The heat pump must be protected from back-

siphoning of water. If there is any chance of back-

siphoning, provide a check valve between the pool and 

the filter pump inlet.

When an automatic chemical feeder is installed 

in the plumbing, it must be installed downstream of the 

heat pump. A check valve must be installed between 

the heat pump and the chemical feeder to prevent back-

siphoning of chemically saturated water into the heat 

pump where it will damage the components. 

3.4 

automatic Flow Control Valve

The inlet/outlet header of the EE-Ti heat pump 

comes equipped with an internal automatic flow control 

valve. The automatic flow control valve maintains 

the proper flow through the heat pump at rates up to 

approximately 125 gpm (475 lpm). If the filter system 

flow rate is higher than approximately 125 gpm (475 

lpm), install a manual bypass valve (see Figure 4). 

note

  Be advised that if your circulation pump is over 

2 HP 

or

 if the total flow exceeds 125 gpm (475 

lpm), you will have to add an external bypass 

valve.

3.5 

Multiple unit installation

3.5.1  Heat pump and Heater Combination

In certain regions of the country it may be more 

economical to run a heat pump during the warmer 

months and a gas heater during the cooler months. 

In some situations it may be desirable to run the 

heat pump in the “Chiller” mode during the hottest 

portion of the year and a heater during the cooler 

months. 

The Zodiac heat pump may be plumbed with a gas 

or electric heater or any combination of heat sources 

including solar. All heat sources must be plumbed in 

parallel to work correctly and efficiently.

Figure 5 illustrates a recommended plumbing 

layout for a heat pump / heater / solar combination 

heating system for a pool / spa combination. Your 

system may not contain all of these components, but the 

basic plumbing will apply by eliminating the component 

in the illustration that is not a part of your system.

3.5.2  Multiple Heat pump Connections

All plumbing on multiple heat pump installations 

must be done in parallel (see Figures 6 and 7). An 

equal flow of water to each heat pump is important for 

optimum operation. 

note

  It may be necessary to adjust water pressure 

switch if a unit is installed below the water level. 

See Section 5.6 for details on when and how to 

adjust the pressure switch.

note

  Each heat pump allows a maximum flow rate of 

125 gpm (475 lpm) and requires a minimum of 

30 gpm (114 lpm).

section 4.  electrical Connections

4.1 

General information

Wiring connections must be made exactly as 

shown in the wiring diagram found on the inside of 

the heat pump access compartment (see Figure 8 for 

single phase electrical wiring and Figure 9 for 3-phase 

electrical wiring). The heat pump must include a 

definite means of grounding and bonding. There is a 

bonding lug on the right side of the heat pump, where a 

bond wire must be attached.

  WarninG

eleCtriCal sHoCK HaZard. 

This heat 

pump contains wiring that carries high voltage. 

Contact with these wires may result in severe 

injury or death. Disconnect power circuit before 

connecting the heat pump

  aVertisseMent

possiBilitÉ de CHoCs ÉleCtriQues

Ce système de chauffage contient du filage 

de haut voltage. Un contact avec ces fils peut 

résulter en des blessures sérieuses ou la mort. 

Débranchez le circuit de puissance avant de 

relier la pompe à chaleur

  aViso

peliGro de desCarGa elÉCtriCa. 

Esta bomba de calor, contiene cableado 

de alta tensión. El contacto con los cables 

podría ocasionar lesiones graves o la muerte. 

Desconecte el circuito de alimentación, antes 

de conectar la bomba de calentar.

  Caution

Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause 

improper and dangerous operation. Verify proper 

operation after servicing.

  attention

Au moment de l’entretien des commandes, 

étiquetez tous les fils avant de les débrancher. 

Des erreurs de câblage peuvent entraîner un 

fonctionnement inadéquat et dangereux.

  preCauCiÓn

Proceda a etiquetar todos los cables antes de su 

desconexión en los controles de mantenimiento. 

Los errores de cableado pueden ocasionar 

un funcionamiento peligroso e inadecuado. 

Comprobar que el funcionamiento es correcto, 

una vez efectuado el mantenimiento.

Summary of Contents for Jandy EE-Ti

Page 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Page 2: ......

Page 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Page 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Page 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Page 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Page 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Page 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Page 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Page 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Page 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Page 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Page 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Page 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Page 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Page 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Page 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Page 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Page 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Page 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Page 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Page 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Page 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Page 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Page 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Page 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Page 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Page 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Page 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Page 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Page 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Page 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...

Reviews: