background image

Page 4

ENGLISH

  

 

 

Jandy

® 

Pro Series JE Heat Pumps   

|

   Installation and Operation Manual

 WarninG

Prolonged immersion in hot water can induce 
hyperthermia.

 WarninG

Hyperthermia occurs when the internal body 
temperature reaches a level several degrees above 
the normal body temperature of 98.6°F (37°C). 
Symptoms include dizziness, fainting, drowsiness, 
lethargy, and an increase in the internal body 
temperature. The effects of  hyperthermia include:
• 

Lack of awareness of impending hazard

• 

Failure to perceive heat

•  

Failure to recognize need to leave spa

•  

Physical inability to leave spa

•  

Fetal damage in pregnant women

•  

Unconsciousness resulting in a danger of

 

drowning

swimming pool Energy saving tips

It is important to note that a heat pump will not heat 

a pool as fast as a large gas or electric pool heater. If 

the pool water is allowed to cool significantly, it may 

take several days to return to the desired swimming 

temperature. For weekend use, it is 

more economical

 

to maintain the pool water temperature at or near your 

desired swimming temperature. If you do 

not

 plan to 

use your pool for a prolonged period, then you might 

choose to turn the heat pump completely off 

or

 decrease 

the temperature setting of the control several degrees to 

minimize energy consumption. 

Zodiac offers the following recommendations to help 

conserve energy and minimize the cost of operating 

your heat pump without sacrificing comfort.

1. 

The American Red Cross recommends a maximum 

water temperature of 78°F (25°C). Use an accurate 

pool thermometer. A difference of 4°F (2°C), 

between 78°F and 82°F (26°C and 28°C), will 

significantly increase energy consumption.

2. 

Carefully monitor the water temperature of your 

pool in the summertime. You can reduce heat 

pump usage due to warmer air temperatures.

3. 

During the winter or when on vacation for longer 

than a week, turn off the heat pump.

4. 

Find the proper setting on the heat pump 

temperature control and use the Set Point Lockout 

or lock the cover on the heat pump controller to 

discourage further adjustments.

5. 

Set the pump time clock to start the pump no 

earlier than 6:00 AM during the pool heating 

season. This is the time when nightly heat loss 

balances.

6. 

Where possible, shelter the pool from prevailing 

winds with well-trimmed hedges or other 

landscaping, cabanas, or fencing.

7. 

The use of an automatic pool cover, if installed, 

provides a valuable safety feature, reduces heat 

loss, conserves chemicals, and reduces the load on 

filtration systems..

8. 

The use of a solar blanket can reduce the heat loss 

caused by evaporation on the surface area of the 

pool.

1.3 

Warranty

The Jandy Pro Series JE heat pump is sold with a 

limited factory warranty.

Make all warranty claims to your Zodiac

®

 dealer or 

directly to Zodiac. Claims must include the heat pump 

serial number and model (this information can be found 

on the rating plate), installation date, and name of the 

installer. Shipping costs are not included in the warranty 

coverage.

The warranty does not cover damage caused by 

improper assembly, installation, operation, winterizing, 

field modification, or failure to earth bond and 

properly ground the unit. Any changes to the heat 

pump, evaporator, heat exchanger, wiring, or improper 

installation may void the warranty.

1.4 

Codes and standards

The Jandy Pro Series JE heat pump is listed by ETL

®

 as 

complying with the latest edition of the “UL Standard 

for Safety for Heating and Cooling Equipment”, UL 

1995 and CSA C22.2 No. 236.

All Zodiac heat pumps must be installed in accordance 

with the local building and installation codes as per the 

utility or authority having jurisdiction. All local codes 

take precedence over national codes. In the absence of 

local codes, refer to the latest edition of the National 

Electrical Code

®

 (NEC

®

) in the United States and 

the Canadian Electrical Code (CEC

®

) in Canada for 

installation.

1.5 

technical assistance

Consult the Zodiac technical support department or 

your local Zodiac dealer with any questions or problems 

involving your Zodiac equipment. An experienced 

technical support staff is ready to assist you in assuring 

the proper performance and application of Zodiac 

products. For technical support call the Zodiac technical 

support department at (800) 822-7933.

1.6 

Materials needed For installation

The following items are needed and are to be supplied 
by the installer for 

all

 heat pump installations:

1. 

Plumbing connections (2”).

2. 

Level surface for proper drainage. (See equipment 

pad for pitch requirements)

3. 

Suitable electrical supply line. See rating plate on 

unit for electrical specifications. A junction box is 

Summary of Contents for Jandy Pro Series JE1500T

Page 1: ...on of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintena...

Page 2: ......

Page 3: ...Spa Connection 3 Wire Connection 16 Figure 11b AquaLink RS or Remote TSTAT Connection 2 Wire Connection 16 Figure 12 AquaLink RS to JE Heat Pump 17 Figure 13 JE Heat Pump Connection to Power Center 1...

Page 4: ...Page 2 ENGLISH Jandy Pro Series JE Heat Pumps Installation and Operation Manual...

Page 5: ...rovides installation and operation instructions for the Jandy Pro Series JE models of heat pumps Read these installation and operation instructions completely before proceeding with the installation C...

Page 6: ...here possible shelter the pool from prevailing winds with well trimmed hedges or other landscaping cabanas or fencing 7 The use of an automatic pool cover if installed provides a valuable safety featu...

