rECoMMEndEd MiniMuM WirE SiZE For SHP PuMPS*
distance from Sub-Panel
0-50 Feet
50-100 Feet
100-150 Feet
150-200 Feet
Pump Model
Branch Fuse aMPs
Class: CC, g, H, J, K,
rK, or t
Voltage
Voltage
Voltage
Voltage
230VaC
115VaC
208-230 VaC 115 VaC 208-230 VaC 115 VaC 208-230 VaC 115 VaC 208-230 VaC 115 VaC
SHPF .50HP/SHPM .75HP
15A
15A
14
12
12
8
10
6
8
6
SHPF .75HP/SHPM 1.0HP
15A
15A
14
12
12
8
10
6
8
6
SHPF 1.0HP/SHPM 1.5HP
15A
20A
12
10
10
8
8
6
6
4
SHPF 1.0-3PH
15A
N/A
14
N/A
12
N/A
10
N/A
8
N/A
SHPF 1.5HP/SHPM 2.0HP
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 1.5-3PH
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 2.0HP/SHPM 2.5HP
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
SHPF 2.0-3PH
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 3.0HP
20A
N/A
10
N/A
8
N/A
6
N/A
4
N/A
SHPF 3.0-3PH
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
SHPF 5.0
25A
N/A
10
N/A
8
N/A
6
N/A
6
N/A
SHPF 1.0HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 1.5HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPF 2.0HP-2-SPD (1)
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
SHPM 1.5HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPM 2.0HP-2-SPD (1)
15A
N/A
12
N/A
10
N/A
8
N/A
6
N/A
SHPM 2.5HP-2-SPD (1)
15A
N/A
12
N/A
8
N/A
6
N/A
6
N/A
*Assumes three (3) copper conductors in a buried conduit and 3% maximum voltage loss in branch circuit. All National Electrical Code (NEC) and local codes must
be followed. Table shows minimum wire size and branch fuse recommendations for a typical installation per NEC.
(1) Two-speed pumps are not rated for use with 208 VAC.
table 2.
recommended Minimum Wire Size
2.
Wire size must be adequate to minimize voltage
drop during the start-up and operation of the
pump. See Table 2 for recommended wire sizes.
3.
Insulate all connections carefully to prevent
grounding or short-circuits. Sharp edges on
terminals require extra protection. To prevent wire
nuts from loosening, tape them using a suitable,
listed (UL, ETL, CSA) electrical insulating tape.
For safety, and to prevent entry of contaminants,
reinstall all conduit and terminal box covers.
Do
not force connections into the conduit box.
4.
To configure the internal wiring of the pump
motor for the correct voltage, refer to the diagram
on the motor data plate.
3.3 Pressure testing
All model SHP pumps come with an additional
disposable o-ring for pressure testing. This is the blue
pressure test o-ring. See Figures 2 and 3.
Caution
Do not open the pump lid before pressure testing,
because the blue pressure test o-ring may fall out. If
this happens, you will need to replace it.
If you have not opened the pump lid, skip to
Section
3.3.2, Conduct Pressure Test.
Warning
To avoid the risk of property damage, severe personal
injury, and/or death, always disconnect the power
source before working on a motor or its connected load.
Warning
To avoid the risk of property damage, severe personal
injury, and/or death, make sure that the control switch
or time clock is installed in an accessible location so
that in the event of an equipment failure or a loose
plumbing fitting the equipment can be turned off. This
location must
not
be in the same area as the pool
pump, filter, and other equipment.
Warning
The pump must be permanently connected to a
dedicated electrical circuit. No other equipment, lights,
appliances or outlets may be connected to the pump
circuit, with the exception of devices that may be
required to operate simultaneously with the pump,
such as a chlorinating device or heater.
3.2.3 Electrical Wiring
1.
The pump motor must be securely and
adequately grounded using the green screw
provided. Ground before attempting to connect
to an electrical power supply.
Do not ground to a
gas supply line.
Page 10
ENGLISH
Jandy
®
Pro Series Stealth
™
Pumps
|
Operation Manual