background image

 

UFR1001E  

12420-0701-03

  

Page

 

5 / 36 

www.ziehl.de 

  

11 

Sealable  LED 

 

  

Press for > 2 s 

Lock / Unlock 

 

 LED  red 

Settings and simulation mode are locked, 
While attempting to set, 

8

LOc 

8

 is displayed for 3s 

 

LED green 

Setting and simulation enabled 

 
 

4.  Detailed description 

 

4.1 

Description of the connections 

Connection 

Description 

A1 and A2  

Rated control supply voltage Us, see 

Technical Data

 

11, 12, 14; 21, 22, 24

 

Relay K1 and K2

 

E1 

– E2  

Enable 

– Input 

Volt-free contact 

8

vsr .

8

 

 

off.

8

 , no function 

8

vsr .

8

 

 

8   

on.

8

 , E1-E2 closed: Vector shift active but not evaluated, 

monitoring of feedback contacts off for use with generator (mains 
synchronization)

 

8

vsr .

8

 

 

8

stby.

8

 , E1-E2 closed: K1 and K2 off (standby), vector shift off 

8

vsr .

8

 

 

8

Y1Y2.

8

 , E1-E2 closed: Feedback contacts no evaluated, vector 

shift off, when using with generator (mains synchronization) 

Y0, Y1, Y2 
Inputs, feedback contacts 

Volt-free n/o or n/c contact, self-learning when switching on 

Set value > turn-on time section switch under 

8

rel .

8

 

 

8

trel.

8

 / can 

switch-off if not connected or if external devices/switches can activate the 
section switch (

8

off .

8

I1 

Supply voltage for digital outputs, max. 27 V DC 

Q1…Q4 

Digital output over-/undervoltage/-frequency, Q3 + Q4 = ROCOF 

Q5 

Digital output error, in Program 3-6 additionally the 2nd threshold value  

L1, L2, L3, N 

Phase L1, L2, L3 and neutral conductor 

 

4.2 

Functional characteristics 

Functional characteristics 

Explanation 

VSR display value 

The highest measured value is always displayed. The display value is reset 
to 0 by deleting the max. value and when resetting into the go (good) state.  

Delay Enable On time 

Runs down when starting the unit and after opening the enable input; during 
this time there is no evaluation of the vector shift 

Reset time 

When a reset time  

8

dof

 

8

 is running, it is always counted down in the 

display (shortest one first) 

Reset 

Use the Reset key or interrupt the control voltage for > 2 s (comply with reset 
delay) 

Display mode 

8

Scn

8

 

After the last measurement it switches into the scan mode; this is indicated 
by the display

8

scn 

8

All measurements will now be displayed cyclically for the time set in 

8

dit

8

MIN / MAX values

 

All min and max values are saved zero-voltage maintained (non-volatile).  

Tripping time  
(only with feedback 
contacts connected)  

Connecting the feedback contacts enables measuring the shut-down time. 
After a tripping time with the test button it is displayed until a button is 
pressed again with a resolution of up to 1ms. 
Total shut-down time = Tripping time + Response time 

dal.

8

  

Summary of Contents for UFR1001E

Page 1: ... 131014 Fz Ba from Firmware 0 04 UFR1001E 12420 0701 03 Page 1 36 www ziehl de NA protection according to VDE AR N 4105 in plant power generators on the low voltage grid For use in in plant power generators on the medium voltage grid according to BDEW With selectable vector shift detection With selectable Rate of Change of Frequency ROCOF df dt protection New Firmware 0 04 ROCOF df dt protection D...

Page 2: ...chronization 12 8 Commissioning 13 8 1 Program setup 13 8 2 Control chart 14 8 3 Description of the parameters 16 8 4 Display mode last decimal point off 16 8 5 Menu mode last decimal point on 17 8 6 Configuration mode last decimal point flashes 17 8 7 Test mode only activated and connected feedback contacts 17 8 8 Alarm counter 17 8 9 Cumulative alarm time display in hours 17 8 10 Alarm memory 18...

Page 3: ... monitoring 40 520 V Measurement against N and or phase phase Under and overfrequency monitoring 45 65 Hz Monitoring the voltage quality 10 minute average value Vector surge monitoring 2 20 connectible Fail safe with monitoring of the connected section switch can be switched off 2 automatic restarts on error Passive autonomous system detection in accordance with Chapter 6 5 3 and Appendix D2 Monit...

Page 4: ...ith error code e g 8Err98 6 LED Time yellow ON A time is displayed 7 Last decimal point red OFF Display mode Illuminated Menu mode Flashes Configuration mode 8 Set Reset key in display mode normal state Press briefly Display of next measured value alarm counter Press for 2 s Reset quit error messages Press for 4 s Displays the program e g 8Pr 18 Press for 10 s Displays the software version e g 80 ...

Page 5: ...al output over undervoltage frequency Q3 Q4 ROCOF Q5 Digital output error in Program 3 6 additionally the 2nd threshold value L1 L2 L3 N Phase L1 L2 L3 and neutral conductor 4 2 Functional characteristics Functional characteristics Explanation VSR display value The highest measured value is always displayed The display value is reset to 0 by deleting the max value and when resetting into the go go...

