9.2.5
For mode
2.03
: Relay output for Heating or Cooling
OffsetDigitalOut
OffsetDigitalOut
Offset Digital Out = Offset for relay output (
“
K2
”
is pre-programmed by the factory).
The relay operating point deviates by the adjusted offset of the Setpoint of the ventila-
tion (if relay
“
K2
”
not inverted, terminal
“
21
”
-
“
24
”
bridged).
Setting range: -10.0...+10.0 K
Factory setting: -1.0 K
•
“
0.0 K
”
set, i.e. heating
“
ON
”
when: actual value = Setpoint
•
During negative offset value heating
“
ON
”
when: actual value = Setpoint - offset
•
During positive offset value heating
“
ON
”
when: actual value = Se offset
Hyst.DigitalOut
Hyst.DigitalOut
Switching hysteresis of the relay
Setting range: 0...10 K, Factory setting: 1.0 K (Kelvin)
Temperature variation with factory setting
|
9K
|
in IO Setup e. g. for controlling a Heating.
If the ambient temperature is lower than the set operating point, the heating remains switched on. If
the ambient temperature exceeds the set operating point of the heating by 2 K (Kelvin), the heating is
switched off. I.e., the release point is situated at the hysteresis value over the operating point.
Example:
Setpoint 15.0
°
C, 5.0 K, Hysteresis 2.0 K
Example:
Setpoint 20.0
°
C, Offset -5.0 K, Hysteresis 2.0 K
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
ON
ON
ON = 15°C + 5 K = 20 °C
OFF = 20°C + 2 K = 22 °C
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
h
e
iz
e
n
_
9
k
_
p
o
s
_
o
ff
s
e
t.
v
s
d
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
OFF = 15°C + 2 K = 17 °C
ON = 20°C - 5K = 15 °C
ON
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
h
e
iz
e
n
_
9
k
_
n
e
g
_
o
ff
s
e
t.
v
s
d
E1 Actual
The activated heating is indicated over the
fi
re symbol in the display.
Temperature variation with reprogramming to
|
10K
|
for
“
K2
”
in IO Setup, e.g., for activation of
the Cooling
Example:
Setpoint 15.0
°
C, 5.0 K, Hysteresis 2.0 K
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
ON
ON
ON = 15°C + 5 K = 20 °C
OFF = 20°C - 2 K = 18 °C
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
k
u
e
h
le
n
_
1
0
k
_
p
o
s
_
o
ff
s
e
t.
v
s
d
If the ambient temperature is higher than the set operat-
ing point, the cooling remains switched on. If the ambient
temperature falls below the set operating point of the
cooling by 2 K (Kelvin), it is switched off. I.e., the OFF
point is situated at the hysteresis value under the ON
point.
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008