background image

Page 7

ENGLISH

  

 

 

Jandy

® 

Pro Series JE Heat Pumps   

|

   Installation and Operation Manual

Figure 1.  Jandy pro series JE Heat pumps dimensions

 3.5" 

 8" 

 B 

 A 

 C 

 F 

 E 

 D 

MODEL SIZE

DIMENSIONS

A

B

C

D

E

F

JE1500T

33”

34”

12.5”

9”

7”

39”

JE2000/2500T

36”

40”

13.8”

19”

15”

43”

JE3000T

36”

44”

13.8”

19”

15”

43”

heat pump is separated from the pool or spa by a 5 foot (1.5 

meters) high solid fence or other permanent barrier.

In Canadian installations, the minimum distance to be 

maintained from the inside wall of the pool or spa is 3 

meters (approx. 10 feet). 

Equipment pad

Place the heat pump on a flat slightly pitched surface, 

such as a concrete or fabricated slab (pad). This allows 

proper drainage of condensation and rain water from the 

base of the unit. If possible, the pad should be placed at 

the same level or slightly higher than the filter system 

equipment pad. 

notE

  Ensure that the pad is pitched not more than ¼ 

inch per foot cm per toward the compressor end 
(front) of the heat pump. Pitch slab from back to 
front ¼ inch per foot maximum and level from 
side to side.

Condensation and drainage

Condensation will occur from the evaporator coil while 

the unit is running and drain at a steady rate, usually 

3 to 5 gallons (11.4 to 18.9 liters) per hour, depending 

upon ambient air temperature and humidity. The more 

humid the ambient conditions, the more condensation 

will be produced. Keep the drain holes of the base of the 

unit clear of debris.
If the heat pump is installed indoors*, means of 

condensate disposal must be provided
* Indoor installation requires factory consultation

lawn sprinklers

Keep lawn sprinkler heads from spraying on the heat 

pump to prevent corrosion and damage. Use a deflector 

Side of 
Heat 
pump

Minimum Clearances for 

Operation

Recommended Clearances 

for Serviceability

Inches

Centimeters

Inches

Centimeters

Front

24

60

36

90

Rear

12

30

24

60

Left

12

30

24

60

Right

12

30

24

60

Top

60

150

60

150

notE:

 Clearances listed in Table 2 are manufacturer’s tested values. 

These are given as minimum values. Where local and national codes 
apply, and values are different than those listed in Table 2, use the 
greater value to ensure safe and proper operation.

table 2.  Heat pump Clearances

if needed.

roof run-off

Make sure the heat pump is not located where large 

amounts of water may run-off from a roof into the unit. 

Sharp sloping roofs without gutters will allow massive 

amounts of rain water, mixed with debris from the roof 

to be forced through the unit. A gutter or down spout 

may be needed to protect the heat pump.

installation of anchor Clamps

In Florida, building codes require that the heat pump be 

anchored to the equipment pad or platform to withstand 

high wind pressures created during hurricanes. Other 

jurisdictions may have similar requirements. Please 

check your local codes for further details. 
This heat pump is provided with anchor clamps 

designed to hold the unit to the equipment pad in high 

wind conditions. Installation of the anchor clamps is 

recommended in all installations and are required in 

Florida (reference Florida Building Code, Mechanical 

Section 301.13).

Summary of Contents for Jandy Pro Series JE1500T

Page 1: ...on of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintena...

Page 2: ......

Page 3: ...Spa Connection 3 Wire Connection 16 Figure 11b AquaLink RS or Remote TSTAT Connection 2 Wire Connection 16 Figure 12 AquaLink RS to JE Heat Pump 17 Figure 13 JE Heat Pump Connection to Power Center 1...

Page 4: ...Page 2 ENGLISH Jandy Pro Series JE Heat Pumps Installation and Operation Manual...

Page 5: ...rovides installation and operation instructions for the Jandy Pro Series JE models of heat pumps Read these installation and operation instructions completely before proceeding with the installation C...

Page 6: ...here possible shelter the pool from prevailing winds with well trimmed hedges or other landscaping cabanas or fencing 7 The use of an automatic pool cover if installed provides a valuable safety featu...

Page 7: ...installation is required to assure safe operation The requirements for Zodiac heat pumps include the following 1 Field assembly if required 2 Appropriate site location and clearances 3 Sufficient air...

Page 8: ...ing Scroll Scroll Scroll CABINET ABS REFRIGERANT 64 Oz R410A 78 Oz R410A 78 Oz R410A 78 Oz R410A 118 Oz R410A 126 Oz R410A 118 Oz R410A 126 Oz R410A REFRIGERANT HIGH PRESSURE ALARM 600 PSI reset to 46...

