Page 21

ENGLISH

  

 

 

Jandy

® 

Pro Series JE Heat Pumps   

|

   Installation and Operation Manual

User Setup mode.

5.5 

set point lockout

Make sure the control is in the 

on

 mode (

pool

 or 

spa

), press and hold the 

up

 and 

down

 buttons for 5 

seconds. The set point will be locked and the control 

will operate in the mode it was in when the Set Point 

Lockout occurred. If an attempt to change the set point 

is made while the control is in Set Point Lockout, the 

control will display 

sEt point loCKEd

. To unlock 

the Set Point Lockout, press and hold the 

up

 and 

down 

buttons for 5 seconds. The unit will display 

sEt point   

unloCKEd

.

5.6 

Water pressure switch adjustment

  Caution

The water pressure switch should be adjusted 
to turn the heater off when the pump is off. 
Setting the switch to close at too low of a flow 
can damage the appliance. Adjust the switch 
to turn the heater off, not on.

The pressure switch is preset at the factory for 

activation at 2 psi (14 kPa). This is the minimum setting 

for the water pressure switch and works for all basic 

installations. Only adjust the water pressure switch if 

the heat pump does not operate 

when the proper flow 

is applied to unit

 

or if the heat pump does not shut 

off when the filter pump is off. Occasionally, unusual 

plumbing configurations or necessary restrictions in 

the plumbing may cause pressure sensing problems. In 

these rare situations, the plumbing system configuration 

may require adjustment of the water pressure switch.

Adjustment of the pressure switch may be necessary 

if any part of the filter system piping is 3 feet (1 m) or 

more above the top of the heat pump jacket.

Do not adjust the pressure switch if the heat pump is 

installed more than 5 feet (1.5 m) above or 10 feet  

(3 m) below the pool surface. Consult your local 

Zodiac

®

 dealer for recommendations.

On some installations, the piping from the heat pump 

to the pool is very short. The back pressure could be 

too low to trigger the pressure switch. If this happens, 

it may be necessary to install a directional fitting or 

elbows where the return line enters the pool. This will 

increase back pressure enough for the heat pump to 

operate properly. If this configuration is necessary, 

be sure to check that the system flow is above the 

minimum requirement of 30 gpm (114 lpm) after the 

direction fitting or elbow has been installed. 

Make sure the pool filter is clean before making any 

pressure switch adjustment: A dirty filter will restrict the 

water flow and the pressure switch cannot be adjusted 

properly. 
To adjust the pressure switch: 
1.   Be sure that all valves in the system are set to 

allow water flow through the heat pump. Start the 

filter pump.

2. 

Set the heat pump control to call for heat. Set the 

heat pump control to the POOL HEAT mode. 

3. 

If the heat pump control displays “NO FLOW”, 

then the flow in the system may be below the 

minimum flow of 30 gpm (114 lpm) needed for 

the safe operation of the heat pump. Investigate 

and correct any flow problems before adjusting the 

water pressure switch.

4. 

Remove the heat pump’s control access panel. The 

water pressure switch is located in the lower left 

corner of the control compartment.

5. 

After confirming the flow rate is at a minimum 

of 30 gpm (114 lpm), slowly rotate the thumb 

wheel on the water pressure switch in a 

counterclockwise 

direction until the “NO FLOW” 

indicator disappears from the control display. 

Remember that there is a time delay before the 

heat pump compressor will start.

6. 

Once the heat pump is running, turn off the filter 

pump. The heat pump should turn off immediately.

7. 

If the heat pump continues to operate when the 

filter pump is off, turn the thumb wheel on the 

water pressure switch in a 

clockwise 

direction 

until “NO FLOW” is displayed on the control and 

the heat pump shuts down. 

8. 

Check the setting of the water pressure switch by 

starting and stopping the filter pump and checking 

the control display and operation of the heater 

between each flow change.

9. 

If the water pressure switch cannot be adjusted 

to accommodate the conditions listed above, 

an external flow switch must be added to the 

plumbing system to ensure that the heat pump will 

not operate without the proper flow through the 

heat exchanger.

section 6.  General Maintenance

6.1 

Water Chemistry

Proper chemical balances are necessary for sanitary 

bathing conditions as well as ensuring your heat pump’s 

long life. Be sure to keep your chemical and mineral 

concentration levels within the values indicated in  

Table 3. 

notE

  For spas, it is also necessary to perform water 

changes in addition to chemical treatment. It is 
recommended to change the spa water every 
60 days for light usage and every 30 days if 
usage is heavy.

Summary of Contents for Jandy Pro Series JE1500T

Page 1: ...on of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintena...

Page 2: ......

Page 3: ...Spa Connection 3 Wire Connection 16 Figure 11b AquaLink RS or Remote TSTAT Connection 2 Wire Connection 16 Figure 12 AquaLink RS to JE Heat Pump 17 Figure 13 JE Heat Pump Connection to Power Center 1...

Page 4: ...Page 2 ENGLISH Jandy Pro Series JE Heat Pumps Installation and Operation Manual...

Page 5: ...rovides installation and operation instructions for the Jandy Pro Series JE models of heat pumps Read these installation and operation instructions completely before proceeding with the installation C...

Page 6: ...here possible shelter the pool from prevailing winds with well trimmed hedges or other landscaping cabanas or fencing 7 The use of an automatic pool cover if installed provides a valuable safety featu...

