Pump Wiring Instructions

PHASE POWER AND SENSOR CORD, LEAD IDENTIFICATION

ZEPA0039E

SEAL FAILURE

BLACK & WHITE 

LEAD  

GROUND

POWER 

CORD 

LEAD

SENSOR CORD 

GREEN GROUND 

BLACK

GREEN  

RED 

WHITE

SENSOR

LEADS

TEMPERATURE

RED & ORANGE

SENSOR

LEADS

“62 HD SERIES” FOUR CONDUCTOR AWG. POWER CORD SIZE

MODEL

BHP

230/1PH

200/3PH

230/3PH

460/3PH

575/3PH

6220

5

8 AWG.

12 AWG.

12 AWG.

12 AWG.

12 AWG.

6221

7 1/2

8 AWG.

8 AWG.

8 AWG.

12 AWG.

12 AWG.

6222

10

N/A

8 AWG.

8 AWG.

12 AWG.

12 AWG.

6223

15

N/A

4 AWG.

4 AWG.

8 AWG.

12 AWG.

6224

20

N/A

4 AWG.

4 AWG.

8 AWG.

8 AWG.

APPROXIMATE CORD DIAMETER PER GAUGE

12/4 AWG.

0.64"

8/4 AWG.

0.93"

4/4 AWG.

1.35"

 NOTE: SENSOR CORD 18/5 AWG. APPROXIMATELY 0.44" DIAMETER.

 Installation and checking of electrical circuits and hardware should be performed by a qualified licensed electrician.
 “Risk of electrical shock”  Do not remove power supply cord and strain relief or connect conduit directly to the pump.

CAUTION

 Power cords, sensor cords, and float cords all must be sealed to prevent gases from the basin entering the control panel.

INSTRUCTIONS FOR CHECKING ROTATION OF THREE PHASE UNITS

It is very important that these units be connected for proper rotation.  Since no rotating parts are visible without removing the pump from the pit, 

the rotation on 3 phase units should be checked before installation into the pit as follows:
After the proper electrical connections are made, momentarily energize the pump observing the direction of kick back due to starting torque. The rotation is 

correct if the kick back is in the opposite direction of the rotation arrow. If the rotation is not correct, disconnect power and switch any two power leads. Turn 

power back on and retest for proper rotation.

THERMAL SENSOR PROTECTION

Two thermal sensors and leads are wired in series with each other and located adjacent to the motor windings. When the temperature exceeds the maximum 

recommended limit, the pump will deactivate when the lead wires are connected to the magnetic starter circuit of a control panel with the thermal cutout feature. 

Continual deactivation of this circuit requires attention from maintenance personnel.

MOISTURE SENSORS

(1)  Pumps with moisture sensors have a separate sensor cord in addition to the power cord.

(2)  Sensor cord conductors are connected to sensors probes in the lower seal cavity. The conductor wires are terminated in the control panel for activating 

an indicator light when moisture is present in the lower seal cavity.

(3)  When the moisture indicator light is activated, the lower seal has allowed leakage of water into the lower oil-filled seal cavity. The pump should be serviced 

within 30 days to avoid damage to the motor and bearings.

(4)   Oil in the motor housing and lower seal cavity must be checked when pump is serviced. If oil from the motor housing contains water or other contamination, 

both seals should be replaced during maintenance. Always replace with new factory recommended oil and service parts. All warranty repairs must be 

made by Zoeller Authorized Service Stations.

(5)   On existing applications where the control panel only has one moisture sensor hookup per pump, one moisture sensor lead from the pump should be 

hooked to the moisture sensor lead in the panel, the other moisture sensor lead from the pump should be hooked to ground to complete the circuit.

(6)  Moisture sensor circuit can be checked for continuity (complete circuit) with a (Volt-OHM-Meter).  Set the VOM to read resistance and connect the VOM 

leads to the sensor cord black and white wires.  The VOM should read approximately 330k Ohms.  Resistance readings significantly lower indicate a seal 

leak with water in the seal chamber.  If VOM reading is open then a problem exists with moisture sensor circuit.

