![ZIGOR ZGR TOWER PRO 6 Operation Manual Download Page 26](http://html1.mh-extra.com/html/zigor/zgr-tower-pro-6/zgr-tower-pro-6_operation-manual_3711800026.webp)
ZGR TOWER PRO 6 10 KVA
Operation manual
www.zigor.com
26
When under the frequency setting press DOWN or when under battery quantity setting press UP, it goes to the
battery capacity setting. The battery capacity line flashes as in above picture (Fig. 4-15).
•
Use button ENTER/ON to choose the different battery capacity. Battery capacity range is 1-200Ah. (Note:
long-press of UP or DOWM can adjustment battery capacity quickly)
•
Press ESC/OFF button to exit the battery capacity setting (save the capacity setting) and goes to
frequency setting or battery quantity setting.
Battery number/quantity setting (bN)
Fig. 4-16 Battery quantity setting
When under the battery capacity setting press DOWN or when under bypass voltage upper limit setting press UP,
it goes to the battery quantity setting. The battery quantity line flashes as in above picture.
•
Use button ENTER/ON to choose the different battery quantity. Battery quantity range is 16
、
18, 20.
•
Press ESC/OFF button to exit the battery quantity setting (save the battery quantity setting) and goes to
battery capacity setting or bypass voltage upper limit setting.
Bypass High Level switch setting (HLS)
Fig. 4-17 Bypass voltage upper limit setting
When under the battery quantity setting press DOWN or when under bypass voltage lower setting press UP, it
goes to the bypass upper limit setting. The bypass upper limit line flashes as in above picture (Fig. 4-17).
•
Use button ENTER/ON to set the different bypass voltage upper limit. The bypass voltage upper limit
range is 5%, 10%, 15%,25% (25% only for 220 V output).
•
Press ESC/OFF button to exit the bypass voltage upper limit setting (save the bypass voltage upper limit
setting) and goes to battery quantity setting or bypass voltage lower limit setting.