Variant 3:
Two regulated groups with different amounts of air
This variant provides for an increase in speed of group
1 (on the regulator) up to a percentage (switch-on
point) of the control range. When the connection point
of group 2 is reached, the group 1 holds the speed.
The second(smaller) group switches on andis slowly
turnedup.
Following settings are without function:
- Group1 100 %
- Off group2
- Minimum2
25.09.2008
v_dia_group_varia3.vsd
100%
GAM
G1
G1
100%
G2
100%
G1 100%: 50%
ON G2: 50%
OFF G2: 45 %
Min. G2: 20%
G1 100%: 40%
nM
[%]
G1 Group1
G2 Group2
Min. G2 Minimum2
nM Motor speed
GAM Total exhaust air volume
Variant 2 (example with 4 groups)
Group 1 (power unit) is a regulatedfan group, group 2,3 4 and4 are unregulatedandoperateddirectly on the mains. The group
control is performedby the
“
master
”
but because this does not have enough free relay outputs, 2 relays of
“
slave
”
units are
used.
In the
“
IO Setup
”
the functions which are executeddirectly by the
“
master
”
are programmed. The functions which are distributed
to the
“
slave
”
units must be set
on the
“
master
”
under
“
Bus
”
.
Group3(9)
M
1 ~
Bus
26.09.2008
v_anschl_group_varia2.vsd
M
1 ~
PTE-6/10AHQX-L
CTE/AHX-L
PTE-6/10AHQX-L
K3
K3
K3
1~ 230 V
50/60 Hz
1~ 230 V
50/60 Hz
M
1 ~
M
1 ~
GND
GND D+
D+
D+
D-
GND
D-
D-
N
N
N
N
N
N
L1
L1
L1
L1
L1
L1
U1
U2
31
31
31
32
32
32
1
Master = Address 1
2
Slave = Address 2
3
Slave = Address 3
1~ 230 V
50/60 Hz
G1
G2
G3
G4
1 Master = Address 1
2 Slave = Address 2
3 Slave = Address 3
G1 Group1stepless controlled (IO Setup function U1/PWM = code 7)
G2 Group2 (IO Function K3 = Code 8)
G3 Group3 (IO Setup function K3 = code 17 for bus controlled)
G4 Group4 (IO Setup function K3 = code 17 for bus controlled)
Address 2 (Slave1) = K3
Grou(9) = IO Function
Group4(10)
Address 3 (Slave2) = K3
Group4(10)= IO Function
Group 1 behaves in such a way that its speedrises constantly until the switch-on point of group 2 On reaching the connection
point for group 2 its relay switches on andthe speedof the
rst group is reduced to an adjustable
“
Minimum2
”
.
If the ventilation requirement increases further, the speedof the
rst groups rises again to
“
100 %
”
, then the group 3 is
connectedandthe
rst group is reduced to
“
Minimum3
”
. andso on.
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
33/83