8. Commissioning
8.1
Program setup
The suitable program must be set on the UFR1001E in accordance with the application. If the UFR1001E is
sealed/locked (red LED illuminated), the sealing has to be deactivated first.
Pr
Connection
Threshold values
Voltage
*1
3 AC with N
Low voltage
1x overvoltage, 1x undervoltage
1x overfrequency, 1x underfrequency
10 min average value, 1x vector shift
1x ROCOF
230 V
2
3 AC without N
400 V
3
3 AC with N
Medium voltage
2x overvoltage, 2x undervoltage
2x overfrequency, 2x underfrequency
10min mean value, 1x vector shift
1x ROCOF
57.7 V
4
3 AC without N
100 V
5
3 AC with N
230 V
6
3 AC without N
400 V
* default setting
Adjustment process:
If present, remove seal (only authorised person)
Apply control supply voltage at A1-A2
Slightly lift the key cover and turn 180°
Actuate the small blue button by firmly pressing the button cover (LED starts flashing) until the
green LED
is illuminated.
Sealing is deactivated
Press
button 1x
display
8
Info.
8
Press button 5x
display
8
Pr 1.
8
Set the program with the buttons
Press button 1x
display
8
no.
8
Press
button 1x
display
8
yes.
8
Press button
Device resets and starts with the newly selected program
Hint:
When changing programs, all parameters of the selected program are reset to “default settings“ (see
table „Default settings“).
Only change the parameters after having selected the correct program.
Summary of Contents for UFR1001E
Page 28: ...UFR1001E 12420 0701 03 Page 28 36 www ziehl de 14 Verification of conformity ...
Page 29: ...UFR1001E 12420 0701 03 Page 29 36 www ziehl de ...
Page 30: ...UFR1001E 12420 0701 03 Page 30 36 www ziehl de ...
Page 31: ...UFR1001E 12420 0701 03 Page 31 36 www ziehl de ...
Page 32: ...UFR1001E 12420 0701 03 Page 32 36 www ziehl de ...
Page 33: ...UFR1001E 12420 0701 03 Page 33 36 www ziehl de ...