Page 6: ...not lead to permanent shut down 5 Important information A marked switch and a protective device must be provided in the supply line in the vicinity of the device easily accessible as a disconnecting element rated current 6A Flawless and safe operation of such a device requires proper transport and storage professional instillation and later commissioning along with operation as intended Only perso...

Page 7: ...inet Ensure sufficient clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or interference with the cooling air current the permissible ambient temperature is decreased Caution Before you apply mains voltage to the device make sure that the permissible control voltage Us on the side rating plate matches the ma...

Page 8: ... connected automatic detection when switching on 4 Switch off the plant without recording an alarm e g with output contact of a ripple control receiver 5 Fuses only when line protection necessary e g 3x16A 6 Contact closed suppresses evaluation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 8stby 8 default sett...

Page 9: ...connected set 8Pr 18 8Pr 38 or 8Pr 58 4 Switch off the plant without recording an alarm e g with output contact of a ripple control receiver 5 Fuses only when line protection necessary e g 3x16A 6 Contact closed suppresses evaluation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 8stby 8 default setting e g thr...

Page 10: ... connected set 8Pr 18 r 8Pr 38 or 8Pr 58 4 Switch off the plant without recording an alarm e g with output contact of a ripple control receiver 5 Fuses only when line protection necessary e g 3x16A 6 Contact closed suppresses evaluation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 8stby 8 default setting e g ...

Page 11: ... be connected automatic detection when switching on 4 Switch off the plant without recording an alarm e g with output contact of a ripple control receiver 5 Fuses only when line protection necessary e g 3x16A 6 Contact closed suppresses evaluation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 8stby 8 default s...

Page 12: ...r no contacts can be connected automatic detection when switching on 4 Switch off the plant without recording an alarm e g with output contact of a ripple control receiver 5 Fuses only when line protection necessary e g 3x16A 6 Contact closed suppresses evaluation of feedback contacts and vector shift 8vsr 8 8 on 8 suppresses feedback contacts 8vsr 8 8y1y2 8 or switches device into standby 8vsr 8 ...

Page 13: ...F 57 7 V 4 3 AC without N 100 V 5 3 AC with N 230 V 6 3 AC without N 400 V default setting Adjustment process If present remove seal only authorised person Apply control supply voltage at A1 A2 Slightly lift the key cover and turn 180 Actuate the small blue button by firmly pressing the button cover LED starts flashing until the green LED is illuminated Sealing is deactivated Press button 1x displ...

Page 14: ...4105 Unit Up Down simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err4 Tolerance Master Slave Err5 Internal control Err6 Communication Err7 Contactor feedback contacts K1 K2 Err8 Limit error Err9 Parameter error Display mode Configuration mode Menu mode 1 3AC N 300V ...

Page 15: ...Unit Up Down simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err4 Tolerance Master Slave Err5 Internal control Err6 Communication Err7 Contactor feedback contacts K1 K2 Err8 Limit error Err9 Parameter error 1 3AC N 300V Display mode Configuration mode Menu mode ...

Page 16: ... 8 VSR8 81 Ph8 a vector surge on one phase leads to an alarm 83 Ph8 a vector surge on all phases simultaneously leads to an alarm 81 Ph8 83 Ph8 Periods 8per 8 Measuring time ROCOF 4 sensitive 50 insensitive Response time 8per 8 Period duration 8dal 8 8 48 8 508 delay Display 8ddi 8 Interval during which the display is updated in the display mode 8 0 18 8 2 08 8 4 Display mode last decimal point of...

Page 17: ... value the change in the display is accelerated 8 7 Test mode only activated and connected feedback contacts If feedback contacts of the section switch are connected to the UFR1001E and activated value set turn on time of section switch e g 5 0s the trip circuit can be tested by pressing the Test button To do that the measurement voltage has to be connected and no alarm is allowed to be present Af...

Page 18: ...during a program change 8 11 Standby counter and standby time The standby counter 8stby8 is increased by 1 with every standby shut down Up to 9999 shut downs are counted That lets the UFR1001E quickly detect how often e g shut down was performed through a ripple control receiver Query the standby counter Change into the display mode Press the button several times until display 8acxx8 Press the but...

Page 19: ...ress the button 1x Code lock on display 8 on8 flashes three times Code lock off display 8 off 8 flashes three times Return to menu mode menu item code lock If there are any problems with the code lock pin forgotten the lock can be switched off and the pin can be reset to 504 by keeping the Set key pressed while switching on the mains until 8Code8 8 off8 appears in the display 8 13 Sealing All the ...

Page 20: ...switch is displayed Adjustment process Select the menu item with the buttons until display 8si 8 Press the button 1x display 8si 8 8u 8 Use the buttons to set the measurement factor for simulation o 8u 8 Voltage 10min mean value frequency last simulated value o 8f 8 Frequency voltage last simulated value o 8vsr 8 Vector shift Press the button 1x display 8 2308 selected measurement factor is simula...

