8K
Group control (Group 2)
Switching on fans depending on modulation
12K *
Group control (Group 3)
Switching on fans depending on modulation
13K *
Group control (Group 4)
Switching on fans depending on modulation
For modes as controller higher
2.01
7K
Setpoint Offset
Deviation between actual value and setpoint to high
For modes as temperature controller with additional functions
2.03
9K
Heating function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis over switch ON point
10K
Cooling function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis below switch ON point
*
Function depending on the version of the software available
12
14
11
22
24
21
K1
K2
11.05.2007
v_relais_k1_k2.vsd
K1
1
= energized, terminals 11-14 bridged
0
= de-energized, terminals 11-12 bridged
K2
1
= energized, terminals 21-24 bridged
0
= de-energized, terminals 21-22 bridged
Function Controller status
K1/ K2
1 = energized
0 = de-energized
Inverting
OFF
ON
1K
Operation without fault, line supply okay
1
0
2K
Fault with indication by relay
0
1
3K
Ext. Fault at digital input for external fault
1
0
4K
Over or falling below modulation
1
0
5K
over or falling below limits for input signal
“
E1
”
1
0
6K
over or falling below limits for input signal
“
E2
”
1
0
7K
setpoint deviation to high
1
0
8K
Activation of second group
1
0
12K
Activation of third group
1
0
13K
Activation of fourth group
1
0
9.10.5
Programming Add-on module type Z-Modul-B
Program the additional inputs and outputs likewise in
“
IO Setup
”
.
After connecting the module, the settings menus are automatically expanded to include the additional
inputs and outputs.
•
1 x analog input 0 - 10 V. For mode
1.01
without function, starting from
2.01
funktion
|
1E
|
or
|
2E
|
possible.
–
Function
|
1E
|
for external target value function.
–
Function
|
2E
|
for external manual operation.
•
1 x output 0 - 10 V (A2 / GND), Function programmable, e.g., for: Fixed voltage, proportional level
control, proportional input signal, group control, drive 2.
•
3x digital inputs (D3 / GND, D4 / GND, D5 / GND) function programmable, e.g.: Enable (ON / OFF),
external malfunction, output limitation, input 1/2, target value 1/2, internal/external preset, controller
/ manual operation, control-function reversal (
“
heating
”
/
“
cooling
”
).
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.
70/105