background image

 

MU1000K 

12370-0705-01

 

Page

 

5 / 12 

www.ziehl.de 

  

Commissioning 

6.1  Overview of commissioning 

The MU1000K can be commissioned to predefined standard ranges or scaled to an arbitrary range. 
 
There are two different ways to do the settings: 
 

Point 6.2 

– 6.4: MU1000K setting a predefined range 

Point 6.5 

– 6.7: MU1000K scaling an arbitrary range 

 

6.2  Overview of the predefined standard ranges 

Following standard ranges can be set without adjustment to the unit: 
 

Input (U / I) 

 

Input (Pt 100) 

 

Output 

Zero 
point 

Full scale   

Zero point  Full scale 

 

Zero 
point 

Full scale 

0 V - 

10 V 

 

-200 °C -   

 

0 V - 

10 V 

2 V - 

10 V 

 

-50 °C -   

 

2 V - 

10 V 

0 mA -  

20 mA 

 

0 °C -    

 

0 mA -  

20 mA 

4 mA -  

20 mA 

 

100 °C -   

 

4 mA -  

20 mA 

 

 

 

200 °C -   

 

 

 

 

 

 

 

0 °C 

 

 

 

 

 

 

 

50 °C 

 

 

 

 

 

 

 

100 °C 

 

 

 

 

 

 

 

150 °C 

 

 

 

 

 

 

 

200 °C 

 

 

 

 

 

 

 

250 °C 

 

 

 

 

 

 

 

300 °C 

 

 

 

 

 

 

 

400 °C 

 

 

 

 

 

 

 

500 °C 

 

 

 

 
 

 

Summary of Contents for MU1000K

Page 1: ...e www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual MU1000K updated 2018 11 12 sm from Firmware 0 04 MU1000K 12370 0705 01 Page 1 12 www ziehl de Universal Measuring Transducer ...

Page 2: ...mmissioning 5 6 1 Overview of commissioning 5 6 2 Overview of the predefined standard ranges 5 6 3 Setting a predefined range 6 6 4 Diagram for setting a predefined range 7 6 5 Query firmware version on the device 8 6 6 Overview of scaling an arbitrary range 8 6 7 Scaling of range 8 6 8 Diagram for scaling of range 9 6 9 Factory setting 10 7 Error search 10 8 Technical data 10 9 Housing Type K 12 ...

Page 3: ... mA are potentially separated from inputs and supply voltage With its universal power supply AC DC 24 240 V the measuring transducer can be connected to all common supply voltages 2 Overview of functions Current input 0 20mA scalable Voltage input 0 10V scalable Input Pt 100 3 wire 200 800 C scalable Output signal 0 20mA and 0 10V or 4 20mA and 2 10V Rated Supply Voltage AC DC 24 240V Insulation b...

Page 4: ... Instead of the industrial norms and regulations written in this instruction manual valid for Europe you must observe out of their geographical scope the valid and relevant regulations of the corresponding country 5 Installation The unit can be installed as follows Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715 for protection against fire external environmental con...

Page 5: ...1000K setting a predefined range Point 6 5 6 7 MU1000K scaling an arbitrary range 6 2 Overview of the predefined standard ranges Following standard ranges can be set without adjustment to the unit Input U I Input Pt 100 Output Zero point Full scale Zero point Full scale Zero point Full scale 0 V 10 V 200 C 0 V 10 V 2 V 10 V 50 C 2 V 10 V 0 mA 20 mA 0 C 0 mA 20 mA 4 mA 20 mA 100 C 4 mA 20 mA 200 C ...

Page 6: ...the zero point of the input Number of LED flashes Pt100 U I 1 x 200 C 0 V 0 mA 2 x 50 C 2 V 4 mA 3 x 0 C 4 x 100 C 5 x 200 C Press button Down Parameterization input full scale only for Pt100 input LED Power flashes 3x Select with button Set the full scale of the input Number of LED Number of LED flashes Pt100 flashes Pt100 1 x 0 C 5 x 200 C 2 x 50 C 6 x 250 C 3 x 100 C 7 x 300 C 4 x 150 C 8 x 400...

Page 7: ...MU1000K 12370 0705 01 Page 7 12 www ziehl de 6 4 Diagram for setting a predefined range Mode Normal state Parameterization mode ...

Page 8: ... the device and keep pressed the button Down After 5s flashes the green LED release button Down Parameterization input type LED Power flashes 1x Select with button Set the input type displayed by LEDs Pt100 U I Press button Down Parameterization input zero point LED Power flashes 2x Connect a signal at the input corresponding to the zero point Press button Down store of value green LED flashes 3 t...

Page 9: ...MU1000K 12370 0705 01 Page 9 12 www ziehl de 6 8 Diagram for scaling of range Signal input Zero point Signal input Full scale Mode Normal state Parameterization mode ...

Page 10: ...sumption 3 W 5 VA Inputs Input resistance Maximus Input signal Error of full scale Voltage input 12 kΩ DC 27 V 0 1 Current input 18 Ω DC 100 mA 0 5 Resolution 14 Bit Measuring range Max Resistance of sensor wire Pt100 sensor input 200 C 800 C 500 Ω Tolerance 0 5 of measured value 0 5 K Resolution 0 1 C Sensor current 0 6 mA Temperature factor 0 04 C K Outputs 2 outputs with common ground Voltage o...

Page 11: ...issible ambient temperature 20 C 65 C Permissible storage temperature 20 C 70 C Permissible wiring temperature 5 C 70 C Climatic conditions 5 85 rel humidity no condition Installation height 2000 m over N N Vibration resistance EN 60068 2 6 2 25 Hz 1 6 mm 25 150 Hz 5 g Auxiliary supply 18V 20mA Supply voltage for external measuring transducer DC 15 20V 25mA Housing Type K Dimension H x W x D 75 x ...

Page 12: ...Page 12 12 www ziehl de 9 Housing Type K Dimensions in mm 1 lower part 2 upper part 3 bar 4 screw 5 holes for screw mount 19 8 19 8 35 4 22 5 75 0 82 5 110 0 1045 1940 19 45 19 60 19 45 19 60 4 2 100 5 5 0 2 1 3 4 3 1 3 2 5 ...

Reviews: