6
Commissioning
6.1 Overview of commissioning
The MU1000K can be commissioned to predefined standard ranges or scaled to an arbitrary range.
There are two different ways to do the settings:
Point 6.2
– 6.4: MU1000K setting a predefined range
Point 6.5
– 6.7: MU1000K scaling an arbitrary range
6.2 Overview of the predefined standard ranges
Following standard ranges can be set without adjustment to the unit:
Input (U / I)
Input (Pt 100)
Output
Zero
point
Full scale
Zero point Full scale
Zero
point
Full scale
0 V -
10 V
-200 °C -
0 V -
10 V
2 V -
10 V
-50 °C -
2 V -
10 V
0 mA -
20 mA
0 °C -
0 mA -
20 mA
4 mA -
20 mA
100 °C -
4 mA -
20 mA
200 °C -
0 °C
50 °C
100 °C
150 °C
200 °C
250 °C
300 °C
400 °C
500 °C