9.4.2
Setting for operation modes
4.01
...
4.03
•
4.01
pressure control, setpoint in Pa
•
4.02
and
4.03
Pressure control for ventilation systems setpoint depending on outdoor temper-
ature
Setting
Setting
Setpoint1
Setpoint1
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Setpoint 2
Setpoint 2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IOSetup).
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: in measuring range of sensor
Factory setting: 100 Pa
Min. Speed
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
Max. Speed
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed manual
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.