 

Check resistance between the green ground conductor of the pump power cord and the sensor cord black and white wires.  This resistance reading should 

indicate an open circuit.  If VOM reading returns a reading other than open, then a problem exists with the sensor circuit wiring or cordage.  If resistance 

readings show a problem with either test, then pump should be repaired by a Zoeller Authorized Service Station. 

CONTROL PANELS

These pumps are nonautomatic. They require a control panel. A motor starter circuit, control circuit, and alarm circuit within the panel are standard features. Out-

door enclosures and alternating relays are often required. Variable level float switches are the most common level sensing device. The following should be noted.
(1)  Single phase units have externally mounted capacitors and starting relays. Your control panel should have provisions for mounting these starting 

 components.

(2)  A pump incorporating the seal failure sensor and thermal sensor protection require that interfacing terminals and functions be incorporated into the panel.

(3)  All pumps require overload protection in panel. Use with approved motor control that matches motor input in full load amperes with overload element(s) 

selected or adjusted in accordance with control instructions.

(4)  Hazardous Location pumps require panels that offer intrinsically safe relays and all other NEC requirements must be followed (See Article 500,501 & 502 

plus any others that apply.)

Summary of Contents for 62 HD Series

Page 1: ...y during installation Reference ZM2354 for repair manual on 62HDSeriesPumps Shouldfurtherassistancebenecessaryplease call our Technical Support Department at 1 800 928 PUMP 7867 Table of Contents Safety Instructions 1 Limited Warranty 2 Preinstallation Information 3 Electrical Data 3 Typical Dewatering Installation 4 Typical Sewage Installation 4 Pump Wiring Instructions 5 6 Operation 7 Maintenanc...

Page 2: ...and you may also have other rights which vary from state to state Zoeller Engineered Products neither assumes nor authorizes any person or company to assume for it any other obligation in connection with the sale of its equipment Any enlargement or modification of this warranty by any other party is their sole responsibility No other warranties expressed or implied including implied warranties of ...

Page 3: ...st be drilled in the discharge pipe below the check valve and pit cover to purge the unit of trapped air Water stream will be visible from this hole during pump run periods This vent hole should be checkedperiodicallyforcloggingandcleanedasnecessary Trappedairiscaused by agitation and or a dry basin 4 Water hammer creates momentary high pressure surges These surges can cause severe damage to check...

Page 4: ...st be below the basin cover and cleaned periodically Water stream will be visible from this hole during pump run periods Also a vent hole is drilled in the pump housing Be sure that this hole is cleared during any servicing 7 Vent gases and odors to the atmosphere through vent pipe per Local and State codes 8 Secure power cord to avoid entanglement with variable level float switch mechanism 9 Do n...

Page 5: ...ture indicator light is activated the lower seal has allowed leakage of water into the lower oil filled seal cavity The pump should be serviced within 30 days to avoid damage to the motor and bearings 4 Oil in the motor housing and lower seal cavity must be checked when pump is serviced If oil from the motor housing contains water or other contamination both seals should be replaced during mainten...

Page 6: ...t be specified at time of initial pump order and are not available for field installation Sensor wire colors are as shown TYPICAL 3 PHASE WIRING DIAGRAM Refer to Sensor and Control Panel sections on page 5 ZEPA0036 ZEPA0038E Single Phase Installation All single phase models require start capacitor run capacitor and relay in the circuit to start and operate properly These components can be purchase...

Page 7: ...han six months the following is recommended Pumps If pit is to remain dry then the pump can remain in the pit With the pump in the pit it should be operated for five minutes once every three months If the pit is to remain wet the pump should be removed and stored as noted above Panels The panel should have all openings sealed to prevent moisture and dust from entering the enclosure Prior to restar...

Page 8: ...verheats and trips overload or blows fuse Incorrect Voltage Unbalanced power source Incorrect motor rotation Negative or low head Excessive water temperature Impeller or seal mechanically bound Capacitor or relay Motor shorted Lost one line in a Three Phase unit C Pumps starts and stops too often Check valve stuck open Level controls out of adjustment Temperature sensor tripping Thermal overload s...

Reviews: