Parameter
Factory set-
ting
Cot 1 Cot 2
Cot 3
Cot 4
Cot 5
Information
Heating1 / Heating2
H1 Offset*
-2.0 K
H1 Hysteresis
0.5 K
H1 Pband- - - - -
H1 Minimum
- - - - -
H1 maximum
- - - - -
H2 Setpoint
- - - - -
H2 Offset
- - - - -
H2 Hysteresis
- - - - -
H2 Pband- - - - -
H2 Minimum
- - - - -
H2 maximum
- - - - -
Day of program
Actual day
0 Day
Curve program
OFF
Knick point1
10 Day
Knick point2
60 Day
Final day
120 Day
Setpoint curve
ON
Setpoint start
26.0
°
C
Setpoint knick1
24.0
°
C
Setpoint knick2
23.0
°
C
Setpoint
nal
20.0
°
C
Minimum curve
ON
Min. start
10 %
Min. knick1
12 %
Min. knick2
17 %
Min.
nal
25 %
Maximum curve
ON
Max. start
75 %
Max. knick1
80 %
Max. knick2
90 %
Max.
nal
100 %
Heating1 curve
ON
Heating1 start
0.0 K
Heating1 knick1
-1.0 K
Heating1 knick2
-1.5 K
Heating1
nal
-2.0 K
Heating2 curve
OFF
Heating2 start
24.0
°
C
Heating2knick1
23.0
°
C
Heating2knick2
22.0
°
C
Heating2
nal
21.0
°
C
- = Only display, no adjustment possible
* = at alternative temperature source (E2, E3 or Bus) setting as Setpoint
Operating Instructions
UNIcon / Acontrol
Menu tables
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
66/83