Page 21: ... 8 Vector surge 8stby8 Standby mode standby time standby counter 8y1y28 Evaluation of the feedback contacts is suppressed when E1 E2 are closed 8Deon8 Delay Enable On suppression time when switching on and after opening the enable input 81 ph 8 83 ph 8 Single phase three phase vector shift evaluation 8rocf8 8per 8 ROCOF df dt Periods 8rel 8 Relay ttrel8 Section switch turn on time 8 off8 no feedba...

Page 22: ...rvoltage V 253 438 253 438 253 438 HM Hysteresis V 3 0 3 0 3 0 3 0 3 0 3 0 dal Response time s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 60 60 60 U_ u_ Alarm on off on on On On on on u_ Undervoltage V 184 318 46 2 80 0 184 318 H_ Hysteresis V 5 0 5 0 1 0 1 0 3 0 3 0 dal Response time s 0 10 0 10 2 70 2 70 2 70 2 70 dof OFF delay s 60 60 60 60 60 60 U__ u__ Alarm on off Off Off off Off...

Page 23: ...ppression time s 2 2 3 3 3 3 vsr Number of phases 3ph 3ph 3ph 3ph 3ph 3ph Rocf rocf Alarm on off Off Off Off Off Off Off dfdt delta f delta t Hz s 0 80 0 80 0 80 0 80 0 80 0 80 Per periods 4 4 4 4 4 4 dal Response time s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 60 60 60 rEL trEL Response time Y1 Y2 s 5 0 5 0 off off off off ddi ddi Display delay s 0 5 0 5 0 5 0 5 0 5 0 5 dit Display ...

Page 24: ...s Adjustable 1 0 99 9 V Measurement error with N 0 6 of the measurement value Measurement error without N 0 8 of the measurement value Display accuracy 100V 1 digit res 1 V 100V 1 digit res 0 1V Measurement function 3 phase with without N Response time Adjustable 0 05 15ms 130 0 s Reset time Adjustable 0 200ms 999 s Frequency measurement Frequency range 40 70 Hz Adjustment range 45 00 65 00 Hz Hys...

Page 25: ...ty EN 61000 6 2 EMC noise emission EN 61000 6 3 Housing Construction form V6 Front to back size 55 mm Dimensions W x H x D 90 x 105 x 69 mm Wiring connection single strand each 1 x 4mm2 Finely stranded with wire end ferrule each 1 x 2 5mm2 Protection class housing IP 30 Protection class terminals IP 20 Mounting snap on fastening on 35 mm mounting rail acc EN 60 715 or with M4 screwed attachment ad...

Page 26: ...n the display Hysteresis error Upper threshold value must be higher than the lower threshold value check the threshold values 8Err98 appears in the display Parameter error Reset to factory settings see Program setup A time expires in the display Always when an OFF delay time 8dof 8 is running it is counted down in the display shortest one first Wait until the time has expired depending on the sett...

Page 27: ...l base 3 Riegel bar for snap mounting 4 Sealing max Ø 1 8 mm 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Bar for wall attachment with screws Riegelbohrung Ø 4 2 mm Bolt hole for fixing to wall with screws Ø 4 2 mm 1 2 6 3 48 58 45 3 61 8 16 5 90 Option 105 98 116 70 1 2 5 6 7 3 69 4 ...

Page 28: ...UFR1001E 12420 0701 03 Page 28 36 www ziehl de 14 Verification of conformity ...

Page 29: ...UFR1001E 12420 0701 03 Page 29 36 www ziehl de ...

Page 30: ...UFR1001E 12420 0701 03 Page 30 36 www ziehl de ...

Page 31: ...UFR1001E 12420 0701 03 Page 31 36 www ziehl de ...

Page 32: ...UFR1001E 12420 0701 03 Page 32 36 www ziehl de ...

Page 33: ...UFR1001E 12420 0701 03 Page 33 36 www ziehl de ...

Page 34: ...UFR1001E 12420 0701 03 Page 34 36 www ziehl de 15 Unbedenklichkeitsbescheinigung ÖVE ÖNORM E 8001 4 712 ...

Page 35: ...60 08 Change the Reset time with the buttons to 8 308 Keep the button pressed for 2s Return to display mode Change Reset time 8dof 8 must be change for all enabled limits 8 on8 Press the button 1x display 8u 8 Pr1 2 8u 8 Pr3 6 Press the button 5x display 8dof 8 8 60 08 Change the Reset time with the buttons to 8 308 Press the btton 1x display 8u 8 Pr1 2 8u 8 Pr3 6 Repeat for all enabled limits 8 o...

Page 36: ...ncy decrease protection f F_ 47 5Hz 100 ms 60 s Frequency increase protection f F 51 5Hz 100 ms 60 18 Adjustment values table BDEW June 2008 acc 3 2 3 3 1 Medium Voltage Pr 3 6 Function Adjustment range of the protective relay Default settings Voltage increase protection U 1 00 1 30 Un 1 15 Un 100 ms Voltage increase protection U 1 00 1 30 Un 1 08 Un 60 s Voltage decrease protection U 0 15 1 00 Un...

Reviews: