11 Malfunctions / trouble shooting
A momentary pending alarm or error message appears alternately with the standard display.
Display
Cause
Adjustment
All displays remain con-
stantly off
Defect in device
•
Not possible to remedy. Replace-
ment necessary.
Fuse defective
•
Check the fuse, if applicable, re-
place it
Display line not pluggedin
•
Check the plug-in connections
Overtemp.
Room temperature lies above the set max-
imum temperature
•
Check the room temperature
Interruption of the sensor leadto input
“
E1
”
•
Check the set maximum temper-
ature
•
Check the sensor leadandconnec-
tion
Undertemp
Room temperature lies below the set mini-
mum temperature
•
Check the room temperature
•
Check the set minimum temperature
EEPROM
damaged parameter memory
•
Not possible to remedy. Replace-
ment of device necessary.
Fan
Fault message from fan terminals D3 (TB)
interrupted
•
Setting of the connectedfans to
function
•
Check whether motor circuit break-
er is on
•
Check the fault message line
Sensor E2
Short-circuit or interruption in the sensor
leadto input
“
E2
”
•
Check the sensor leadandconnec-
tion
E3
Short-circuit or interruption in the sensor
leadto input
“
E3
”
•
Check the sensor leadandconnec-
tion
Messages in operation as master
Common alarm
General alarm via Bus.
Example for fault on device no. 4
•
Check the device with fault
Buserror
Bus connection interrupted
Example for interruption on device no. 2
•
Check all stall numbers
•
Checking the Bus connections
•
Checking of voltage supply
Exhaust air sum
Exhaust air volume of 100 % was ex-
ceeded
(totalling function)
•
Check the exhaust air percentages
on every regulator (
“
fan
”
Exhaust air
percentage
“
) They may not add up
to more than 100 %.
Operating Instructions
UNIcon / Acontrol
Malfunctions / trouble shooting
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
71/83