14

Display

Possible causes

Solutions

Resetting

Error 12

ST5 sensor error  

compressor discharge 

sensor

Sensor is faulty or offline  (J13 

connector)

 Reconnect or change the sensor Press 

Error 13

ST4 sensor fault fluid line 

sensor

Sensor is faulty or offline  (J16 

connector)

 Reconnect or change the sensor Press 

Error 14

ST1 sensor fault water 

intake sensor

Sensor is faulty or offline  (J46 

connector)

 Reconnect or change the sensor Press 

  

4.3  I  Additional menus

To access the menu, press 

.

To browse the menus and modify the values, press 

 or 

To validate a selection, press 

.

To go back in the menus, press 

Water temperature on intake

Air temperature
Defrost sensor
Fluid line sensor

Compressor discharge temperature
Compressor operating speed
Ventilator operating speed

Opening of electronic valve

(only accessible to professionals)

Temperature set point

Hysteresis to switch to cooling mode in 

relation to the setpoint
Calibration of the ST1 water intake sensor
Calibration of the ST2 air intake sensor
Cooling mode activation
Fixed operating hours counter
Counter with operating hours reset
Activation of continuous screen backlighting
Activation of heating priority mode
“ON” operation of the filtration pump (if P50 

= 3)
“OFF” operation of the filtration pump (if P50 

= 3)

Only accessible to professionals

Values provided for information purposes, factory settings

EN

Summary of Contents for Heat Select ZS500 MD4

Page 1: ...H0430700_REVJ 2019 04 More documents on www zodiac com Instructions for installation and use English Heat pump Translation of the original instructions in French EN...

Page 2: ...ipment even postage and packing paid travels at the risks and perils of the recipient The latter shall issue reserves in writing on the carrier s delivery slip if damage is detected caused during tran...

Page 3: ...the device it is vital that you read this installation and user manual as well as the warranty booklet delivered with the device Failure to do so may result in material damage or serious or fatal inju...

Page 4: ...y or any other support The device must not be installed With the blowing towards a permanent or temporary obstacle awning brushwood etc less than 5 metres away Within range of water or mud jets sprays...

Page 5: ...valve water entry adjustment valve optional water exit adjustment valve optional water treatment minimum distance Connection to a standard filtration circuit To evacuate the condensation fit a 18 pip...

Page 6: ...tions in force in the country where it is installed The device is provided for connection to a general power supply with a TT and TN S neutral regime Electrical protection by circuit breaker D curve f...

Page 7: ...kit available as an accessory plastic cover metal support RJ11 RJ45 extension cable For the connection consult the manual supplied with the kit 1 4 2 Heating priority option This function helps to ke...

Page 8: ...t least 12 hours day the longer this time the longer the appliance will have enough operating range to heat up in Smart or Eco Silence mode Cover the basin with a sheet bubble canopy canvas etc to pre...

Page 9: ...and D fully then valve E by half the air which has built up in the heat pump condenser and the filtration circuit will bleed out If valves D and E are not present open valve A wide and close valve C...

Page 10: ...perating speed Operating power V1 100 Smart Boost V2 75 Eco Silence V3 50 Objective Most economical and quietest operation Smart temperature control no intervention is needed to change the operating m...

Page 11: ...fine the time ranges and operating modes by daily or weekly range Water cooling function activated Displays the water flow present or Set the rate using valve E or C if no valve E In this setting phas...

Page 12: ...shock which may cause material damage serious injury or even death Do not disconnect the electricity supply when the device is running If the electric power supply is interrupted wait a minute before...

Page 13: ...t in its defrost cycle this is not normal Switch off and disconnect the heat pump immediately and contact your reseller The device is not working If there is no display check the supply voltage and th...

Page 14: ...ventilator motor Error 06 Compressor supply overheating Machine s rear panel slots blocked Clean the rear panel If problem persists call an approved technician Automatic if fewer than 4 faults per ho...

Page 15: ...n the menus press Water temperature on intake Air temperature Defrost sensor Fluid line sensor Compressor discharge temperature Compressor operating speed Ventilator operating speed Opening of electro...

Page 16: ...15 4 4 I Wiring diagrams 4 4 1 ZS500 MD4 MD5 MD8...

Page 17: ...16 4 4 2 ZS500 TD5 TD8 EN...

Page 18: ...B 50 connector to be glued x2 C Condensation evacuation kit 18 D Winterizing cap x2 E Winterizing cover Heating priority F Kit for remote control G Plant room kit H Condensate pan I PAC NET cleaning...

Page 19: ...ntensity A 10 13 9 6 22 8 Minimum cable section mm 3x2 5 3x2 5 5x2 5 3x6 5x2 5 3G2 5 3G2 5 5G2 5 3G6 5G2 5 Proof pressure Pa 300 000 Service pressure Pa 150 000 Head loss mCE 1 5 Water flow recommende...

Page 20: ...23 49180 St Barth l my d Anjou cedex S A S U au capital de 1 267 140 SIREN 395 068 679 RCS PARIS Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Pour plus d...

Reviews: