1.3.8 Connecting the options
1.3.8.1 Hot water battery
Primary 90/70°C
Unit
CAE 508
CAE 510
CAE 513
Power
kW 23
35
41
Water flow rate
m³/h
1
1.6
1.9
Water load loss
mCE 1.25
1.9
2.5
Air load loss
Pa
30
50
72
Primary 45/40°C
Unit
CAE 508
CAE 510
CAE 513
Power
kW 5.9
9.8
11.6
Water flow rate
m³/h
1.03
1.7
2.01
Water load loss
mCE 1.54
2.3
3.12
Air load loss
Pa
28.5
47.3
67.7
1.3.8.2 Titanium water condenser
Water temperature input to the hot water battery: 45 °C minimum, 90°C maximum.
Maximum pressure water battery circuit: 3 bars
Power returned to the air at 27°C input to the hot water battery.
Connection to the primary circuit: before any valves or pumps
.
CAE 508-510-513
hot water battery (connections
using Ø20/27, male fitting)
suction
blowing
CAE 508-510-513
water condenser
main water heating
system
water treatment
pump
filter
by-pass
suction
blowing
water circulation
Average flow rate of water
in the condenser: 6 to 8m³/h
(depending on the device)
condenser inlet and outlet:
PVC Ø50
Automatic purge
Circulator
Check valve or
solenoid valve
Shut-off valve
Summary of Contents for CAE
Page 22: ...1 Sch ma lectrique Sch ma de puissance CAE 508 510 513...
Page 23: ...2 Sch ma de commande CAE 508 510 513...
Page 25: ...4 Dimensions weight without option Kg CAE 508 228 CAE 510 235 CAE 513 240...
Page 26: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...
Page 27: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...