background image

Page 3

ENGLISH

  

 

 Zodiac

®

 Jandy

® 

Heat Pumps Model EE-Ti   

|

   Installation and Operation Manual

1.2.1  spa/Hot tub safety rules

 WarninG

The U.S. Consumer Product Safety Commission 

warns that elevated water temperature can 

be hazardous. Consult heater operation and 

installation instructions for water temperature 

guidelines before setting temperature.

 aVertisseMent

La Commission U.S. de Sécurité des Produits 

pour les Consommateurs indique que des 

températures de l’eau élevées peuvent être 

dangereuses. Voir la notice d’installation 

et de fonctionnement pour le réglage de la 

température.

 aViso

La Comisión de Seguridad de Productos para 

el Consumidor de los Estados Unidos, advierte 

que una temperatura elevada del agua puede 

ser peligrosa. Consulte las instrucciones de 

instalación y funcionamiento del calentador 

para seguir las directrices relacionadas con la 

temperatura del agua antes de proceder a fijar 

la temperatura.

 WarninG

The following “Safety Rules for Hot Tubs,” 

recommended by the U.S. Consumer Product 

Safety Commission, should be observed when 

using the spa.

  aVertisseMent

Les Règlements suivants pour Cuves 

Thermales, tel que recommandés par la 

Commission U.S. de Sécurité des Produits pour 

les Consommateurs, devraient être respectés 

lors de l’utilisation du spa.

  

aViso

Al utilizar el spa, deberán observarse, las 

siguientes “Reglas de Seguridad para Baños 

Calientes” recomendadas por la Comisión de 

Seguridad de Productos para el Consumidor de 

los Estados Unidos.

1.  Spa or hot tub water temperature should never 

exceed 104°F (40°C). One hundred degrees 

Fahrenheit (100°F [38°C]) is considered safe for a 

healthy adult. Special caution is recommended for 

young children.

2.  The drinking of alcoholic beverages before or 

during spa or hot tub use can cause drowsiness 

which could lead to unconsciousness, and 

subsequently result in drowning.

section 1.  General information

1.1 

introduction

This manual provides installation and operation 

instructions for the Zodiac EE-Ti models of heat pumps.  

Read these installation and operation instructions 

completely before proceeding with the installation. 

Consult Zodiac Pool Systems, Inc. (“Zodiac”) with any 

questions regarding this equipment. To obtain additional 

copies of this manual contact us at 800-822-7933. The 

following is the address for information:

  Zodiac Pool Systems, Inc.  

2620 Commerce Way 

Vista, CA 92081 USA

The EE-Ti heat pump gets electrical power from 

an external source and provides a dual digital thermostat 

control system for pool/spa combinations or preheat 

convenience.

This heat pump is specifically designed for heating 

fresh water swimming pools and spas. Do not use it 

as a general service heater. Consult your dealer for the 

appropriate Zodiac products for these applications.

note

  “Fresh water swimming pools and spas” include 

systems that utilize saltwater chlorine generator  

units, such as the Zodiac AquaPure

®

 Electronic 

Chlorine Generator. Please ensure that the salt 

content of the pool/spa 

does not exceed

 

4500 ppm and water flow rate is within  

30-125 gpm (110-475 lpm).

installation and service must be performed by 

a qualified installer or service agency.

to the installer: 

After installation, these 

instructions must be given to 

the homeowner or left on or 

near the heat pump.

to the user: 

This manual contains 

important information that 

will help you in operating and 

maintaining this heat pump. 

Please retain it for future 

reference.

attention

1.2 

Consumer information and safety

The EE-Ti series of heat pumps are designed 

and manufactured to provide many years of safe 

and reliable service when installed, operated and 

maintained according to the information in this manual 

and the installation codes referred to in later sections. 

Throughout the manual, safety warnings and cautions 

are identified by the “ “ symbol. Be sure to read and 

comply with all of the warnings and cautions.

Summary of Contents for Jandy EE-Ti

Page 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Page 2: ......

Page 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Page 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Page 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Page 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Page 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Page 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Page 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Page 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Page 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Page 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Page 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Page 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Page 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Page 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Page 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Page 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Page 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Page 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Page 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Page 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Page 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Page 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Page 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Page 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Page 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Page 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Page 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Page 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Page 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Page 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...

Reviews: