16
ZP2 Series Compact Repeater Installation Manual
Configurable inputs
Configurable options
For configuraton options, see your fire panel installation manual.
Relay outputs
Number of relay outputs
2
Relay output specification
Potential free, NO/NC/C
Maximum output current
2 A / 30 VDC
Remote equipment outputs
Output voltage [1]
Minimum
Maximum
Supply voltage (VIN1, VIN2)
− 1.5 V (for example, 22.5 V at 24 V)
Supply voltage (VIN1, VIN2)
− 0.6 V (for example, 23.4 V at 24 V)
Maximum output current
1A
[1] For all local and remote expansion equipment outputs combined.
Mechanical and environmental specifications
Mechanical
Cabinet dimensions (L x W x H)
300 x 61 x 240 mm
Weight
2 kg
Number of cable knockouts
6 x Ø 20 mm at top of cabinet
4 x Ø 20 mm at bottom of cabinet
6 x Ø 20 mm at back of cabinet
IP rating
IP30 (DIN rail mounting only)
Environmental
Operating temperature
−5 to +40ºC
Storage temperature
−20 to +50ºC
Relative humidity
10 to 95% noncondensing