section 8. troubleshooting

8.1 

troubleshooting Guide

The following table provides symptoms and solutions for general troubleshouting problems for the heat pump.

table 4.  Heat pump troubleshouting Guide

sYMptoM

CorrECtiVE aCtion

Heat pump will not start, no control board display.

Breaker or fuse may be tripped. Reset breaker or check fuse. If 
heat pump still does not run, call for service.

three-phase models only

 - The phases may be 

reversed or there may be a loss of phase, call for service.

Heat pump will not start, control board display working.

Heat pump may be in delay count down of 5 minutes. Make 
sure control board thermostat is calling for heater to come on 
(check setting on thermostat and temperature reading). Make 
sure heat pump is not in cooling mode.

Heat pump runs but does not heat.

Verify cold air is blowing out the top of the heat pump. If the 
heat pump has just been installed or if the pool water has been 
allowed to cool significantly, it is necessary to run the heat 
pump continually for 24-48 hours. If the heat pump has been in 
operation for some time, increase the circulating pump time, or 
switch the control board to Maintain Heat function. If heating a 
spa, verify no air intake stand pipes are open. If heat pump still 
does not heat, call for service.

Heat pump does not run and control board displays:  
FAULT- 
NO FLOW

Verify circulating pump is on and all necessary valves are in the 
correct positions. Verify filter and skimmers are clean. Check 
water level in pool. Temporarily turn off all fountains and water 
falls that bypass the heat pump water inlet. If this does not 
correct the problem, call for service.

Heat pump does not run and control board display shows: 
FAULT- 
HIGH REF PRESSURE

Verify circulating pump is on and that there are no water flow 
restrictions to the heat pump. If the filter pump is a two speed 
or variable speed pump, switch to a higher speed. Make sure 
all necessary valves are open or in the proper positions to allow 
proper water flow to the heat pump. Verify filter and skimmers 
are clean. Check for water level in the pool. This condition may 
also appear if the heat pump has not been operated for an 
extended period. To clear the condition, cycle the heat pump, 
on and off, up to 3 times. If this does not correct the problem, 
call for service.

Heat pump does not run or short cycles and control board 
display shows: 
FAULT- 
LOW REF PRESSURE

Check that fan is operating and air is coming out of the top of 
the heat pump, while short cycling. If heat pump does not run at 
all, call for service.

Heat pump leaking water.

Possible heat exchanger or plumbing leak. Turn the heat 
pump off, then turn circulating pump off for at least one hour 
to see if the water leak stops. If the water leak stops, normal 
condensation is occurring. If the water leak continues, after the 
heat pump is shut off for at least one hour, call for service.

Summary of Contents for Jandy Pro Series JE1500T

Page 1: ...on of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintena...

Page 2: ......

Page 3: ...Spa Connection 3 Wire Connection 16 Figure 11b AquaLink RS or Remote TSTAT Connection 2 Wire Connection 16 Figure 12 AquaLink RS to JE Heat Pump 17 Figure 13 JE Heat Pump Connection to Power Center 1...

Page 4: ...Page 2 ENGLISH Jandy Pro Series JE Heat Pumps Installation and Operation Manual...

Page 5: ...rovides installation and operation instructions for the Jandy Pro Series JE models of heat pumps Read these installation and operation instructions completely before proceeding with the installation C...

Page 6: ...here possible shelter the pool from prevailing winds with well trimmed hedges or other landscaping cabanas or fencing 7 The use of an automatic pool cover if installed provides a valuable safety featu...

Page 7: ...installation is required to assure safe operation The requirements for Zodiac heat pumps include the following 1 Field assembly if required 2 Appropriate site location and clearances 3 Sufficient air...

Page 8: ...ing Scroll Scroll Scroll CABINET ABS REFRIGERANT 64 Oz R410A 78 Oz R410A 78 Oz R410A 78 Oz R410A 118 Oz R410A 126 Oz R410A 118 Oz R410A 126 Oz R410A REFRIGERANT HIGH PRESSURE ALARM 600 PSI reset to 46...

Page 9: ...ed indoors means of condensate disposal must be provided Indoor installation requires factory consultation Lawn Sprinklers Keep lawn sprinkler heads from spraying on the heat pump to prevent corrosion...

Page 10: ...ater connections are no more than 10 feet below the pool water surface or no more than 5 feet above it See instructions for pressure switch adjustment Section 5 6 in the heat pump start up section of...

Page 11: ...ng on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to adjust water...

Page 12: ...the front cover of the junction box 4 Electrical supply lines must be run through watertight conduit Route the wires and conduit through the knock out designated for high voltage on the right side of...

Page 13: ...CAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP POOL HEATER VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FROM...

Page 14: ...and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass Valv...

Page 15: ...BK BL BK BK BR W BL Y Y BL W BR HIGH REFRIGERANT PRESS SWITCH LOW REFRIGERANT PRESS SWITCH WATER TEMP DEFROST TEMP BK R R L1 L2 Y Y Y Y BK W R R FAN MOTOR BR BR W BK W W W W W R R GROUND GR GR R REVE...

Page 16: ...GR Y GROUND POWER BOARD COMPRESSOR FAN MOTOR WATER PRESSURE SWITCH USER INTERFACE REVERSING VALVE OPTIONAL HIGH REFRIGERANT PRESSURE SWITCH LOW REFRIGERANT PRESSURE SWITCH CONTACTOR W W W W W L1 L2 L3...

Page 17: ...a Remote Pool Off Spa Selector 3 Wire Connection Install the Remote Pool Off Spa Selector 1 Turn off the power to both the pool spa control system and the heat pump unit 2 Remove the screws that attac...

Page 18: ...Setup mode press and hold the MENU POOL and SPA buttons for 5 seconds NOTE The display will revert back to OFF after one minute since the last key press 3 Press the Up or Down button to display REMOTE...

Page 19: ...trol connected to the heat pump the display on the heat pump will show JANDY REMOTE ONLINE PUSH MENU TO DISABLE When the JE heat pump is online with the RS control all functionality of the control on...

Page 20: ...re control When that happens the heat pump will automatically shut off but the filter pump will keep running 5 2 Operating the Controller Your new Jandy Pro Series JE heat pump is controlled by an adv...

Page 21: ...LL will not be displayed if the unit is not provided with chiller You can change the temperature set point by pressing the Up or Down button Repeatedly press the Up or Down button until you reach the...

Page 22: ...de 2 To enter the User Setup mode press and hold the MENU button for 5 seconds 3 To select spa timer use the Up or Down button to scroll through to display SELECT USER SETUP SPA TIMER Press the MENU b...

Page 23: ...mum requirement of 30 gpm 114 lpm after the direction fitting or elbow has been installed Make sure the pool filter is clean before making any pressure switch adjustment A dirty filter will restrict t...

Page 24: ...em which has been under water Zodiac recommends that you inspect your heat pump on a regular basis and especially after abnormal weather conditions The following basic guidelines are suggest ed for yo...

Page 25: ...t gas enters the heat exchanger where the water extracts the heat The pump pulls in cool pool water which in turn converts the hot gas back into a liquid refrigerant and starts the cycle over again Th...

Page 26: ...run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers are clean Check water level in pool Tempora...

Page 27: ...sure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re closes...

Page 28: ...pansion Valve 1500 R0575000 15 Thermal Expansion Valve 2000 2500 R0575100 15 Thermal Expansion Valve 3000 R0575200 16 Air Temperature Sensor All R0575300 17 High Pressure Switch All R0575400 18 Low Pr...

Page 29: ...mps Installation and Operation Manual 9 3 Zodiac JE 1500 Heat Pumps Exploded View C 1 2 3 4 5 6 7 8 9 10 11 12 20 21 DETAIL C SCALE 1 8 13 14 15 16 17 18 19 33 See Figure 19 for detail Figure 16 Zodia...

Page 30: ...allation and Operation Manual 9 4 Zodiac JE 2000 JE2500 JE3000 Heat Pumps Exploded View C 1 2 3 4 5 6 7 9 8 10 12 20 11 21 23 DETAIL C SCALE 1 8 15 14 13 17 18 22 19 33 See Figure 20 for detail Figure...

Page 31: ...ation and Operation Manual 9 5 Zodiac JE Single Phase Electric Box 9 6 Zodiac JE Three Phase Electric Box Figure 18 Zodiac JE Single Phase Electric Box Figure 19 Zodiac JE Three Phase Electric Box 24...

Page 32: ...acPoolSystems com Zodiac Pool Systems Canada Inc 2115 South Service Road West Unit 3 Oakville ON L6L 5W2 1 888 647 4004 www ZodiacPoolSystems ca ZODIAC is a registered trademark of Zodiac Internationa...

Reviews: