3
1.1.3 Storage and transport conditions
1.1.4 Field of application
1.1.5 Operating principle
1.2 Description
1.2.1 Technical specifications
Appliance
Dehumidifying
capacity*
Power
consumed*
Power restored on
the ambient air*
Available
pressure**
Air flow-
rate
without option
L/h
W
W
mmCE
m³/h
CAE 508
8 2710 6500 15
2040
CAE 510
10
4040
9695
19
2720
CAE 513
13.5 5430 13030 23
3400
* under the following nominal conditions: air 30°C - humidity 70%.
**pressure available without hot water battery, refer to the battery load losses (see §1.3.8.1)
class: I
refrigerant gas:
R407C
refrigerant charge: see product information plate
1.2.2 Operating conditions
operating range: 10°C to 40°C (temperature in the swimming pool hall)
optimum operating conditions: between 25 °C and 30 °C
Hygro Control on request
Exclusive use: dehumidifying swimming pool halls.
Not to be used for any other purpose.
Install in a dry, ventilated technical room, protected from frost and damp, and not
used to store pool maintenance products.
The appliance must be transported upright on its pallet.
Condensation
Air
+35°C
40%RH
Air
+28°C
65% RH
Compressor
Expansion valve
Summary of Contents for CAE
Page 22: ...1 Sch ma lectrique Sch ma de puissance CAE 508 510 513...
Page 23: ...2 Sch ma de commande CAE 508 510 513...
Page 25: ...4 Dimensions weight without option Kg CAE 508 228 CAE 510 235 CAE 513 240...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...