7.12.1
Factory setting allocations / possible allocations
Every input or output of the device can be assigned to any (suitable) control function. The following
assignments
|
Codes
|
are pre-programmed
at the factory
:
Relays 1 (Terminals 11 - 14 - 12)
K1
Fault
Code
|
3
|
Relays 2 (Terminals 21 - 24 - 22)
K2
Heating1
Code
|
1
|
Relays 3 (Terminals 31 - 34 - 32)
K3
Peak load fan
Code
|
4
|
Analog output 1 (0 - 10 V)
A1
Ventilation
Code
|
0
|
Analog output 2 (0 - 10 V)
A2
Throttle shutter
Code
|
2
|
Analog output 3 (0 - 10 V)
A3
Heating1
Code
|
1
|
Inverter output function
U1/U2
Ventilation
Code
|
0
|
Possibilities for allocation:
Function
Code
*
* These functions can be distributed to other
devices in a bus system by the
“
master
”
if the
inputs and outputs of the
“
master
”
are not suf
fi
-
cient. (
Installation Bus)
Ventilation
|
0
|
Heating1
|
1
|
Shutter
|
2
|
Fault
|
3
|
Max. load ON/OFF
|
4
|
Heating2
|
5
|
+++
|
6
|
Group1 *
|
7
|
Group2 *
|
8
|
Group3 *
|
9
|
Group4 *
|
10
|
Group5 *
|
11
|
Freshairshutter*
|
12
|
Heatexchange Inlet air *
|
13
|
Heat exchanger Bypass *
|
14
|
Max. load 0 - 10 V
|
15
|
Fan Operation
|
16
|
Bus controlled
|
17
|
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
The Installation menu
L-BAL-E139-GB 2022/03 Index 006
Part.-No.
41/92