34
Error code
Error
Possible cause
Measure
0x0000
Device is ready for operation.
-
-
0x0100
Actuator power supply is not
present or is too low
• Actuator power supply is not
sufficient.
►
Check the actuator power
supply.
0x0101
Temperature above maximum
permitted temperature.
• Ambient temperature is too
high.
• Overload of the products.
►
Provide sufficient ventilation/
cooling/connection.
►
Check that the product
moves freely.
0x0102
Temperature is below minimum
permitted temperature.
• Ambient temperature is too
low.
►
Provide an adequate
operating temperature.
0x0104
Pressure below minimum
permitted operating pressure.
• Operating pressure too low.
• Pressure supply not
connected.
Ö
Check the pressure supply.
0x0105
Pressure above maximum
permitted operating pressure.
• Operating pressure too high.
Ö
Check the pressure supply.
Ö
Install a pressure reducer.
0x0300
ControlWord is not plausible.
• Multiple bits were set in the
ControlWord.
►
In the ControlWord, check
that only one bit is set.
0x0301
Position implausible
• Transmitted TeachPosition is
not plausible.
►
Check the transmitted
process data.
• Permissible range,
depending on installation
size: Jaw stroke x 200
Example: GEP2016 with jaw
stroke of approx. 16.1 mm
results in a value of 3220.
0x0304
PositionTolerance is not
plausible.
• Transmitted PositionTol-
erance is not plausible.
►
Check the transmitted
process data.
0x0306
DeviceMode is not plausible.
• Transmitted DeviceMode is
not plausible.
►
Check the transmitted
process data.
0x0307
Motion task cannot be
executed.
• Multiple motion tasks in the
same direction.
• Move command transmitted
despite existing error.
►
Reset the direction flag.
• through move command
in the opposite direction
• through error reset
• through reset direction
flag
►
Send the move command
again.
0x0308
WorkpieceNo cannot be
selected.
• Transmitted workpiece
number is outside the
permitted range.
►
Check the transmitted
process data.
►
Apply the process data via a
handshake.
0x0309
TeachPosition was changed.
• Modified process data were
not taken over.
►
Apply the process data via a
handshake.
0x030F
TeachTolerance was changed.
• Modified process data were
not taken over.
►
Apply the process data via a
handshake.
0x0310
DeviceMode was changed.
• Modified process data were
not taken over.
►
Apply the process data via a
handshake.
0x0311
WorkpieceNo was changed.
• Modified process data were
not taken over.
►
Apply the process data via a
handshake.
0x0312
Initial state after gripper restart
• Modified process data were
not taken over.
►
Apply the process data via a
handshake.
13 Error diagnosis
INSTALLATION AND OPERATING INSTRUCTIONS:
LWR50L-24/-25
DDOC01073 / -
EN / 2022-07-20
Zimmer GmbH • Im Salmenkopf 5 •
77866 Rheinau, Germany •
+49 7844 9138 0 • www.zimmer-group.com