ZGR TOWER PRO 6 10 KVA
Operation manual
www.zigor.com
37
Overload to bypass
> 95 % event, cannot inverter-fed
Load for a long time when rated output current under 125 %
Bypass load capacity is controlled by bypass circuit breaker, tripping when
circuit current is exceeded.
Dynamic respond
± 5,0% (100% balance load)
≤
5 % in a cycle
Inverter output current limit
When current instantaneous value is 2 ~ 3 times of rated current peaks
(1.414 * rated power / (3 * 220)), the inverter will be conducted in each
pulse current limit protection.
DC component
≤
200 mV
Parallel circumfluence
1
+
1
≤
8 %, N
+
1
≤
3 %
Parallel equal current
1
+
1
≤
8 %, N
+
1
≤
10 %
EPO (Emergency Power Off)
Shut down UPS immediately
Surge
Meeting IEC60664-1 1.2/50uS+8/20uS 6kV/3kA.
Audible & Visual alarms
Line Failure, Battery Low, Overload, System Fault
Communications
USB or RS232 , SNMP card (optional) , Relay card (optional)
ENVIRONMENTAL AND MECHANIC CHARACTERISTICS
Protection
IP20
Noise level (at 1m)
< 50 dBA
Operating temperature
0 ºC
~
40 ºC
Storage temperature
-25 ºC
~
55 ºC
Relative humidity
0 ~ 95% (non-condensing)
Altitude max.
< 1500 m (without power reduction)
Dimensions (W x H x D)
191 x 720 x 483
mm
191 x 335 x 410
mm
191 x 720 x 483
mm
191 x 335 x 410
mm
Approx. Weight
69 kg
12 kg
77 kg
12 kg
STANDARDS
Marks
CE
Directives
EN 60950-1 , EN 62040-1, EN 62040-2, EN 62040-3, ROHS
IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-
6,IEC61000-4-8
NOTE: External battery Cabinet or Rack must be used for higher quantity and capacity of batteries.
•
The technical specifications may be modified without prior notice.
•
For any other technical need or modification of existing ones, consult ZIGOR.