MU1000K
12370-0705-01
Page
6 / 12
www.ziehl.de
6.3 Setting a predefined range
•
Power off the device
•
Press Button
[Set]
and keep pressed
•
Power on the device, and keep pressed the button [Set]
After 5s flashes the green LED, release button [Set]
Parameterization
„input type“ >> LED Power flashes 1x
•
Select with button [Set] the input type (displayed by LEDs Pt100 / U / I)
•
Press button [Down]
Parameterization
„input zero point“ >> LED Power flashes 2x
•
Select with button [Set] the zero point of
the input
Number of
LED
flashes
Pt100
U
I
1 x
- 200 °C
0 V
0 mA
2 x
- 50 °C
2 V
4 mA
3 x
0 °C
4 x
100 °C
5 x
200 °C
•
Press button [Down]
Parameterization
„input full scale“ (only for Pt100 input) >> LED Power flashes 3x
•
Select with button [Set] the full scale of
the input
Number of
LED
Number of
LED
flashes
Pt100
flashes
Pt100
1 x
0 °C
5 x
200 °C
2 x
50 °C
6 x
250 °C
3 x
100 °C
7 x
300 °C
4 x
150 °C
8 x
400 °C
9 x
500 °C
•
Press button [Down]
Parameterization
„output“ >> LED Power flashes 4x
•
Select with button [Set] the output range
Number of
LED
flashes
U / I
1 x
0 - 10V / 0 - 20mA
2 x
2 - 10V / 4 - 20mA
•
Press button [Down]
End of parameterization, Power LED lights permanently