8. If the heater is equipped with a pressure relief
valve, clean any accumulated corrosion and make
sure that water runs freely.
9. Inspect the outside of the combustion chamber
and burner for corrosion and indication of im-
proper operation.
10. Perform a temperature rise test in accordance
with
Section 7.8
.
11. Regularly inspect electrical controls for deterio-
ration. Repair and replace as necessary.
12. Make a visual check of the main burner flame.
The flame can be seen in a view port on the lower
right side of the heater. The flame should be light
blue in color and short, see Figure 36. If flame
appearance is otherwise, adjustment is necessary
as described in the following section.
NOTE
After installation and first start-up, check the
heat exchanger for black carbon soot buildup
after the following periods of operation:
24 hours, seven (7) days, 30 days, 90 days
and once every six (6) months thereafter.
NOTE
Keep this manual in a safe place for future
reference by you and your professional
technician when inspecting and servicing the
heater.
Section 9. Troubleshooting
9.1
General Heater Troubleshooting
Table 11 lists some of the more common prob-
lems, causes and solutions encountered when running
the heater. Most problems occur when the heater is
being started for the first time after installation or at
spring start-up. Careful installation and maintenance
will help ensure years of trouble free use from your
LXi heater.
Be aware that premix combustion systems of the
type found in the LXi heaters have special character-
istics that affect operation and troubleshooting. See
Section 10.2
and
Section 10.3
for important informa-
tion about the system.
9.2
Service Codes
The LXi controller monitors several functions
of the heater. In the event of a malfunction, the LXi
controller will display a FAULT message. Table 12
lists the LXi Heater Service Codes along with potential
causes and remedies.
9.3
Ignition Control LED Service Codes
In addition to the service codes shown in the
previous section, the ignition controller in the LXi
heater has an LED light that flashes to indicate various
different faults. Table 10 lists the LED codes and the
corresponding fault description:
Table 10. Ignition Control LED Fault Codes
LED Code
Fault Description
The LED light is on continu-
ously.
Ignition Control Fault. Refer to
qualified service personnel.
LED single flash.
Air flow fault.
LED double flash.
Flame exists when there is NO
call for heat. Refer to qualified
service personnel.
LED triple flash.
Ignition lockout (heater has
cycled three (3) times and has
locked out after the third try).