Page 7: ...installation is required to assure safe operation The requirements for Zodiac heat pumps include the following 1 Field assembly if required 2 Appropriate site location and clearances 3 Sufficient air...

Page 8: ...ing Scroll Scroll Scroll CABINET ABS REFRIGERANT 64 Oz R410A 78 Oz R410A 78 Oz R410A 78 Oz R410A 118 Oz R410A 126 Oz R410A 118 Oz R410A 126 Oz R410A REFRIGERANT HIGH PRESSURE ALARM 600 PSI reset to 46...

Page 9: ...ed indoors means of condensate disposal must be provided Indoor installation requires factory consultation Lawn Sprinklers Keep lawn sprinkler heads from spraying on the heat pump to prevent corrosion...

Page 10: ...ater connections are no more than 10 feet below the pool water surface or no more than 5 feet above it See instructions for pressure switch adjustment Section 5 6 in the heat pump start up section of...

Page 11: ...ng on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to adjust water...

Page 12: ...the front cover of the junction box 4 Electrical supply lines must be run through watertight conduit Route the wires and conduit through the knock out designated for high voltage on the right side of...

Page 13: ...CAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP POOL HEATER VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FROM...

Page 14: ...and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass Valv...

Page 15: ...BK BL BK BK BR W BL Y Y BL W BR HIGH REFRIGERANT PRESS SWITCH LOW REFRIGERANT PRESS SWITCH WATER TEMP DEFROST TEMP BK R R L1 L2 Y Y Y Y BK W R R FAN MOTOR BR BR W BK W W W W W R R GROUND GR GR R REVE...

Page 16: ...GR Y GROUND POWER BOARD COMPRESSOR FAN MOTOR WATER PRESSURE SWITCH USER INTERFACE REVERSING VALVE OPTIONAL HIGH REFRIGERANT PRESSURE SWITCH LOW REFRIGERANT PRESSURE SWITCH CONTACTOR W W W W W L1 L2 L3...

Page 17: ...a Remote Pool Off Spa Selector 3 Wire Connection Install the Remote Pool Off Spa Selector 1 Turn off the power to both the pool spa control system and the heat pump unit 2 Remove the screws that attac...

Page 18: ...Setup mode press and hold the MENU POOL and SPA buttons for 5 seconds NOTE The display will revert back to OFF after one minute since the last key press 3 Press the Up or Down button to display REMOTE...

Page 19: ...trol connected to the heat pump the display on the heat pump will show JANDY REMOTE ONLINE PUSH MENU TO DISABLE When the JE heat pump is online with the RS control all functionality of the control on...

Page 20: ...re control When that happens the heat pump will automatically shut off but the filter pump will keep running 5 2 Operating the Controller Your new Jandy Pro Series JE heat pump is controlled by an adv...

Page 21: ...LL will not be displayed if the unit is not provided with chiller You can change the temperature set point by pressing the Up or Down button Repeatedly press the Up or Down button until you reach the...

Page 22: ...de 2 To enter the User Setup mode press and hold the MENU button for 5 seconds 3 To select spa timer use the Up or Down button to scroll through to display SELECT USER SETUP SPA TIMER Press the MENU b...

Page 23: ...mum requirement of 30 gpm 114 lpm after the direction fitting or elbow has been installed Make sure the pool filter is clean before making any pressure switch adjustment A dirty filter will restrict t...

Page 24: ...em which has been under water Zodiac recommends that you inspect your heat pump on a regular basis and especially after abnormal weather conditions The following basic guidelines are suggest ed for yo...

Page 25: ...t gas enters the heat exchanger where the water extracts the heat The pump pulls in cool pool water which in turn converts the hot gas back into a liquid refrigerant and starts the cycle over again Th...

Page 26: ...run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers are clean Check water level in pool Tempora...

Page 27: ...sure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re closes...

Page 28: ...pansion Valve 1500 R0575000 15 Thermal Expansion Valve 2000 2500 R0575100 15 Thermal Expansion Valve 3000 R0575200 16 Air Temperature Sensor All R0575300 17 High Pressure Switch All R0575400 18 Low Pr...

Page 29: ...mps Installation and Operation Manual 9 3 Zodiac JE 1500 Heat Pumps Exploded View C 1 2 3 4 5 6 7 8 9 10 11 12 20 21 DETAIL C SCALE 1 8 13 14 15 16 17 18 19 33 See Figure 19 for detail Figure 16 Zodia...

Page 30: ...allation and Operation Manual 9 4 Zodiac JE 2000 JE2500 JE3000 Heat Pumps Exploded View C 1 2 3 4 5 6 7 9 8 10 12 20 11 21 23 DETAIL C SCALE 1 8 15 14 13 17 18 22 19 33 See Figure 20 for detail Figure...

Page 31: ...ation and Operation Manual 9 5 Zodiac JE Single Phase Electric Box 9 6 Zodiac JE Three Phase Electric Box Figure 18 Zodiac JE Single Phase Electric Box Figure 19 Zodiac JE Three Phase Electric Box 24...

Page 32: ...acPoolSystems com Zodiac Pool Systems Canada Inc 2115 South Service Road West Unit 3 Oakville ON L6L 5W2 1 888 647 4004 www ZodiacPoolSystems ca ZODIAC is a registered trademark of Zodiac Internationa...

Reviews: