4
Figure 2
Figure 3
5. STARTING-UP
Technical characteristics:
Model
L-shaped heating electrical resistor power at nominal voltage
Weight
REL 3
3 kW*
4 Kg
REL
6
6 kW*
4 Kg
REL
9
9 kW*
5 Kg
REL
12
12 kW*
5 Kg
* with a manufacturer tolerance of ± 5 %
•
appliance protection index:
IP 45
.
5.1 Operating conditions
The temperature of the water circulating in the exchanger must be between 2°C and 40°C.
Before switching the device on, you need to make sure:
• the hydraulic fittings are correctly tightened,
• there is no leak,
• the appliance is correctly fixed to the wall,
• the connections of the electric cables are correctly tightened,
Incorrectly tightened cables may cause overheating of terminals,
• the appliance is correctly connected to the Earth,
• the water contained in the appliance is not frozen,
In this case, it is interdict to put the heater under operation.
5.2 Starting-up
•
switch on the filtration pump,
•
check the degassing and water circulation in the heater,
•
engage the protective 30 mA differential circuit breaker associated with the heater (or the fused
isolating switch with upstream a 30 mA differential circuit breaker),
•
set the switch to the “on” position,
•
adjust the control thermostat to the desired temperature.
Marks * to 6: * = 16°C ; 1 = 20°C ; 2 = 24°C ; 3 = 28°C ; 4 = 32°C ; 5 = 36°C ; 6 = 40°C
Note
: the indicator of heating of orange color indicates that the device is heating the basin.
5.3 Checking
Make sure that the heater stops when:
•
decreasing the required temperature on the control display (notice: when the temperature of the
water is below 16°C, the heater will always be operating, although it is set to “*”),
•
filtration is switched off,
Single-phase power supply connection
Filtration
electric box
Three-phase power supply connection
Heater terminal
strip
Protection with 30 mA differential
circuit breaker at line head
Phase Neutral
Earth
For the power cabl’s cross section,
see table
Single-phase power supply: 230Vac (S terminal) + Neutral (C
terminal) + Earth
Three-phase power supply: 400Vac (R-S-T terminals) + Neutral (N
terminal) + Earth
Heater terminal
strip
Protection with 30 mA differential
circuit breaker at line head
Phases Neutral
Earth
For the power cabl’s cross section,
see table
Filtration
electric box
clamps