...

Page 14: ...lg x 2 1 8 pulg 1 150197 10 Tubo largo DN40 x 5 5 cm 1 1 2 pulg x 8 3 4 pulg sch 40 1 010619 019509 019509 LISTA DE VERIFICACIÓN VISTA EN DESPIECE BOMBA DE CC Todas las instalaciones deben cumplir con todos los códigos eléctricos y de plomería aplicables incluyendo pero no limitado a el Código Eléctrico Nacional los códigos de plomería locales regionales y o estatales etc No está diseñada para uso...

Page 15: ... a alta velocidad creando una condición turbulenta la mezcla de aire y de agua puede causar un bloqueo por aire total o parcial y reducir o detener el flujo de agua en la tubería de descarga b Desviéelflujodeentradadeaguaparareducirlaturbulencia Por logeneral desviarelflujodeaguahacialapareddelcontenedor para agua corrige el problema de bloqueo por aire 7 Elniveldeaguasemantienealto LabombadeCCsig...

Page 16: ...etrasa para reducir las falsas alarmas La luz amarilla de alarma desactivada indica que el timbre está silenciado R R CABLE DE ALIMENTACIÓN CONECTADO A TIERRA LCD ALIMENTACIÓN DE CA DESPLAZAMIENTO CARGADA BOMBA REINICIADA CARGANDO REINICIO DE LAALARMA BATERÍA BAJA ALARMA DESACTIVADA CONTACTOS DE LAALARMA CABLE VERDE AL INTERRUPTOR DE FLOTADOR CABLE NEGRO CABLE BLANCO EL PASADOR DE FIJACIÓN DEBE IN...

Page 17: ... Californie Cancer et anomalies de la reproduction www P65warnings ca gov 12 Ilestdelaresponsabilitédupropriétairedevérifierlabatterieetleraccordement de la batterie au moins une fois par mois Les batteries contiennent de l acide et il est nécessaire de prendre des précautions lors de leur manipulation 1 Assurez vous que l alimentation électrique est capable de supporter les exigences de tension d...

Page 18: ...lter d une soi disant défaillance d une pompe le propriétaire doit conserver la pompe à des fins d enquête La pompe de secours à courant continu a été conçue pour remplacer la pompe de puisard principale pendant les pannes d électricité imprévues ou les défaillances de la pompe principale La pompe à courant continu les commandes électroniques et toutes les pièces requises pour l installation sont ...

Page 19: ...ettre le bon fonctionnement de l interrupteur à flotteur 5 Toujours DÉBRANCHER la pompe de la source d alimentation avant de la manipuler Toujours la BRANCHER sur un circuit protégé séparé et qui soit correctement mis à la terre NEJAMAIScouper joindreouendommagerlecordond alimentation réaliser une jonction uniquement dans un boîtier de raccordement étanche NEPAStransporternisouleverlapompeparsonco...

Page 20: ...ÉVACUATION DE LA POMPE PRINCIPALE SERRER À LA MAIN UNIQUEMENT LE TROU D ÉVENT DOIT ÊTRE VISIBLE INTERRUPTEUR À FLOTTEUR POMPE À COURANT CONTINU POMPE PRINCIPALE M53 OU M98 INSTALLATION NORMALE VUE ÉCLATÉE DU SYSTÈME DE LA POMPE SORTIE DE LA POMPE PRINCIPALE 25 MM 1 PO MIN IMPORTANT LE NIVEAU D ARRÊT DU FLOTTEUR DOIT ÊTRE PLUS HAUT QUE LA POMPE DE SECOURS À COURANT CONTINU POMPE C C INSTALLÉE EN LI...

Page 21: ... butoir inférieur du flotteur pour éviter que des débris n empêchent le bon fonctionnement du flotteur reportez vous à la figure 2 5 Montez le chargeur de courant continu au mur Si cela est plus pratique le chargeur peut être posé sur une étagère toute proche Le chargeur doit être situé entre 0 9 et 1 2 m 3 et 4 pi au dessus du puisard 6 Raccordez le fil vert du capteur au raccordement du capteur ...

Page 22: ... 1 1 2 po x 22 2 cm 8 3 4 po 1 010619 019509 019509 LISTE DE VÉRIFICATION VUE EXPLOSÉE DE LA POMPE À COURANT CONTINU Toutes les installations doivent être conformes aux codes de la plomberie et de l électricité y compris au code national d électricité américain aux codes de la plomberie locale nationale ou de l état etc Système non conçu pour une utilisation dans des zones dangereuses SK2961 BOÎTI...

Page 23: ...n mélange d air et d eau peut causer un bouchon d air complet ou partiel et réduire ou arrêter le flux d eau dans le tuyau d évacuation b Déroutez le flux entrant d eau pour réduire l agitation Le détournement du flux d eau contre la paroi de la cuve permet normalement de régler le problème de bouchon d air 7 Le niveau d eau reste élevé La pompe à courant continu continue de fonctionner a La batte...

Page 24: ...t chargé indique une batterie entièrement chargée prête à fonctionner Le voyant jaune en charge indique le courant qui va à la batterie Le voyant rouge batterie faible clignote lorsque la tension est inférieure à 10 8 V et clignote rapidement lorsqu elle est inférieure à 8 4 V Le voyant jaune de pompe en cycle va clignoter lorsque le flotteur est activé et reste allumé après 3 secondes REMARQUE La...

Reviews: