4. Installation
The following regulations must be observed:
• e.g. VDE 0100
• EN 806
• Installation must comply with all statutory regulations, as well as those of the local
electricity and water supply companies.
• The rating plate and technical specifications
• Only intact and appropriate tools must be used
Installation site
• Appliance must only be installed in frost-free rooms . Never expose appliance to
frost .
• The Appliance must be wall mounted and has to be installed with water connectors
downward or alternative transversely with water connections left .
• The appliance complies with protection type IP25 and may therefore be installed in
protection zone 1 according to VDE 0100 part 701 (IEC 60364-7) .
• In order to avoid thermal losses, the distance between the instantaneous water
heater and the tap connection should be as small as possible .
• The appliance must be accessible for maintenance work .
• Plastic pipes may only be used if they conform to DIN 16893, Series 2 .
• The specific resistance of the water must be at least 1100 Ω cm at 15 °C . The specific
resistance can be asked for with your water distribution company .
• When considering the location of the heater, consideration should be given to the
safe and visible disposal of any water resulting from leaks and seepage . This is par-
ticularly relevant when the heater is located in a cupboard or any concealed loca-
tion . For guidance please call Zip on 0345 6 005 005 .