Page 9: ...ed indoors means of condensate disposal must be provided Indoor installation requires factory consultation Lawn Sprinklers Keep lawn sprinkler heads from spraying on the heat pump to prevent corrosion...

Page 10: ...ater connections are no more than 10 feet below the pool water surface or no more than 5 feet above it See instructions for pressure switch adjustment Section 5 6 in the heat pump start up section of...

Page 11: ...ng on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to adjust water...

Page 12: ...the front cover of the junction box 4 Electrical supply lines must be run through watertight conduit Route the wires and conduit through the knock out designated for high voltage on the right side of...

Page 13: ...CAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP POOL HEATER VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FROM...

Page 14: ...and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass Valv...

Page 15: ...BK BL BK BK BR W BL Y Y BL W BR HIGH REFRIGERANT PRESS SWITCH LOW REFRIGERANT PRESS SWITCH WATER TEMP DEFROST TEMP BK R R L1 L2 Y Y Y Y BK W R R FAN MOTOR BR BR W BK W W W W W R R GROUND GR GR R REVE...

Page 16: ...GR Y GROUND POWER BOARD COMPRESSOR FAN MOTOR WATER PRESSURE SWITCH USER INTERFACE REVERSING VALVE OPTIONAL HIGH REFRIGERANT PRESSURE SWITCH LOW REFRIGERANT PRESSURE SWITCH CONTACTOR W W W W W L1 L2 L3...

Page 17: ...a Remote Pool Off Spa Selector 3 Wire Connection Install the Remote Pool Off Spa Selector 1 Turn off the power to both the pool spa control system and the heat pump unit 2 Remove the screws that attac...

Page 18: ...Setup mode press and hold the MENU POOL and SPA buttons for 5 seconds NOTE The display will revert back to OFF after one minute since the last key press 3 Press the Up or Down button to display REMOTE...

Page 19: ...trol connected to the heat pump the display on the heat pump will show JANDY REMOTE ONLINE PUSH MENU TO DISABLE When the JE heat pump is online with the RS control all functionality of the control on...

Page 20: ...re control When that happens the heat pump will automatically shut off but the filter pump will keep running 5 2 Operating the Controller Your new Jandy Pro Series JE heat pump is controlled by an adv...

Page 21: ...LL will not be displayed if the unit is not provided with chiller You can change the temperature set point by pressing the Up or Down button Repeatedly press the Up or Down button until you reach the...

Page 22: ...de 2 To enter the User Setup mode press and hold the MENU button for 5 seconds 3 To select spa timer use the Up or Down button to scroll through to display SELECT USER SETUP SPA TIMER Press the MENU b...

Page 23: ...mum requirement of 30 gpm 114 lpm after the direction fitting or elbow has been installed Make sure the pool filter is clean before making any pressure switch adjustment A dirty filter will restrict t...

Page 24: ...em which has been under water Zodiac recommends that you inspect your heat pump on a regular basis and especially after abnormal weather conditions The following basic guidelines are suggest ed for yo...

Page 25: ...t gas enters the heat exchanger where the water extracts the heat The pump pulls in cool pool water which in turn converts the hot gas back into a liquid refrigerant and starts the cycle over again Th...

Page 26: ...run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers are clean Check water level in pool Tempora...

Page 27: ...sure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re closes...

Page 28: ...pansion Valve 1500 R0575000 15 Thermal Expansion Valve 2000 2500 R0575100 15 Thermal Expansion Valve 3000 R0575200 16 Air Temperature Sensor All R0575300 17 High Pressure Switch All R0575400 18 Low Pr...

Page 29: ...mps Installation and Operation Manual 9 3 Zodiac JE 1500 Heat Pumps Exploded View C 1 2 3 4 5 6 7 8 9 10 11 12 20 21 DETAIL C SCALE 1 8 13 14 15 16 17 18 19 33 See Figure 19 for detail Figure 16 Zodia...

Page 30: ...allation and Operation Manual 9 4 Zodiac JE 2000 JE2500 JE3000 Heat Pumps Exploded View C 1 2 3 4 5 6 7 9 8 10 12 20 11 21 23 DETAIL C SCALE 1 8 15 14 13 17 18 22 19 33 See Figure 20 for detail Figure...

Page 31: ...ation and Operation Manual 9 5 Zodiac JE Single Phase Electric Box 9 6 Zodiac JE Three Phase Electric Box Figure 18 Zodiac JE Single Phase Electric Box Figure 19 Zodiac JE Three Phase Electric Box 24...

Page 32: ...acPoolSystems com Zodiac Pool Systems Canada Inc 2115 South Service Road West Unit 3 Oakville ON L6L 5W2 1 888 647 4004 www ZodiacPoolSystems ca ZODIAC is a registered trademark of Zodiac Internationa...

Reviews: