4
© Copyright 2017 Zoeller
®
Co. All rights reserved.
Pump Wiring Instructions
FOR YOUR PROTECTION, ALWAYS DISCONNECT THE PUMP FROM ITS POWER SOURCE BEFORE HANDLING.
All electrical connections must be wired and grounded in accordance with the National Electrical Code and all applicable
local codes and ordinances.
“Risk of electrical shock”
Do not remove the power supply cord and strain relief or connect conduit directly to pump.
Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician.
FIGURE 3A. Models E810
and E815 Wiring Diagram
002397
254 mm (10") MAX.
127 mm (5") MIN.
FIGURE 2. Pump Control Switch Installation
Use the diagram above to secure the float switch properly and obtain the proper tether to customize the on-off cycle to each application. Note the
minimum off level shown above. On Prepackaged Systems, the tether length is set at 5”.
Note:
Failure to keep within proper tether
limits may prevent reliable switch operation.
Note:
Cable must be mounted in horizontal
position.
Determining Pumping Range
in Inches (1 inch - 2.5 cm)
Use only as a guide. Due to weight
of cable, pumping range above
horizontal is not equal to pumping
range below horizontal. Ranges are
based on testing in nonturbulent
conditions. Range may vary due to
water temperature and cord shape. As
tether length increases, so does the
variance of the pumping range.
Tether Length (inches)
5 10
Pumping Range (GPM)
9 13.5
min.
max.
SK305D
SK2651
ALARM FLOAT
PUMP CONTROL
FLOAT TREE
FLOAT
406 mm (16")
MIN. OFF
Electrical Data
Amps
KVA
Code
Winding
Resistance
Line-to-Line
Model
BHP
RPM
Voltage
Phase
Hertz
Full Load
Shut Off
Locked
Rotor
E810
1
1750
230
1
60
7.0
7.0
24.5
G
2.3 / 2.0*
E815
2
1750
230
1
60
10.5
10.5
44.0
B
1.80 / 1.60*
RE810
1
1750
230
1
60
7.0
7.0
24.5
G
**
RE815
2
1750
230
1
60
10.5
10.5
44.0
B
**
* Line to line reading from the electrical load will only reflect the run winding resistance. Start winding resistance can only be measured after
removing the cover.
** Start & run winding resistance can only be measured after removing the cover and checking at the through wall terminals.
152554
RUN
O.L.
MOTOR
(3)
BLUE
RED
WHITE
BLACK
GREEN
L1
L2
START
(1)
(2)
YELLOW
BLUE
RED
CAPACITOR
(WHITE)
(BLACK)
(BROWN)
FIGURE 3B. Models RE810
and RE815 Wiring Diagram
(932 Replacement Grinder
Assembly w/ Manual Run)
RUN
O.L.
MOTOR
(3)
BLUE
RED
GREEN
START
(1)
(2)
YELLOW
BLUE
RED
CAPACITOR
(WHITE)
(BLACK)
WHITE
BLACK
RED
YELLOW
BLUE
ORANGE
R
RELAY
4
6
0
1
R
2
6
4
5
GE RELAY
(BROWN)
1)
NOTES:
INSULATORS REQUIRED ON GE RELAY TERMINALS 2 & 5;
OMRON RELAY TERMINALS 1 & 4.