UFR1001E
12420-0701-03
Page
6 / 36
www.ziehl.de
After a shut-down in the simulation mode the total shut-down time is
displayed until the button is pressed again)
The longer time of both channels is always displayed.
Alarm counter
The unit saves max 100 alarms (cause, measurement value, at operating
time). The LEDs indicate the cause; the tripping value that led to the alarm
each stands in the 7-segment display. Alternately the time difference, current
operating time
– tripping operating time is displayed. (how long ago the
alarm triggered)
Cumulative alarm time
8
tal .
8
The cumulative alarm time TAL indicates how long the relay was switched
off due to an alarm. It is recorded with a resolution of 1 minute and only
when the control voltage is applied.
Query: In the display mode button to
8
ac .
8
is displayed. 1x
button =
Cumulative alarm time
8
tal .
8
Standby mode
8
vsr .
8
8
stby.
8
If E1-E2 are closed (e.g., by ripple control receiver, timer, dimmer), Relays
K1 and K2 are switched off. The number and duration of the shut-downs is
recorded.
Query: In the display mode button to
8
ac .
8
is displayed. 2x
button =
Standby counter
8
stby.
8
1x
button = Standby time
8
stby.
8
Standby mode
8
vsr .
8
8
y1y2.
8
If E1-E2 are closed, the evaluation of the feedback contacts is suppressed.
That means when using generators, a section switch can be used for mains
synchronization.
Automatic restart attempts
If there is an error by the feedback contacts
8
err7
8
, 2 restart attempts are
automatically performed in an interval of 10s.
False triggering by undervoltage trips (e.g. during a thunderstorm) do not
lead to permanent shut-down.
5. Important information
A marked switch and a protective device must be provided
in the supply line
in the
vicinity of the device (easily accessible) as a disconnecting element
(rated current ≤ 6A).
Flawless and safe operation of such a device requires proper transport and storage, professional
instillation and later commissioning along with operation as intended.
Only persons who are familiar with the installation, commissioning and operation of the device and who
are correspondingly qualified for their job are permitted to work on the device. They must comply with the
contents of the operating manual, the instructions attached to the device and the pertinent safety
regulations for the erection and operation of electrical equipment.
The devices are built and certified in accordance with EN 60255 and leave the factory in a safe and
technically flawless condition. To maintain this condition they must comply with the safety regulations
marked in the operating manual with the headline "Caution". Failure to follow the safety regulations can
lead to death, bodily injury or property damage to the device itself and to other devices and equipment.
If the information contained in the operating instructions/operating manual are not sufficient,
please contact us directly or contact your responsible agency or representative.
Instead of the industrial norms and stipulations stated in the operating manual and applicable in Europe
you must comply with the valid and applicable regulations in the country of utilisation if the device is used
outside of the area of application.
WARNING
Hazards electrical voltage!
Can lead to an electric shock and burns.
Disconnect and de-energize before working on the system and the device.
!
Summary of Contents for UFR1001E
Page 28: ...UFR1001E 12420 0701 03 Page 28 36 www ziehl de 14 Verification of conformity ...
Page 29: ...UFR1001E 12420 0701 03 Page 29 36 www ziehl de ...
Page 30: ...UFR1001E 12420 0701 03 Page 30 36 www ziehl de ...
Page 31: ...UFR1001E 12420 0701 03 Page 31 36 www ziehl de ...
Page 32: ...UFR1001E 12420 0701 03 Page 32 36 www ziehl de ...
Page 33: ...UFR1001E 12420 0701 03 Page 33 36 www ziehl de ...