Page 7: ...installation is required to assure safe operation The requirements for Zodiac heat pumps include the following 1 Field assembly if required 2 Appropriate site location and clearances 3 Sufficient air...

Page 8: ...ing Scroll Scroll Scroll CABINET ABS REFRIGERANT 64 Oz R410A 78 Oz R410A 78 Oz R410A 78 Oz R410A 118 Oz R410A 126 Oz R410A 118 Oz R410A 126 Oz R410A REFRIGERANT HIGH PRESSURE ALARM 600 PSI reset to 46...

Page 9: ...ed indoors means of condensate disposal must be provided Indoor installation requires factory consultation Lawn Sprinklers Keep lawn sprinkler heads from spraying on the heat pump to prevent corrosion...

Page 10: ...ater connections are no more than 10 feet below the pool water surface or no more than 5 feet above it See instructions for pressure switch adjustment Section 5 6 in the heat pump start up section of...

Page 11: ...ng on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to adjust water...

Page 12: ...the front cover of the junction box 4 Electrical supply lines must be run through watertight conduit Route the wires and conduit through the knock out designated for high voltage on the right side of...

Page 13: ...CAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP POOL HEATER VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FROM...

Page 14: ...and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass Valv...

Page 15: ...BK BL BK BK BR W BL Y Y BL W BR HIGH REFRIGERANT PRESS SWITCH LOW REFRIGERANT PRESS SWITCH WATER TEMP DEFROST TEMP BK R R L1 L2 Y Y Y Y BK W R R FAN MOTOR BR BR W BK W W W W W R R GROUND GR GR R REVE...

Page 16: ...GR Y GROUND POWER BOARD COMPRESSOR FAN MOTOR WATER PRESSURE SWITCH USER INTERFACE REVERSING VALVE OPTIONAL HIGH REFRIGERANT PRESSURE SWITCH LOW REFRIGERANT PRESSURE SWITCH CONTACTOR W W W W W L1 L2 L3...

Page 17: ...a Remote Pool Off Spa Selector 3 Wire Connection Install the Remote Pool Off Spa Selector 1 Turn off the power to both the pool spa control system and the heat pump unit 2 Remove the screws that attac...

Page 18: ...Setup mode press and hold the MENU POOL and SPA buttons for 5 seconds NOTE The display will revert back to OFF after one minute since the last key press 3 Press the Up or Down button to display REMOTE...

Page 19: ...trol connected to the heat pump the display on the heat pump will show JANDY REMOTE ONLINE PUSH MENU TO DISABLE When the JE heat pump is online with the RS control all functionality of the control on...

Page 20: ...re control When that happens the heat pump will automatically shut off but the filter pump will keep running 5 2 Operating the Controller Your new Jandy Pro Series JE heat pump is controlled by an adv...

Page 21: ...LL will not be displayed if the unit is not provided with chiller You can change the temperature set point by pressing the Up or Down button Repeatedly press the Up or Down button until you reach the...

Page 22: ...de 2 To enter the User Setup mode press and hold the MENU button for 5 seconds 3 To select spa timer use the Up or Down button to scroll through to display SELECT USER SETUP SPA TIMER Press the MENU b...

Page 23: ...mum requirement of 30 gpm 114 lpm after the direction fitting or elbow has been installed Make sure the pool filter is clean before making any pressure switch adjustment A dirty filter will restrict t...

Page 24: ...em which has been under water Zodiac recommends that you inspect your heat pump on a regular basis and especially after abnormal weather conditions The following basic guidelines are suggest ed for yo...

Page 25: ...t gas enters the heat exchanger where the water extracts the heat The pump pulls in cool pool water which in turn converts the hot gas back into a liquid refrigerant and starts the cycle over again Th...

Page 26: ...run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers are clean Check water level in pool Tempora...

Page 27: ...sure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re closes...

Page 28: ...pansion Valve 1500 R0575000 15 Thermal Expansion Valve 2000 2500 R0575100 15 Thermal Expansion Valve 3000 R0575200 16 Air Temperature Sensor All R0575300 17 High Pressure Switch All R0575400 18 Low Pr...

Page 29: ...mps Installation and Operation Manual 9 3 Zodiac JE 1500 Heat Pumps Exploded View C 1 2 3 4 5 6 7 8 9 10 11 12 20 21 DETAIL C SCALE 1 8 13 14 15 16 17 18 19 33 See Figure 19 for detail Figure 16 Zodia...

Page 30: ...allation and Operation Manual 9 4 Zodiac JE 2000 JE2500 JE3000 Heat Pumps Exploded View C 1 2 3 4 5 6 7 9 8 10 12 20 11 21 23 DETAIL C SCALE 1 8 15 14 13 17 18 22 19 33 See Figure 20 for detail Figure...

Page 31: ...ation and Operation Manual 9 5 Zodiac JE Single Phase Electric Box 9 6 Zodiac JE Three Phase Electric Box Figure 18 Zodiac JE Single Phase Electric Box Figure 19 Zodiac JE Three Phase Electric Box 24...

Page 32: ...acPoolSystems com Zodiac Pool Systems Canada Inc 2115 South Service Road West Unit 3 Oakville ON L6L 5W2 1 888 647 4004 www ZodiacPoolSystems ca ZODIAC is a registered trademark of Zodiac Internationa...

Reviews: